ID-range 110000-110249

110005 - 110033

Troubleshooting classes

 

Description

This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer.

Reaction

Class

2

 

Solution

Class

8

Restart of NC-control necessary.

110034

Illegal denominator for damping value.

 

Description

The Eigen-damping (denominator) of simulation drives was initialized invalid.

Reaction

Class

1

Element is initialized by default value.

Solution

Class

1

Correct parameter list of axis.

Parameter

%1:

Logical axis number [-]

 

%2:

Incorrect value [-]

 

%3:

Limit value [-]

 

%4:

Corrected value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110035

Illegal numerator for damping value.

 

Description

The damping (numerator) of simulation drives was initialized invalid.

Reaction

Class

1

Element is initialized by default value.

Solution

Class

1

Correct parameter list of axis.

Parameter

%1:

Logical axis number [-]

 

%2:

Incorrect value [-]

 

%3:

Limit value [-]

 

%4:

Corrected value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110036

Illegal denominator for inner frequency.

 

Description

The Eigen-frequency (denominator) of simulation drives was initialized not valid.

Reaction

Class

1

Element is initialized by default value.

Solution

Class

1

Correct parameter list of axis.

Parameter

%1:

Logical axis number [-]

 

%2:

Incorrect value [-]

 

%3:

Limit value [-]

 

%4:

Corrected value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110037

Illegal numerator for inner frequency.

 

Description

The Eigen-frequency (numerator) of simulation drives was initialized not valid.

Reaction

Class

1

Element is initialized by default value.

Solution

Class

1

Correct parameter list of axis.

Parameter

%1:

Logical axis number [-]

 

%2:

Incorrect value [-]

 

%3:

Limit value [-]

 

%4:

Corrected value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110038

Illegal denominator for time constant.

 

Description

The time constant (denominator) of simulation drives was initialized invalid.

Reaction

Class

1

Element is initialized by default value.

Solution

Class

1

Correct parameter list of axis.

Parameter

%1:

Logical axis number [-]

 

%2:

Incorrect value [-]

 

%3:

Limit value [-]

 

%4:

Corrected value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110039

Illegal numerator for time constant.

 

Description

The time constant (numerator) of simulation drives was initialized not valid.

Reaction

Class

1

Element is initialized by default value.

Solution

Class

1

Correct parameter list of axis.

Parameter

%1:

Logical axis number [-]

 

%2:

Incorrect value [-]

 

%3:

Limit value [-]

 

%4:

Corrected value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110040

Simu drive: dead time exceeds maximum limit.

 

Description

The dead time of simulation drives was initialized invalid.

Reaction

Class

1

Element is initialized by default value.

Solution

Class

1

Correct parameter list of axis.

Parameter

%1:

Logical axis number [-]

 

%2:

Incorrect value [-]

 

%3:

Limit value [-]

 

%4:

Corrected value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110041

Simu drive: amplification factor is 0.

 

Description

The proportional gain for simulation drives was set to zero. This is an illegal value.

Reaction

Class

1

Element is initialized by default value.

Solution

Class

1

Correct parameter list of axis.

Parameter

%1:

Logical axis number [-]

 

%2:

Incorrect value [0.01/sec]

 

%3:

Corrected value [0.01/sec]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110042

D/A-converter resolution is illegal (numerator).

 

Description

The resolution for the digital/analog converter (numerator) is specified with zero. This value is illegal.

Reaction

Class

1

Element is initialized by default value.

Solution

Class

1

Correct parameter list of axis.

Parameter

%1:

Logical axis number [-]

 

%2:

Incorrect value [-]

 

%3:

Corrected value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110043

D/A-converter resolution is illegal (denominator).

 

Description

The resolution for the digital/analog converter (denominator) is specified with zero. This value is illegal.

Reaction

Class

1

Element is initialized by default value.

Solution

Class

1

Correct parameter list of axis.

Parameter

%1:

Logical axis number [-]

 

%2:

Incorrect value [-]

 

%3:

Corrected value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110048

SERCOS-drive: illegal type of protocol.

 

Description

The SERCOS telegram type S-0-00015 was specified with an illegal value.

Reaction

Class

1

Element is set to user defined telegram type 7.

Solution

Class

1

Correct parameter list of axis.

Parameter

%1:

Logical axis number [-]

 

%2:

Incorrect value [-]

 

%3:

Limit value [-]

 

%4:

Corrected value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110051

Illegal axis modifier for axis of type "TRANSLATOR".

 

Description

The axis mode P-AXIS-00015 (bit coded) is not set to linear for the given translatoric axis.

Reaction

Class

1

The axis mode is set to linear.

Solution

Class

1

Correction of axis parameter list

Parameter

%1:

Logical axis number [-]

P-AXIS-00016

%2:

Incorrect value [-]

P-AXIS-00015

%3:

Corrected value [-]

P-AXIS-00015

Error type

2, Error message by data transfer from parameter list into control device.

 

110052

Difference of modulo less than or equal to 0.

 

Description

The difference between upper P-AXIS-00126 and lower modulo limit P-AXIS-00127 is smaller 0. The modulo range for rotatory axis or spindles at least must be bigger 0.0001°.

Reaction

Class

1

The upper and lower modulo limit is initialized by a default value.

Solution

Class

1

 

Parameter

%1:

Logical axis number [-]

 

%2:

Incorrect value [0.1 µm or 0,0001°]

P-AXIS-00126 - P-AXIS-00127

%3:

Limit value [0.1 µm or 0,0001°]

 

%4:

Corrected value [0.1 µm or 0,0001°]

 

%5:

Corrected value [0.1 µm or 0,0001°]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110053

Axis modifier illegal.

 

Description

For a rotatory axis the axis mode P-AXIS-00015 (bit coded) at least must be set to linear / optimized alignment mode / modulo.

Reaction

Class

1

The axis mode is set to linear.

Solution

Class

1

Correction of axis parameter list

Parameter

%1:

Logical axis number [-]

P-AXIS-00016

%2:

Actual value [-]

P-AXIS-00015

%3:

Corrected value [-]

P-AXIS-00015

Error type

2, Error message by data transfer from parameter list into control device.

 

110054

Axis position greater than software limit switch.

 

Description

The given axis position P-AXIS-00017 is above the positive software limit switch P-AXIS-00178.

Reaction

Class

1

 

Solution

Class

6

Correct element in axis parameter list.

Parameter

%1:

Logical axis number [-]

 

%2:

Incorrect value [0.1 µm or 0,0001°]

 

%3:

Limit value [0.1 µm or 0,0001°]

 

%4:

Corrected value [0.1 µm or 0,0001°]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110055

Axis position smaller than software limit switch.

 

Description

The given axis position P-AXIS-00017 is below the negative software limit switch P-AXIS-00177.

Reaction

Class

1

 

Solution

Class

6

Correct element in axis parameter list.

Parameter

%1:

Logical axis number [-]

 

%2:

Incorrect value [0.1 µm or 0,0001°]

 

%3:

Limit value [0.1 µm or 0,0001°]

 

%4:

Corrected value [0.1 µm or 0,0001°]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110059

Limit of velocity for stand still is above maximum velocity of axis.

 

Description

The limit velocity P-AXIS-00216 for display of stand still is above the maximum axis velocity.

Reaction

Class

1

 

Solution

Class

1

 

Parameter

%1:

Logical axis number [-]

 

%2:

Incorrect value [0.1 µm or 0,0001°]

 

%3:

Limit value [0.1 µm or 0,0001°]

 

%4:

Corrected value [0.1 µm or 0,0001°]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110060

Unknown drive type.

 

Description

The given axis type P-AXIS-00018 is unknown. Following types are valid:

1 – linear axis

2 – rotatory axis

4 – spindle

Reaction

Class

3

Stop of actual job.

Solution

Class

7

Set correct axis type in parameter list.

Parameter

%1:

Logical axis number [-]

 

%2:

Incorrect value [-]

 

Error type

-

 

110061

Turning rate at modulo error less than 0.

 

Description

The number of modulo revolutions P-AXIS-00125 is zero. For a active modulo compensation P-AXIS-00120 the revolutions must be bigger zero.

Reaction

Class

1

Initialization of Modulo revolutions with default value.

Solution

Class

1

Correct value in parameter list.

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [-]

 

%3:

Limit value [-]

 

%4:

Corrected value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110062

Axis number may not be changed after having started the system.

 

Description

The parameter P-AXIS-00016 for straightforward identification of axis in system cannot be changed while CNC kernel is running. The new logical axis number is not transferred, the previous active logical axis number remains valid.

Reaction

Class

1

None.

Solution

Class

1

Only change logical axis number P-AXIS-00016 in configuration mode or if CNC kernel does not run respectively.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [-]

Current value of P-AXIS-00016.

%3:

Corrected value [-]

Corrected value of P-AXIS-00016.

Error type

2, Error message by data transfer from parameter list into control device.

 

110063

Drive type may not be changed after having started the system.

