FB_CamAxis

FB_CamAxis 1:

This class (FB) defines a uniform coupling of cams to an axis via the TF8550 CurveEditor. Any instance can be assigned for operation during runtime.

FB_CamAxis 2:

Class is abstract

Since the class is defined as ABSTRACT, the class cannot be instantiated and must be implemented using inheritance.

Syntax:

FUNCTION_BLOCK ABSTRACT FB_CamAxis EXTENDS FB_Axis

FB_CamAxis 3: Properties

Name

Type

Access

Initial value

Description

Name

STRING

Get, Set

<SourceName>

Specifies the name of the class instance.

FB_CamAxis

EnableEnvelopeCurveAlarms

BOOL

Get, Set

FALSE

Enables monitoring of the actual curve in relation to the configured envelope.

FB_Axis

Axis

I_AxisBase

Get

NULL

Interface to the assigned TF8560 axis.

Referencing

I_Referencing

Get

<Local>

Functions for referencing the axis.

FB_Motion

Motion

I_MotionBase

Get

NULL

Interface to the assigned TF8560 motion object.

ErrorAlarmTL

TcEventSeverity

Get, Set

Error (3)

Severity of the alarm that the axis triggers in the error state.

Specific

I_MotionSpecific

Get

-

Technology-specific functions/values

FB_BaseMd

MachineData

I_MdBaseContainer

Get

-

Interface for machine data handling.

FB_Base

BaseState

E_BaseState

Get

eNotHandled

Initialization state of the class instance.

Error

BOOL

Get

FALSE

Class is in an error state.

ResultMessage

I_AppMessage

Get

-

Access to the class-internal EventLogger.

[PROTECTED] _Name

STRING

Get

<SourceName>

.Name without leading 'fb'.

1 Obsolete

FB_CamAxis 4: Methods

Name

Description

Reset()

Resets the error state of the class.

FB_CamAxis

SetCurve(iCurve)

Assign the curve to be used

FB_Axis

SetPosition(bCommand)

Setting the axis position with the FB_AxisHmi.Setposition.

FB_Motion

CheckAxisState()

Checks the current state of the axis.

FeedEnable(bFeedEnableP, bFeedEnableN)

Enable of a direction of movement.

JogNegative(bCommand)

Starts/stops a jog movement in negative direction.

JogPositive(bCommand)

Starts/stops a jog movement in positive direction.

Power(bCommand)

Switching on the drive control.

SetMotionRef(iMotion)

Assignment method for the TF8560 motion object.

FB_BaseMd

[PROTECTED] AddMdComp()

Adds a component of type I_MdComponent to the machine data container.

FB_Base

GetHMI()

Returns the assigned HMI object.

The method is not implemented in the FB_Base class. If the method is not overwritten by inheritance, a pseudo variable is always returned.

SetHMI(ipBase)

General assignment method for an FB_BaseHmi extending class as a local HMI.

The method is not implemented in the FB_Base class. If the method is not overridden by inheritance, it always fails.

[PROTECTED] _IsMyself(iCmp)

Identifies whether the transferred object corresponds to its own instance.

[PROTECTED] _QueryNamespace()

Extracts the first part of the instance path as an object namespace.

[PROTECTED] _QueryObjectName()

Extracts the last part of the instance path as the object name.

1 Is obsolete

FB_CamAxis 5: Possible events

ID

Description

Alarm/Message

11

Object error state

Alarm

21

Command rejected

Alarm

301x

Envelope limit exceeded

Alarm

10

Axis Errors

Alarm

20

Axis command rejected

Alarm

FB_CamAxis 6: Machine data

Component

Description

Index range

Number of instances

FB_MdFileInfo

File information

0x