 

Description

The parameter P-AXIS-00020 for drive type of axis cannot be changed while CNC kernel is running. The new drive type is not transferred, the previous active drive type remains valid.

Reaction

Class

1

None.

Solution

Class

1

Only change drive type P-AXIS-00020 in configuration mode or if CNC kernel does not run respectively.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [-]

Current value of P-AXIS-00020.

%3:

Corrected value [-]

Corrected value of P-AXIS-00020.

Error type

2, Error message by data transfer from parameter list into control device.

 

110064

All axis have to have different axis numbers.

 

Description

For two axes in system the same logical axis number setting P-AXIS-00016 is used. This is not allowed. The data transfer for the second axis with the same logical axis number is rejected.

Reaction

Class

1

None.

Solution

Class

1

Use for all the axes in system different logical axis numbers P-AXIS-00016.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [-]

Current logical axis number.

%3:

Corrected value [-]

Corrected logical axis number P-AXIS-00016.

Error type

2, Error message by data transfer from parameter list into control device.

 

110065

Unknown drive type.

 

Description

The given drive type is not known.

Reaction

Class

3

 

Solution

Class

7

Check P-AXIS-00020

Parameter

%1:

Logical axis number [-]

s. P-AXIS-00016

%2:

Incorrect value [-]

s. P-AXIS-00020

Error type

-

 

110066

Missing gear with specified number.

 

Description

Try to select an unknown gear step, e.g. by G112 X<gear step>.

Reaction

Class

3

 

Solution

Class

7

 

Parameter

%1:

Actual value [-]

Gear Stepp

%2:

Logical axis number [-]

 

%3:

Upper limit value [-]

Maximum number of gears

Error type

-

 

110067

Axis data for gear step incomplete.

 

Description

The parameter list of an axis is initialized incomplete. This can just happen, if the parameter set of an axis is passed in binary form to the CNC.

Reaction

Class

3

 

Solution

Class

7

 

Parameter

%1:

Logical axis number [-]

 

%2:

Incorrect value [-]

incorrect bit

Error type

2, Error message by data transfer from parameter list into control device.

 

110068

Hardware independent axis dates for position controller incomplete.

 

Description

The parameter list of an axis is initialized incomplete. This can just happen, if the parameter set of an axis is passed in binary form to the CNC.

Reaction

Class

3

 

Solution

Class

7

 

Parameter

%1:

Logical axis number [-]

 

%2:

Incorrect value [-]

incorrect bit

Error type

2, Error message by data transfer from parameter list into control device.

 

110069

Hardware dependent axis dates for position controller incomplete.

 

Description

The parameter list of an axis is initialized incomplete. This can just happen, if the parameter set of an axis is passed in binary form to the CNC.

Reaction

Class

3

 

Solution

Class

7

 

Parameter

%1:

Logical axis number [-]

 

%2:

Incorrect value [-]

incorrect bit

Error type

2, Error message by data transfer from parameter list into control device.

 

110070

Machine dates for path controller incomplete.

 

Description

The parameter list of an axis is initialized incomplete. This can just happen, if the parameter set of an axis is passed in binary form to the CNC.

Reaction

Class

3

 

Solution

Class

7

 

Parameter

%1:

Logical axis number [-]

 

%2:

Incorrect value [-]

incorrect bit

Error type

2, Error message by data transfer from parameter list into control device.

 

110071

Axis dates for acceleration and velocity precontrol incomplete.

 

Description

The parameter list of an axis is initialized incomplete. This can just happen, if the parameter set of an axis is passed in binary form to the CNC.

Reaction

Class

3

 

Solution

Class

7

 

Parameter

%1:

Logical axis number [-]

 

%2:

Incorrect value [-]

incorrect bit

Error type

2, Error message by data transfer from parameter list into control device.

 

110073

Parameters for digital drive interface incomplete.

 

Description

The parameter list of an axis is initialized incomplete. This can just happen, if the parameter set of an axis is passed in binary form to the CNC.

Reaction

Class

3

 

Solution

Class

7

 

Parameter

%1:

Logical axis number [-]

 

%2:

Incorrect value [-]

incorrect bit

Error type

2, Error message by data transfer from parameter list into control device.

 

110074

Parameters for manual operation mode incomplete.

 

Description

The parameter list of an axis is initialized incomplete. This can just happen, if the parameter set of an axis is passed in binary form to the CNC.

Reaction

Class

3

 

Solution

Class

7

 

Parameter

%1:

Logical axis number [-]

 

%2:

Incorrect value [-]

incorrect bit

Error type

2, Error message by data transfer from parameter list into control device.

 

110075

Parameters for position controller and interpolator incomplete.

 

Description

The parameter list of an axis is initialized incomplete. This can just happen, if the parameter set of an axis is passed in binary form to the CNC.

Reaction

Class

3

 

Solution

Class

7

 

Parameter

%1:

Logical axis number [-]

 

%2:

Incorrect value [-]

incorrect bit

Error type

2, Error message by data transfer from parameter list into control device.

 

110076

Axis number is 0.

 

Description

The logical number of the axis parameter list must not be zero.

Reaction

Class

3

 

Solution

Class

7

 

Parameter

%1:

Incorrect value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110077

Gear switch position exceeds positive software limit switch.

 

Description

The gear switch position P-AXIS-00078 exceeds the positive software limit switch P-AXIS-00178.

Reaction

Class

1

The gear switch position is set to the middle of both software limit switches.

Solution

Class

1

Correct of value in parameter list.

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [-]

 

%3:

Limit value [-]

 

%4:

Corrected value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110078

Gear switch position exceeds negative software limit switch.

 

Description

The gear switch position P-AXIS-00078 is below the negative software limit switch P-AXIS-00177.

Reaction

Class

1

The gear switch position is set to the middle of both software limit switches.

Solution

Class

1

Correct of value in parameter list.

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [-]

 

%3:

Limit value [-]

 

%4:

Corrected value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110079

maximum speed is not allowed to be 0.

 

Description

The maximum velocity of the axis is given by 0. The maximum velocity must be greater 0.

Reaction

Class

1

Initialization of parameter with default value.

Solution

Class

1

Correct value in parameter list.

Parameter

%1:

Logical axis number [-]

 

%2:

Incorrect value [1µm/sec or 0,001°/sec]

 

%3:

Corrected value [1µm/sec or 0,001°/sec]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110080

maximum speed is greater than maximum speed defined in "spezif.inc".

 

Description

The maximum velocity P-AXIS-00212 of the axis exceeds the maximum velocity of the CNC.

Reaction

Class

1

Initialization of parameter with maximum velocity of CNC.

Solution

Class

1

Correct value in parameter list.

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [1µm/sec or 0,001°/sec]

 

%3:

Limit value [1µm/sec or 0,001°/sec]

 

%4:

Corrected value [1µm/sec or 0,001°/sec]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110081

maximum acceleration is not allowed to be 0.

 

Description

The maximum acceleration P-AXIS-00008 of the axis is given by 0. The maximum acceleration must be greater 0.

Reaction

Class

1

Initialization of parameter with minimum acceleration of CNC value.

Solution

Class

1

Correct value in parameter list.

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [1µm/sec or 0,001°/sec]

 

%3:

Corrected value [1µm/sec or 0,001°/sec]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110082

maximum acceleration is greater than maximum value defined in "spezif.inc".

 

Description

The maximum acceleration P-AXIS-00008 of the axis exceeds the maximum acceleration of the CNC.

Reaction

Class

1

Initialization of parameter with default acceleration of CNC value.

Solution

Class

1

Correct value in parameter list.

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [1mm/sec^2 or 1°/sec^2]

 

%3:

Limit value [1mm/sec^2 or 1°/sec^2]

 

%4:

Corrected value [1mm/sec^2 or 1°/sec^2]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110083

Illegal SLOPE time.

 

Description

The value for the slope time P-AXIS-00201 is not valid.

Reaction

Class

1

Output of warning. The value for P-AXIS-00201 is set to the limit value.

Solution

Class

1

Choose value for P-AXIS-00201 bigger than the limit value.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [1 µsec]

Actual value of P-AXIS-00201.

%3:

Limit value [1 µsec]

Limit value of P-AXIS-00201.

%4:

Corrected value [1 µsec]

Corrected value of P-AXIS-00201.

Error type

2, Error message by data transfer from parameter list into control device.

 

110084

Rapid feed rate is not allowed to be 0.

 

Description

The rapid velocity P-AXIS-00209 of the axis is given by 0. The maximum velocity must be greater 0.

Reaction

Class

1

Initialization of parameter with default value.

Solution

Class

1

Correct value in parameter list.

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [1µm/sec or 0,001°/sec]

 

%3:

Corrected value [1µm/sec or 0,001°/sec]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110085

Rapid feed rate is greater than maximum feed rate.

 

Description

The rapid feed rate P-AXIS-00209 lies above the maximum velocity of the axis.

Reaction

Class

1

Initialization of parameter with maximum velocity of axis.

Solution

Class

1

Correct value in parameter list.

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [1µm/sec or 0,001°/sec]

 

%3:

Limit value [1µm/sec or 0,001°/sec]

 

%4:

Corrected value [1µm/sec or 0,001°/sec]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110086

Implausible contour resolution.

 

Description

The denominator of the resolution P-AXIS-00233 of the measurement system is given with zero. This value must be initialized unequal zero. The resolution of the measurement system is given as factor between P-AXIS-00234 / P-AXIS-00233 in increments per 0,1 µm or per 0,0001°.

Reaction

Class

1

Initialization of denominator with default value

Solution

Class

1

Correct value in parameter list

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [-]

 

%3:

Corrected value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110087

Implausible controller window.

 

Description

The size of the window P-AXIS-00236 was given with zero. The window is used to display the “in position” state information of an axis, if the position lag is smaller than the specified window.

Reaction

Class

1

Initialization of window with default value

Solution

Class

1

Correct value in parameter list

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [-]

 

%3:

Corrected value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110088

Acceleration step 1 is 0.

 

Description

The acceleration P-AXIS-00011 of the first Step of the linear slope (not jerk limited) is given with zero. The acceleration must be bigger 0.

Reaction

Class

1

Initialization of acceleration with default value

Solution

Class

1

Correct value in parameter list

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [1mm/sec^2 or 1°/sec^2]

 

%3:

Corrected value [1mm/sec^2 or 1°/sec^2]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110089

Acceleration step 1 is greater than maximum acceleration.

 

Description

The acceleration P-AXIS-00011 of the first Step of the linear slope (not jerk limited) is bigger than the maximum acceleration P-AXIS-00008 of the axis.

Reaction

Class

1

Limitation of acceleration with maximum value

Solution

Class

1

Correct value in parameter list

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [1mm/sec^2 or 1°/sec^2]

 

%3:

Upper limit value [1mm/sec^2 or 1°/sec^2]

 

%4:

Corrected value [1mm/sec^2 or 1°/sec^2]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110090

Acceleration step 2 is 0.

 

Description

The acceleration P-AXIS-00012 of the second Step of the linear slope (not jerk limited) is given with zero. The acceleration must be bigger 0.

Reaction

Class

1

Initialization of acceleration with default value

Solution

Class

1

Correct value in parameter list

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [1mm/sec^2 or 1°/sec^2]

 

%3:

Corrected value [1mm/sec^2 or 1°/sec^2]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110091

Acceleration step 2 is greater than maximum acceleration.

 

Description

The acceleration P-AXIS-00012 of the second Step of the linear slope (not jerk limited) is bigger than the maximum acceleration P-AXIS-00008 of the axis.

Reaction

Class

1

Limitation of acceleration with maximum value

Solution

Class

1

Correct value in parameter list

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [1mm/sec^2 or 1°/sec^2]

 

%3:

Upper limit value [1mm/sec^2 or 1°/sec^2]

 

%4:

Corrected value [1mm/sec^2 or 1°/sec^2]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110092

Acceleration limit step 1 is 0.

 

Description

The current limit acceleration P-AXIS-00005 of the first Step of the linear slope (not jerk limited) is given with zero. The acceleration must be bigger 0.

Reaction

Class

1

Initialization of acceleration with default value

Solution

Class

1

Correct value in parameter list

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [1mm/sec^2 or 1°/sec^2]

 

%3:

Corrected value [1mm/sec^2 or 1°/sec^2]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110093

Acceleration limit step 1 is greater than maximum acceleration.

 

Description

The current limit acceleration P-AXIS-00005 of the first Step of the linear slope (not jerk limited) is bigger than the maximum acceleration P-AXIS-00008 of the axis.

Reaction

Class

1

Limitation of acceleration with maximum value

Solution

Class

1

Correct value in parameter list

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [1mm/sec^2 or 1°/sec^2]

 

%3:

Upper limit value [1mm/sec^2 or 1°/sec^2]

 

%4:

Corrected value [1mm/sec^2 or 1°/sec^2]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110094

Acceleration limit step 2 is 0.

 

Description

The current limit acceleration P-AXIS-00006 of the second step of the linear slope (not jerk limited) is given with zero. The acceleration must be bigger 0.

Reaction

Class

1

Initialization of acceleration with default value

Solution

Class

1

Correct value in parameter list

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [1mm/sec^2 or 1°/sec^2]

 

%3:

Corrected value [1mm/sec^2 or 1°/sec^2]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110095

Acceleration limit step 2 is greater than maximum acceleration.

 

Description

The current limit acceleration P-AXIS-00006 of the second step of the linear slope (not jerk limited) is bigger than the maximum acceleration P-AXIS-00008 of the axis.

Reaction

Class

1

Limitation of acceleration with maximum value

Solution

Class

1

Correct value in parameter list

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [1mm/sec^2 or 1°/sec^2]

 

%3:

Upper limit value [1mm/sec^2 or 1°/sec^2]

 

%4:

Corrected value [1mm/sec^2 or 1°/sec^2]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110096

Switching feed rate is 0.

 

Description

The velocity limit P-AXIS-00221 for change between acceleration of the first and second step of the linear slope (not jerk limited) is given with 0. The value must be bigger 0.

Reaction

Class

1

Limitation of acceleration with maximum value

Solution

Class

1

Correct value in parameter list

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [1µm/sec or 0,001°/sec]

 

%3:

Corrected value [1µm/sec or 0,001°/sec]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110097

Switching feed rate is greater than maximum feed rate.

 

Description

The velocity limit P-AXIS-00221 for change between acceleration of the first and second step of the linear slope (not jerk limited) is bigger than the maximum acceleration P-AXIS-00008 of the axis.

Reaction

Class

1

Limitation of acceleration with maximum value

Solution

Class

1

Correct value in parameter list

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [1µm/sec or 0,001°/sec]

 

%3:

Upper limit value [1µm/sec or 0,001°/sec]

 

%4:

Corrected value [1µm/sec or 0,001°/sec]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110098

Switching feed rate is 0.

 

Description

The velocity limit P-AXIS-00211 for change between current limit acceleration of the first and second step of the linear slope (not jerk limited) is given with 0. The value must be bigger 0.

Reaction

Class

1

Limitation of acceleration with maximum value

Solution

Class

1

Correct value in parameter list

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [1µm/sec or 0,001°/sec]

 

%3:

Corrected value [1µm/sec or 0,001°/sec]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110099

Switching feed rate is greater than maximum feed rate.

 

Description

The velocity limit P-AXIS-00211 for change between current limit acceleration of the first and second step of the linear slope (not jerk limited) is bigger than the maximum acceleration P-AXIS-00008 of the axis.

Reaction

Class

1

Limitation of velocity with maximum value

Solution

Class

1

Correct value in parameter list

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [1µm/sec or 0,001°/sec]

 

%3:

Upper limit value [1µm/sec or 0,001°/sec]

 

%4:

Corrected value [1µm/sec or 0,001°/sec]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110100

Acceleration is 0.

 

Description

The acceleration P-AXIS-00001 of the non linear slope (jerk limited) is given with zero. The acceleration must be bigger 0.

Reaction

Class

1

Initialization of acceleration with default value

Solution

Class

1

Correct value in parameter list

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [1mm/sec^2 or 1°/sec^2]

 

%3:

Corrected value [1mm/sec^2 or 1°/sec^2]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110101

Acceleration is greater than maximum acceleration.

 

Description

The acceleration P-AXIS-00001 of the nonlinear slope (jerk limited) is bigger than the maximum acceleration P-AXIS-00008 of the axis.

Reaction

Class

1

Limitation of acceleration with maximum value

Solution

Class

1

Correct value in parameter list

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [1mm/sec^2 or 1°/sec^2]

 

%3:

Upper limit value [1mm/sec^2 or 1°/sec^2]

 

%4:

Corrected value [1mm/sec^2 or 1°/sec^2]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110102

Deceleration is 0.

 

Description

The deceleration P-AXIS-00002 of the non linear slope (jerk limited) is given with zero. The acceleration must be bigger 0.

Reaction

Class

1

Initialization of acceleration with default value

Solution

Class

1

Correct value in parameter list

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [1mm/sec^2 or 1°/sec^2]

 

%3:

Corrected value [1mm/sec^2 or 1°/sec^2]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110103

Deceleration is greater than maximum value.

 

Description

The deceleration P-AXIS-00002 of the nonlinear slope (jerk limited) is bigger than the maximum acceleration P-AXIS-00008 of the axis.

Reaction

Class

1

Limitation of acceleration with maximum value

Solution

Class

1

Correct value in parameter list

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [1mm/sec^2 or 1°/sec^2]

 

%3:

Upper limit value [1mm/sec^2 or 1°/sec^2]

 

%4:

Corrected value [1mm/sec^2 or 1°/sec^2]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110104

SLOPE time for increasing acceleration is too small.

 

Description

The (time for reaching the maximum acceleration P-AXIS-00196 (ramp time) of jerk limited slope is smaller than the minimal ramp time P-AXIS-00201 of the axis.

Reaction

Class

1

Limitation of ramp time with minimal value

Solution

Class

1

Correct value in parameter list

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [1 µsec]

 

%3:

Lower limit value [1 µsec]

 

%4:

Corrected value [1 µsec]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110105

SLOPE time for decreasing acceleration is too small.

 

Description

The time for decreasing the maximum acceleration P-AXIS-00196 to zero (ramp time) of jerk limited slope is smaller than the minimal ramp time P-AXIS-00201 of the axis.

Reaction

Class

1

Limitation of ramp time with minimal value

Solution

Class

1

Correct value in parameter list

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [1 µsec]

 

%3:

Lower limit value [1 µsec]

 

%4:

Corrected value [1 µsec]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

 

 

 

110106

SLOPE time for increasing deceleration is too small.

 

Description

The time for reaching the maximum deceleration P-AXIS-00198 (ramp time) of jerk limited slope is smaller than the minimal ramp time P-AXIS-00201 of the axis.

Reaction

Class

1

Limitation of ramp time with minimal value

Solution

Class

1

Correct value in parameter list

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [1 µsec]

 

%3:

Lower limit value [1 µsec]

 

%4:

Corrected value [1 µsec]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110107

SLOPE time for decreasing deceleration is too small.

 

Description

The time for decreasing the maximum deceleration P-AXIS-00197 to zero (ramp time) of jerk limited slope is smaller than the minimal ramp time P-AXIS-00201 of the axis.

Reaction

Class

1

Limitation of ramp time with minimal value

Solution

Class

1

Correct value in parameter list

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [1 µsec]

 

%3:

Lower limit value [1 µsec]

 

%4:

Corrected value [1 µsec]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110110

Difference of software limit switches is 0.

 

Description

The movement range between the software limit switches is zero.

Reaction

Class

1

The software limit switches are set to default values

Solution

Class

1

Correct value in parameter list.

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [-]

 

%3:

Actual value [-]

 

%4:

Incorrect value [-]

Actual range

%5:

Corrected value [-]

Corrected range

Error type

2, Error message by data transfer from parameter list into control device.

 

110111

Speed override is 0.

 

Description

The parameter P-AXIS-00109 for maximum axis specific velocity override is smaller than permissible minimum value.

The parameter value is set to default minimum value.

Reaction

Class

1

None.

Solution

Class

1

Parameter setting of P-AXIS-00109 bigger than or equal to lower limit value.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [-]

Current permille value P-AXIS-00109.

%3:

Corrected value [-]

Corrected permille value P-AXIS-00109.

Error type

2, Error message by data transfer from parameter list into control device.

 

110112

Speed override exceeds limit.

 

Description

The parameter P-AXIS-00109 for maximum axis specific velocity override is smaller than permissible minimum value.

The parameter value is set to default maximum value.

Reaction

Class

1

None.

Solution

Class

1

Parameter setting of P-AXIS-00109 smaller than or equal to upper limit value.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [-]

Current parameter value P-AXIS-00109.

%3:

Limit value [-]

Upper parameter limit value.

%4:

Corrected value [-]

Corrected parameter value P-AXIS-00109.

Error type

2, Error message by data transfer from parameter list into control device.

 

110113

Measuring feed rate is 0.

 

Description

The parameter P-AXIS-00215 for feed of measurement movement is smaller than minimum permissible value. The parameter value is set to default value.

Reaction

Class

1

None.

Solution

Class

1

Setting of feed for measurement bigger than minimum value.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [1µm/sec or 0,001°/sec]

Current feed for measurement movement P-AXIS-00215.

%3:

Corrected value [1µm/sec or 0,001°/sec]

Corrected feed for measurement movement P-AXIS-00215.

Error type

2, Error message by data transfer from parameter list into control device.

 

110114

Measuring feed rate exceeds limit.

 

Description

The parameter P-AXIS-00215 for feed of measurement movement is bigger than maximum permissible value. The parameter value is set to default value.

Reaction

Class

1

None.

Solution

Class

1

Setting of feed for measurement smaller than maximum value.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [1µm/sec or 0,001°/sec]

Current active feed for measurement P-AXIS-00215.

%3:

Limit value [1µm/sec or 0,001°/sec]

Upper limit for measurement feed.

%4:

Corrected value [1µm/sec or 0,001°/sec]

Corrected feed for measurement P-AXIS-00215.

Error type

2, Error message by data transfer from parameter list into control device.

 

110115

Number of gear step is 0.

 

Description

The parameter P-AXIS-00079 for active gear step after startup of CNC is set to zero. The gear step is set to default gear step.

Reaction

Class

1

None.

Solution

Class

1

Gear step bigger than 0.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [-]

Current value for gear step P-AXIS-00079.

%3:

Corrected value [-]

Corrected gear step P-AXIS-00079.

Error type

2, Error message by data transfer from parameter list into control device.

 

110116

Illegal measuring method. Only one method may be selected.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [-]

 

%3:

Actual value [-]

 

%4:

Corrected value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110117

Measuring via SERCOS-protocol only for kenngr.antr_typ equal to ANTR_TYP_SERCOS.

 

Description

Invalid parameter setting for P-AXIS-00116 for SERCOS -measurement is used.

The parameter P-AXIS-00116 is set to default value.

Reaction

Class

1

None.

Solution

Class

1

Only use parameter P-AXIS-00116 if drive type P-AXIS-00020 setting is SERCOS drive.

Parameter

%1:

Logical axis number [-]

Logical axis number of affected axis P-AXIS-00016.

%2:

Actual value [-]

Current value of P-AXIS-00020

%3:

Drive type [-]

Corrected value of P-AXIS-00116.

%4:

Corrected value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110118

At least one measuring method must be defined.

 

Description

If one axis is marked as measurement axis P-AXIS-00118 also the measurement method has to be parameterized. The parameter P-AXIS-00117 is set to value 1.

Reaction

Class

1

None.

Solution

Class

1

Depending on drive type P-AXIS-00020 at least one measurement method must be parameterized or P-AXIS-00118 must be set to zero.

Parameter

%1:

Logical axis number [-]

Logical axis number of affected axis P-AXIS-00016.

%2:

Corrected value [-]

Current drive type P-AXIS-00020.

Error type

2, Error message by data transfer from parameter list into control device.

 

110119

Assignment of 0 to parameter is not permitted.

 

Description

The parameter P-AXIS-00023 for control of display function in position controller is set to invalid value. The parameter P-AXIS-00023 is set to lower limit value.

Reaction

Class

1

None.

Solution

Class

1

Only use parameter setting of P-AXIS-00023 bigger than 0.

Parameter

%1:

Logical axis number [-]

Logical axis number of affected axis P-AXIS-00016.

%2:

Actual value [-]

Current value P-AXIS-00023.

%3:

Corrected value [-]

Corrected value P-AXIS-00023.

Error type

2, Error message by data transfer from parameter list into control device.

 

110120

Parameter value exceeds limit.

 

Description

The parameter P-AXIS-00023 for control of display function in position controller is set to invalid high value. The parameter P-AXIS-00023 is set to upper limit value.

Reaction

Class

1

None.

Solution

Class

1

Only use parameter setting of P-AXIS-00023 smaller than upper limit value.

Parameter

%1:

Logical axis number [-]

Logical axis number of affected axis P-AXIS-00016.

%2:

Actual value [-]

Current value P-AXIS-00023.

%3:

Limit value [-]

Upper limit value.

%4:

Corrected value [-]

Corrected value P-AXIS-00023.

Error type

2, Error message by data transfer from parameter list into control device.

 

110121

Illegal modifier of precontrol.

 

Description

The given kind of the feed forward control is incorrect. You just can specify the values (see P-AXIS-00223) described in the description.

Reaction

Class

1

 

Solution

Class

1

 

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [-]

Bit coded variable P-AXIS-00223

%3:

Limit value [-]

 

%4:

Corrected value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110122

Numerator of velocity feed forward factor is 0.

 

Description

The numerator of the factor for normalization of the velocity feed forward control P-AXIS-00228 was given with zero.

Reaction

Class

1

 

Solution

Class

1

 

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [-]

 

%3:

Corrected value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

Numerator is initialized with default value.

110123

Denominator of velocity feed forward factor is 0.

 

Description

The denominator of the factor for normalization of the velocity feed forward control P-AXIS-00226 was given with zero.

Reaction

Class

1

 

Solution

Class

1

 

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [-]

 

%3:

Corrected value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

Denominator is initialized with default value.

110124

Hand wheel resolution is smaller than lower limit.

 

Description

The axis specific resolution parameter with active manual mode P-AXIS-00025 has to set to value > 0.

Reaction

Class

1

None.

Solution

Class

1

Only use manual mode resolution P-AXIS-00025 > 0.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [-]

Current resolution P-AXIS-00025.

%3:

Corrected value [-]

Corrected resolution P-AXIS-00025.

Error type

2, Error message by data transfer from parameter list into control device.

 

110125

Maximum feed rate for manual mode is not allowed to be 0.

 

Description

The maximum velocity P-AXIS-00213 with active manual mode operation is zero. The maximum velocity is set to default value.

Reaction

Class

1

None.

Solution

Class

1

Maximum velocity setting for manual mode P-AXIS-00213 bigger than 0.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [1µm/sec or 0,001°/sec]

Current maximum velocity P-AXIS-00213.

%3:

Corrected value [1µm/sec or 0,001°/sec]

Corrected maximum velocity P-AXIS-00213.

Error type

2, Error message by data transfer from parameter list into control device.

 

110126

Maximum feed rate for manual mode exceeds limit.

 

Description

The maximum velocity P-AXIS-00213 with active manual mode operation exceeds upper limit value. The maximum velocity is set to default value.

Reaction

Class

1

None.

Solution

Class

1

Maximum velocity setting for manual mode P-AXIS-00213 smaller than P-AXIS-00212.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [1µm/sec or 0,001°/sec]

Current maximum velocity P-AXIS-00213.

%3:

Limit value [1µm/sec or 0,001°/sec]

Upper limit value of velocity.

%4:

Corrected value [1µm/sec or 0,001°/sec]

Corrected maximum velocity P-AXIS-00213

Error type

2, Error message by data transfer from parameter list into control device.

 

110127

Maximum feed rate for manual mode is not allowed to be 0.

 

Description

The acceleration P-AXIS-00009 for active manual mode operation is smaller than the minimum permissible value of the axis.

The acceleration is set to minimum permissible value.

Reaction

Class

1

None.

Solution

Class

1

Use acceleration setting bigger than minimum value.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [1mm/sec^2 or 1°/sec^2]

Current setting of P-AXIS-00009.

%3:

Corrected value [1mm/sec^2 or 1°/sec^2]

Corrected setting of P-AXIS-00009.

Error type

2, Error message by data transfer from parameter list into control device.

 

110128

Maximum feed rate for manual mode exceeds limit.

 

Description

The acceleration P-AXIS-00009 for active manual mode operation is bigger than the maximum acceleration P-AXIS-00008 of the axis.

The acceleration is limited to P-AXIS-00008.

Reaction

Class

1

None.

Solution

Class

1

Use acceleration setting smaller than P-AXIS-00008

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [1mm/sec^2 or 1°/sec^2]

Current setting of P-AXIS-00009.

%3:

Upper limit value [1mm/sec^2 or 1°/sec^2]

Upper limit value for acceleration P-AXIS-00008.

%4:

Corrected value [1mm/sec^2 or 1°/sec^2]

Limited acceleration P-AXIS-00009.

Error type

2, Error message by data transfer from parameter list into control device.

 

110129

Percentage for manual mode feed rate in manual mode too small.

 

Description

While active manual mode with parallel interpolation (G201) the axis dynamic values are distributed with percentage value between path interpolation and axis specific manual mode interpolator. The percentage share value of maximum velocity P-AXIS-00212 for manual mode interpolator is made via P-AXIS-00083.

The percentage share value of maximum velocity for manual mode is set to lower limit value.

Reaction

Class

1

None

Solution

Class

1

Percentage share value setting of P-AXIS-00083 bigger than lower limit value.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [0,1%]

Current percentage share value P-AXIS-00083.

%3:

Lower limit value [0,1%]

Lower limit value for percentage share value.

%4:

Corrected value [0,1%]

Corrected percentage share value P-AXIS-00083.

Error type

2, Error message by data transfer from parameter list into control device.

 

110130

Percentage for manual mode feed rate in manual mode too big.

 

Description

While active manual mode with parallel interpolation (G201) the axis dynamic values are distributed with percentage value between path interpolation and axis specific manual mode interpolator. The percentage share value of maximum velocity P-AXIS-00212 for manual mode interpolator is made via P-AXIS-00083.

The percentage share value of maximum velocity for manual mode is set to default upper limit value.

Reaction

Class

1

None.

Solution

Class

1

Percentage share value setting of P-AXIS-00083 smaller than upper limit value.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [0,1%]

Current percentage share value P-AXIS-00083.

%3:

Upper limit value [0,1%]

Upper limit value for percentage share value.

%4:

Corrected value [0,1%]

Corrected percentage share value P-AXIS-00083.

Error type

2, Error message by data transfer from parameter list into control device.

 

110131

Percentage for manual mode acceleration in manual mode too small.

 

Description

While active manual mode with parallel interpolation (G201) the axis dynamic values are distributed with percentage value between path interpolation and axis specific manual mode interpolator. The percentage share value of maximum acceleration P-AXIS-00008 for manual mode interpolator is made via P-AXIS-00082.

The percentage share value of maximum velocity for manual mode is set to lower limit value.

Reaction

Class

1

None.

Solution

Class

1

Percentage share value setting of P-AXIS-00082 bigger than lower limit value.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [0,1%]

Current percentage share value P-AXIS-00082.

%3:

Lower limit value [0,1%]

Lower limit value for percentage share value.

%4:

Corrected value [0,1%]

Corrected percentage share value P-AXIS-00082.

Error type

2, Error message by data transfer from parameter list into control device.

 

110132

Percentage for manual mode acceleration in manual mode too big.

 

Description

While active manual mode with parallel interpolation (G201) the axis dynamic values are distributed with percentage value between path interpolation and axis specific manual mode interpolator. The percentage share value of maximum acceleration P-AXIS-00008 for manual mode interpolator is made via P-AXIS-00082.

The percentage share value of maximum velocity for manual mode is set to upper limit value.

Reaction

Class

1

None.

Solution

Class

1

Percentage share value setting of P-AXIS-00082 smaller than upper limit value.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [0,1%]

Current percentage share value P-AXIS-00082.

%3:

Upper limit value [0,1%]

Upper limit value for percentage share value.

%4:

Corrected value [0,1%]

Corrected percentage share value P-AXIS-00082.

Error type

2, Error message by data transfer from parameter list into control device.

 

110133

Percentage for interpolation feed rate in manual mode too small.

 

Description

While active manual mode with parallel interpolation (G201) the axis dynamic values are distributed with percentage value between path interpolation and axis specific manual mode interpolator. The percentage share value of maximum velocity P-AXIS-00212 for path interpolator is made via P-AXIS-00095.

The percentage share value of maximum velocity for manual mode is set to lower limit value.

Reaction

Class

1

None.

Solution

Class

1

Percentage share value setting of P-AXIS-00095 bigger than lower limit value.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [0,1%]

Current percentage share value P-AXIS-00095.

%3:

Lower limit value [0,1%]

Lower limit value for percentage share value.

%4:

Corrected value [0,1%]

Corrected percentage share value P-AXIS-00095.

Error type

2, Error message by data transfer from parameter list into control device.

 

110134

Percentage for interpolation feed rate in manual mode too big.

 

Description

While active manual mode with parallel interpolation (G201) the axis dynamic values are distributed with percentage value between path interpolation and axis specific manual mode interpolator. The percentage share value of maximum velocity P-AXIS-00212 for path interpolator is made via P-AXIS-00095.

The percentage share value of maximum velocity for manual mode is set to upper limit value.

Reaction

Class

1

None.

Solution

Class

1

Percentage share value setting of P-AXIS-00095 smaller than upper limit value.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [0,1%]

Current percentage share value P-AXIS-00095.

%3:

Upper limit value [0,1%]

Upper limit value for percentage share value.

%4:

Corrected value [0,1%]

Corrected percentage share value P-AXIS-00095.

Error type

2, Error message by data transfer from parameter list into control device.

 

110135

Percentage for interpolation acceleration in manual mode too small.

 

Description

While active manual mode with parallel interpolation (G201) the axis dynamic values are distributed with percentage value between path interpolation and axis specific manual mode interpolator. The percentage share value of maximum acceleration P-AXIS-00008 for path interpolator is made via P-AXIS-00094.

The percentage share value of maximum velocity for manual mode is set to lower limit value.

Reaction

Class

1

None.

Solution

Class

1

Percentage share value setting of P-AXIS-00094 bigger than lower limit value.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [0,1%]

Current percentage share value P-AXIS-00094.

%3:

Lower limit value [0,1%]

Lower limit value for percentage share value.

%4:

Corrected value [0,1%]

Corrected percentage share value P-AXIS-00094.

Error type

2, Error message by data transfer from parameter list into control device.

 

110136

Percentage for interpolation acceleration in manual mode too big.

 

Description

While active manual mode with parallel interpolation (G201) the axis dynamic values are distributed with percentage value between path interpolation and axis specific manual mode interpolator. The percentage share value of maximum acceleration P-AXIS-00008 for path interpolator is made via P-AXIS-00094.

The percentage share value of maximum velocity for manual mode is set to upper limit value.

Reaction

Class

1

None.

Solution

Class

1

Percentage share value setting of P-AXIS-00094 smaller than upper limit value.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [0,1%]

Current percentage share value P-AXIS-00094.

%3:

Upper limit value [0,1%]

Upper limit value for percentage share value.

%4:

Corrected value [0,1%]

Corrected percentage share value P-AXIS-00094.

Error type

2, Error message by data transfer from parameter list into control device.

 

110137

Filtering time is not allowed to be 0 for operating mode "hand wheel".

 

Description

While active manual mode in operation mode handwheel the parameter P-AXIS-00069 defines the number of CNC cycles which are used for average filtering of handwheel increments.

The parameter P-AXIS-00069 is set to default minimum value.

Reaction

Class

1

None.

Solution

Class

1

Only use filter time setting P-AXIS-00069 bigger than 0.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [1 µsec]

Current filter time P-AXIS-00069.

%3:

Corrected value [1 µsec]

Corrected filter time P-AXIS-00069.

Error type

2, Error message by data transfer from parameter list into control device.

 

110138

Filtering time exceeds limit for operating mode "hand wheel".

 

Description

While active manual mode in operation mode handwheel the parameter P-AXIS-00069 defines the number of CNC cycles which are used for average filtering of handwheel increments.

The parameter P-AXIS-00069 is limited by permissible maximum value.

Reaction

Class

1

None.

Solution

Class

1

Only use filter time setting P-AXIS-00069 smaller than upper limit value.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [1 µsec]

Current filter time P-AXIS-00069.

%3:

Upper limit value [1 µsec]

Corrected filter time P-AXIS-00069.

%4:

Corrected value [1 µsec]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110139

Rapid feed rate for operating mode "incremental mode" is 0.

 

Description

While active manual mode in operation mode continuous jog the parameter P-AXIS-00210 defines the rapid velocity.

The parameter P-AXIS-00210 is set to minimum value.

Reaction

Class

1

None.

Solution

Class

1

Only use setting for P-AXIS-00210 bigger than 0.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [1µm/sec or 0,001°/sec]

Current rapid velocity P-AXIS-00210.

%3:

Corrected value [1µm/sec or 0,001°/sec]

Corrected rapid velocity P-AXIS-00210.

Error type

2, Error message by data transfer from parameter list into control device.

 

110140

Rapid feed rate for operating mode "incremental mode" exceeds limit.

 

Description

While active manual mode in operation mode continuous jog the parameter P-AXIS-00210 defines the rapid velocity.

The parameter P-AXIS-00210 is set to maximum permissible value.

Reaction

Class

1

None.

Solution

Class

1

Only use setting for P-AXIS-00210 smaller than maximum value.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [1µm/sec or 0,001°/sec]

Current rapid velocity P-AXIS-00210.

%3:

Upper limit value [1µm/sec or 0,001°/sec]

Maximum permissible velocity.

%4:

Corrected value [1µm/sec or 0,001°/sec]

Corrected rapid velocity P-AXIS-00210.

Error type

2, Error message by data transfer from parameter list into control device.

 

110141

Incremental feed rate greater than maximum incremental feed rate.

 

Description

While active manual mode in operation mode continuous jog the parameter P-AXIS-00077 defines the continuous jog velocity.

The parameter P-AXIS-00077 is set to maximum permissible value.

Reaction

Class

1

None.

Solution

Class

1

Only use setting for P-AXIS-00077 smaller than maximum value.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [1µm/sec or 0,001°/sec]

Current velocity P-AXIS-00077.

%3:

Upper limit value [1µm/sec or 0,001°/sec]

Maximum permissible velocity.

%4:

Corrected value [1µm/sec or 0,001°/sec]

Corrected velocity P-AXIS-00077.

Error type

2, Error message by data transfer from parameter list into control device.

 

110142

Jog step distance has to be positive.

 

Description

While active manual mode in operation mode incremental jog the parameter P-AXIS-00232 defines the incremental jog path.

The parameter P-AXIS-00232 is set to minimum permissible value.

Reaction

Class

1

None.

Solution

Class

1

Only use setting for P-AXIS-00232 bigger than minimum value.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [0.1 µm or 0,0001°]

Current incremental jog path P-AXIS-00232.

%3:

Corrected value [0.1 µm or 0,0001°]

Corrected incremental jog path P-AXIS-00232.

Error type

2, Error message by data transfer from parameter list into control device.

 

110143

Jog step distance greater than maximum jog step distance.

 

Description

While active manual mode in operation mode incremental jog the parameter P-AXIS-00076 defines the jog velocity.

The parameter P-AXIS-00076 is set to maximum permissible value.

Reaction

Class

1

None.

Solution

Class

1

Only use setting for P-AXIS-00076 smaller than maximum value.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [1µm/sec or 0,001°/sec]

Current incremental jog velocity P-AXIS-00076.

%3:

Upper limit value [1µm/sec or 0,001°/sec]

Maximum permissible incremental jog velocity.

%4:

Corrected value [1µm/sec or 0,001°/sec]

Corrected incremental jog velocity P-AXIS-00076.

Error type

2, Error message by data transfer from parameter list into control device.

 

110144

Positive and negative manual mode offset limits are 0.

 

Description

Both positive and negative offset limits P-AXIS-00138, P-AXIS-00137 for movement range with active manual mode operation are zero. The offset limits are corrected according to specific limit values.

Reaction

Class

1

None.

Solution

Class

1

Setting of positive offset limit P-AXIS-00138 bigger than 0, setting of negative offset limit P-AXIS-00137 smaller than 0.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Corrected value [-]

Corrected value for positive offset limit P-AXIS-00138.

%3:

Corrected value [-]

Corrected value für negative offset limit P-AXIS-00137.

Error type

2, Error message by data transfer from parameter list into control device.

 

110145

Positive manual mode offset limit negative.

 

Description

The positive offset limit P-AXIS-00138 for positive movement range with active manual mode operation is smaller than 0. The offset limit is corrected according to specific default value.

Reaction

Class

1

None.

Solution

Class

1

Setting of positive offset limit P-AXIS-00138 bigger than 0

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [-]

Current value of P-AXIS-00138.

%3:

Corrected value [-]

Corrected value of P-AXIS-00138.

Error type

2, Error message by data transfer from parameter list into control device.

 

110146

Negative manual mode offset limit positive.

 

Description

The negative offset limit P-AXIS-00137 for negative movement range with active manual mode operation is positive. The offset limit is corrected according to specific default value.

Reaction

Class

1

None.

Solution

Class

1

Setting of negative offset limit P-AXIS-00137 smaller than 0

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [-]

Current value of P-AXIS-00137.

%3:

Corrected value [-]

Corrected value of P-AXIS-00137.

Error type

2, Error message by data transfer from parameter list into control device.

 

110147

maximum feed rate in machine reference search greater than vb_max.

 

Description

The fast homing speed for CNC controlled homing exceeds the maximum velocity of the axis.

Reaction

Class

1

The homing velocity is limited to the maximum velocity.

Solution

Class

1

 

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [1µm/sec or 0,001°/sec]

 

%3:

Limit value [1µm/sec or 0,001°/sec]

 

%4:

Corrected value [1µm/sec or 0,001°/sec]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110148

minimum feed rate in machine reference search greater than vb_max.

 

Description

The slow homing speed for CNC controlled homing exceeds the maximum velocity of the axis.

Reaction

Class

1

The homing velocity is limited to the maximum velocity.

Solution

Class

1

 

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [1µm/sec or 0,001°/sec]

 

%3:

Limit value [1µm/sec or 0,001°/sec]

 

%4:

Corrected value [1µm/sec or 0,001°/sec]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110149

minimum feed rate in machine reference search greater than maximum feed rate.

 

Description

The slow homing speed for CNC controlled homing exceeds the fast homing velocity.

Reaction

Class

1

The slow homing velocity is limited to the fast-homing velocity.

Solution

Class

1

 

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [1µm/sec or 0,001°/sec]

 

%3:

Limit value [1µm/sec or 0,001°/sec]

 

%4:

Corrected value [1µm/sec or 0,001°/sec]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110150

Amplifier factor is 0.

 

Description

The proportional gain was set to zero. This is an illegal value.

Reaction

Class

1

Element is initialized by default value.

Solution

Class

1

Correct parameter list of axis.

Parameter

%1:

Logical axis number [-]

 

%2:

Incorrect value [0.01/sec]

 

%3:

Corrected value [0.01/sec]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110151

D/A converter resolution (denominator) is 0.

 

Description

The resolution for the digital/analog converter (denominator) is specified with zero. This value is illegal.

Reaction

Class

1

Element is initialized by default value.

Solution

Class

1

Correct parameter list of axis.

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [-]

 

%3:

Corrected value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110153

Illegal value for minimum position lag/software limit switch.

 

Description

The minimal position lag limit P-AXIS-00169 is set to big. The value is limited by a quarter of the overall movement range (distance between negative and positive software limit switches).

Reaction

Class

1

Limitation to a quarter of movement range

Solution

Class

1

Decrease of value in parameter list.

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [0.1 µm or 0,0001°]

 

%3:

Limit value [0.1 µm or 0,0001°]

P-AXIS-00177, P-AXIS-00178

%4:

Corrected value [0.1 µm or 0,0001°]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110154

Dynamical position lag exceeds range of permissible values.

 

Description

The factor P-AXIS-00167 of the position lag monitoring has been initialized to big. The factor has dependent on the type of position lag monitoring P-AXIS-00172 an different meaning.

Reaction

Class

1

The position lag factor is limited by the maximum value.

Solution

Class

1

Decrease of value in parameter list.

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [-]

 

%3:

Limit value [-]

 

%4:

Corrected value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110162

Interpreter can not evaluate given list.

 

Description

CNC wants to evaluate an axis parameter list or compensation value list, which should be exist as file, but detects that the file doesn’t exist in path.

Reaction

Class

3

 

Solution

Class

1

· If the message appear during startup sequence the paths given by parameters P-STUP-00015 and P-STUP-00017 have to be checked.

· If the message appears after an order to access a file, check the path send by the order.

Error type

-

 

110163 - 110181

 

 

Description

This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer.

Reaction

Class

2

 

Solution

Class

8

Restart of NC-control necessary.

110182

Factor for spindle speed is 0.

 

Description

The given factor for the monitoring of the spindle revolution P-AXIS-00217 equals zero.

Reaction

Class

1

Value is initialized with a default.

Solution

Class

1

Correct value in parameter list.

Parameter

%1:

Logical axis number [-]

 

%2:

Incorrect value [-]

 

%3:

Corrected value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110183

Type of axis may not be changed after system booted.

 

Description

The parameter P-AXIS-00018 for type of axis cannot be changed while CNC kernel is running. The new axis type is not transferred, the previous active axis type remains valid.

Reaction

Class

1

None.

Solution

Class

1

Only change axis type P-AXIS-00018 in configuration mode or if CNC kernel does not run respectively.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [-]

Current value of P-AXIS-00018.

%3:

Corrected value [-]

Corrected value of P-AXIS-00018.

Error type

2, Error message by data transfer from parameter list into control device.

 

110184 - 110198

 

 

Description

This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer.

Reaction

Class

3

 

Solution

Class

8

Restart of NC-control necessary.

110199

Received unknown axis.

 

Description

 

Reaction

Class

3

 

Solution

Class

6

 

Parameter

%1:

Logical axis number [-]

 

Error type

-

 

110200 - 110209

 

 

Description

This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer.

Reaction

Class

2

 

Solution

Class

8

Restart of NC-control necessary.

110210

Corrected unknown type of axis to "ACHSTYP_TRANSLATOR".

 

Description

The axis type P-AXIS-00018 in the parameter list is not known.

Reaction

Class

1

The type is set to TRANSLATOR (=1)

Solution

Class

1

Correct value in parameter list.

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [-]

 

%3:

Corrected value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110211

Corrected unknown drive type to "ACHSTYP_SIMU".

 

Description

The specified drive type is unknown.

Reaction

Class

1

The type is set to SIMULATION (= 4)

Solution

Class

1

Correct value in parameter list.

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [-]

 

%3:

Corrected value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110212

 

 

Description

This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer.

Reaction

Class

3

 

Solution

Class

8

Restart of NC-control necessary.

110213

Unknown characteristic acceleration curve.

 

Description

An unknown type P-AXIS-00202 for acceleration characteristic curve was given. Following types are allowed:

0 – off

1 – Hyperbel 4. Grades

2 – Polynom 3. Grades

3 – corresponding to asynchronous motor 1/n or. 1/n²

Reaction

Class

1

Turn off type.

Solution

Class

1

Correct the type in the parameter list.

Parameter

%1:

Logical axis number [-]

 

%2:

Incorrect value [-]

 

%3:

Corrected value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110214

Limit of rotational speed is smaller than permissible value.

 

Description

The limit revolution P-AXIS-00103 for acceleration characteristic curve was given to big.

Reaction

Class

1

Turn off type.

Solution

Class

1

Correct the limit revolution in the axis list.

Parameter

%1:

Logical axis number [-]

 

%2:

Incorrect value [1µm/sec or 0,001°/sec]

 

%3:

Lower limit value [1µm/sec or 0,001°/sec]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110215

Acceleration limit is greater than permissible value.

 

Description

Acceleration limit P-AXIS-00007 of acceleration characteristic curve was specified to big. This value must not be above the maximum axis acceleration P-AXIS-00008.

Reaction

Class

1

Limitation of value

Solution

Class

1

Correct specified acceleration in the parameter list.

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [1µm/sec or 0,001°/sec]

 

%3:

Limit value [1µm/sec or 0,001°/sec]

 

%4:

Corrected value [1µm/sec or 0,001°/sec]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110216

Acceleration minimum is smaller than permissible value.

 

Description

Minimum acceleration P-AXIS-00010 of acceleration characteristic curve was specified to big. This value must not be above the constant acceleration P-AXIS-00007.

Reaction

Class

1

Limitation of value

Solution

Class

1

Correct specified acceleration in the parameter list.

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [1µm/sec or 0,001°/sec]

 

%3:

Limit value [1µm/sec or 0,001°/sec]

 

%4:

Incorrect value [1µm/sec or 0,001°/sec]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110217

Number of sections within list for leadscrew error compensation.

 

Description

Within the list for leadscrew error compensation there is the parameter P-COMP-00020 (see [COMP, Axis Compensation]) which is used to specify the number of entries into that list.

During interpretation of that list by the CNC it is checked if the specified number of list entries exceeds the lower or upper number of entries that are necessary or maximal possible to correctly use the leadscrew error compensation.

Reaction

Class

3

The reaction of the CNC depends whether the number given by P-COMP-00020 exceeds the lower or upper limit for the number of list entries.

If the value of P-COMP-00020 is

  • 0 CNC recovers using 2 entries that are initialized with 0
  • 1 CNC recovers adding internal 1 entry and initializes him with the data of the first entry.

· > obere Grenze
CNC takes the maximal number of entries that are possible (see parameter 2 of the message) to do the leadscrew error compensation.

Solution

Class

7

Check the value given by parameter P-COMP-00020.

The value must be≥2 und≤ the value that is displayed as parameter 2 of this message.

Parameter

%1:

Logical axis number [-]

From user by parameter P-COMP-00020 specified number of entries in the list for compensation of leadscrew errors.

%2:

Incorrect value [-]

Shows how many list entries are used to do the leadscrew error compensation.

%3:

Lower limit value [-]

 

%4:

Upper limit value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110218

Illegal grating of sections for leadscrew error compensation.

 

Description

The interval between 2 interpolation points out of the list with correction values for leadscrew error compensation is defined by parameter P-COMP-00009.

The message appears, because the value for the interval is < 0.

Reaction

Class

3

Correction of the value

Solution

Class

7

User has to define a value≥0 at parameter P-COMP-00009.

Parameter

%1:

Logical axis number [-]

The value the user defined at parameter P-COMP-00009.

%2:

Incorrect value [Increment]

The CNC uses this value instead the user defined value.

%3:

Lower limit value [Increment]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110219

Maximum speed of manual mode exceeds axis limit.

 

Description

The given maximum velocity for manual mode P-AXIS-00213 exceeds the general maximum velocity of the axis P-AXIS-00212.

Reaction

Class

1

Velocity is limited to maximum axis velocity.

Solution

Class

1

Correct parameter in axis list.

Parameter

%1:

Logical axis number [-]

 

%2:

Incorrect value [1µm/sec or 0,001°/sec]

 

%3:

Corrected value [1µm/sec or 0,001°/sec]

 

%4:

Instance [-]

Actual gear Step P-AXIS-00136

%5:

Upper limit value [1µm/sec or 0,001°/sec]

Maximum axis velocity P-AXIS-00212

Error type

2, Error message by data transfer from parameter list into control device.

 

110220

Rapid traverse rate of manual mode exceeds axis limit.

 

Description

The given maximum velocity for rapid speed manual mode P-AXIS-00210 exceeds the general maximum velocity of the axis P-AXIS-00212.

Reaction

Class

1

Velocity is limited to maximum axis velocity for rapid speed.

Solution

Class

1

Correct parameter in axis list.

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [1µm/sec or 0,001°/sec]

 

%3:

Corrected value [1µm/sec or 0,001°/sec]

 

%4:

Instance [-]

Actual gear Step P-AXIS-00136

%5:

Upper limit value [1µm/sec or 0,001°/sec]

Maximum axis velocity P-AXIS-00209

Error type

2, Error message by data transfer from parameter list into control device.

 

110221

Tip speed exceeds max. speed of axis.

 

Description

The given maximum velocity for continuous manual mode P-AXIS-00077 exceeds the general maximum velocity of the axis P-AXIS-00213.

Reaction

Class

1

 

Solution

Class

1

 

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [1µm/sec or 0,001°/sec]

 

%3:

Corrected value [1µm/sec or 0,001°/sec]

 

%4:

Instance [-]

Actual gear Step P-AXIS-00136

%5:

Upper limit value [1µm/sec or 0,001°/sec]

Maximum axis velocity in manual mode P-AXIS-00213

Error type

2, Error message by data transfer from parameter list into control device.

 

110222

Jog speed exceeds max. speed of axis.

 

Description

The given maximum velocity for incremental manual mode P-AXIS-00076 exceeds the general maximum velocity of the axis P-AXIS-00213.

Reaction

Class

1

 

Solution

Class

1

 

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [1µm/sec or 0,001°/sec]

 

%3:

Corrected value [1µm/sec or 0,001°/sec]

 

%4:

Instance [-]

Actual gear Step P-AXIS-00136

%5:

Upper limit value [1µm/sec or 0,001°/sec]

Maximum axis velocity in manual mode P-AXIS-00213

Error type

2, Error message by data transfer from parameter list into control device.

 

110225 - 110227

Troubleshooting classes

 

Description

This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer.

Reaction

Class

2

 

Solution

Class

8

Restart of NC-control necessary.

110228

Logical axis number in axis parameter list and in command-PDU not equal.

 

Description

CNC gets an order to parametrize an axis with a data set from a given list.

The message appears, because the number of the logical axis in the list isn’t the same as that of the axis.

Reaction

Class

3

Abort interpretation of the list.

Solution

Class

7

Check which list to use for axis parametrization. Maybe you must change the number of the logical axis in the list or have to use another list.

Parameter

%1:

Actual value [-]

Number of logical axis. The list that should be interpreted contains that number.

%2:

Expected value [-]

Number of logical axes, which should be parametrized with the values contained in list.

Error type

-

 

110229

Logical axis number in compensation data list and in command-PDU not equal.

 

Description

A logical axis should use a list with compensation values. Therefore this list is interpreted.

While interpreting it is detected, that the number of the logical axis of the compensation value list isn’t that number of the logical axis that should use this list.

Reaction

Class

3

Abort interpretation of the compensation value list.

Solution

Class

7

Check which list to use for compensation. Maybe you must change the number of the logical axis in the list or must use another list.

Parameter

%1:

Actual value [-]

Number of logical axes. The compensation list that should be interpreted contains that number (P-COMP-00001).

%2:

Expected value [-]

Number of logical axis, which should use the compensation list (P-STUP-00036).

Error type

-

 

110230

Number of gear steps of a C-axis out of range.

 

Description

In axis with axis type spindle P-AXIS-00018 the entry for default CAX gear step P-AXIS-00052 has invalid value. With use of CNC command < #CAX > this default gear step is used for the rotary C-axis.

The CAX gear step is set to default value.

Further information to CAX functionality see [PROG, Programming].

Reaction

Class

1

None.

Solution

Class

1

Use correct entry for default gear step P-AXIS-00052.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [-]

Current default gear step P-AXIS-00052.

%3:

Limit value [-]

Maximum value of gear step.

%4:

Corrected value [-]

Corrected value for default CAX gear step P-AXIS-00052.

Error type

2, Error message by data transfer from parameter list into control device.

 

110231

A translatory axis cannot be a C-axis.

 

Description

Within the axis mode P-AXIS-00015 (bit coded) the translatoric axis is specified as C-axis. This is just possible for rotatory axis or spindles.

Reaction

Class

1

The axis mode is set to linear. C-axis bit is cleared.

Solution

Class

1

Correction of axis parameter list

Parameter

%1:

Logical axis number [-]

P-AXIS-00016

%2:

Incorrect value [-]

P-AXIS-00015

%3:

Corrected value [-]

P-AXIS-00015

Error type

2, Error message by data transfer from parameter list into control device.

 

110232

hw_addr_index out of range.

 

Description

The given default hardware number of the gear step is not valid.

Reaction

Class

1

Hardware number is set to default value.

Solution

Class

1

Correct value in parameter list.

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [-]

 

%3:

Upper limit value [-]

 

%4:

Corrected value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110233 / 110234

 

 

Description

This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer.

Reaction

Class

3

 

Solution

Class

8

Restart of NC-control necessary.

110236

Led screw error compensation without correction value list.

 

Description

CNC detects inconsistent parametrization concerning leadscrew error compensation.

Within an axis configuration list by parameter P-AXIS-00175 leadscrew error compensation is activated.

Therefore, CNC expects correct data in which path to get a list with compensation values and what’s the name of file. User provides that data by parameter P-STUP-00016, P-STUP-00017, P-STUP-00036 of the startup list.

In the corresponding compensation value list it is necessary to provide correct values by parameter P-COMP-00001 and P-COMP-00020 for the leadscrew error compensation.

Reaction

Class

1

CNC deactivates lead screw error compensation.

Solution

Class

1

· Check parameters
P-STUP-00016
P-STUP-00017
P-STUP-00036
P-COMP-00001
P-COMP-00020 regarding consistent data.

· If you don’t need leadscrew error compensation set parameter P-AXIS-00175 to 0.

Parameter

%1:

Logical axis number [-]

Parameter P-AXIS-00016 from a axis configuration list which have lead screw error compensation configured by setting P-AXIS-00175 to 1.

Error type

2, Error message by data transfer from parameter list into control device.

 

110237

Order of filter too big.

 

Description

The specified order of the filter is too high.

Reaction

Class

1

Warning, the filter order is set to the maximum permissible value.

Solution

Class

1

Correct the filter order

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis

%2:

Actual value [-]

Number of the affected filter

%3:

Actual value [-]

Filter type

%4:

Incorrect value [-]

Invalid filter order

%5:

Corrected value [-]

Corrected filter order

Error type

2, Error message by data transfer from parameter list into control device.

 

110238

Filter prototype not permitted.

 

Description

The specified prototype of the filter is unknown.

Reaction

Class

1

The filter prototype is set to 1 (critical damping).

Solution

Class

1

Correct the filter prototype P-AXIS-00153

Parameter

%1:

Logical axis number [-]

Logical axis number of affected axis

%2:

Actual value [-]

Number of affected filter

%3:

Actual value [-]

Invalid filter prototype

%4:

Corrected value [-]

Corrected filter prototype P-AXIS-00153

Error type

2, Error message by data transfer from parameter list into control device.

 

110239

Filter type not permitted.

 

Description

The specified filter type is unknown. You just can specify the described filter types.

Reaction

Class

3

The filter is deactivated.

Solution

Class

7

Correct the filter type P-AXIS-00204

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis

%2:

Actual value [-]

Number of affected filters

%3:

Incorrect value [-]

Invalid filter type

Error type

2, Error message by data transfer from parameter list into control device.

 

110240

Filter share exceeds permissible range.

 

Description

The parameter defines the signal share in percent, which is processed by the filter. The given part for the signal is out of range.

Reaction

Class

1

The signal share is set to the corresponding limit (0 or 100 percent).

Solution

Class

1

 

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis

%2:

Actual value [0,1%]

Number of affected filter

%3:

Actual value [0,1%]

Invalid filter share P-AXIS-00164

%4:

Corrected value [-]

Corrected filter share P-AXIS-00164

Error type

2, Error message by data transfer from parameter list into control device.

 

110241

Acceleration at current limit is 0.

 

Description

The acceleration for rapid movements P-AXIS-00004 of the non linear slope (jerk limited) is given with zero. The acceleration must be bigger 0.

Reaction

Class

1

Initialization of acceleration with default value

Solution

Class

1

Correct value in parameter list

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [1mm/sec^2 or 1°/sec^2]

 

%3:

Corrected value [1mm/sec^2 or 1°/sec^2]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110242

Acceleration at current limit is greater than axis acceleration.

 

Description

The acceleration P-AXIS-00004 for rapid movements of the nonlinear slope (jerk limited) is bigger than the maximum acceleration P-AXIS-00008 of the axis.

Reaction

Class

1

Limitation of acceleration with maximum value

Solution

Class

1

Correct value in parameter list

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [1mm/sec^2 or 1°/sec^2]

 

%3:

Upper limit value [1mm/sec^2 or 1°/sec^2]

 

%4:

Corrected value [1mm/sec^2 or 1°/sec^2]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110243

Ramp time for acceleration at current limit too small.

 

Description

The time P-AXIS-00200 (ramp time) for in-/decreasing the maximum current limit acceleration P-AXIS-00004 of the jerk limited slope is smaller than the minimal ramp time P-AXIS-00201 of the axis.

Reaction

Class

1

Limitation of ramp time with minimal value

Solution

Class

1

Correct value in parameter list

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [1 µsec]

 

%3:

Lower limit value [1 µsec]

 

%4:

Corrected value [1 µsec]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110244

Logical axis number of master axis is missing for GANTRY operation.

 

Description

The axis is marked as slave axis of a gantry link with P-AXIS-00015 but the correct master axis entry P-AXIS-00070 is missing.

Reaction

Class

3

None.

Solution

Class

7

Use correct entry for logical axis number P-AXIS-00070 of leading master axis.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Logical axis number [-]

Current logical axis number of leading master axis P-AXIS-00070.

Error type

2, Error message by data transfer from parameter list into control device.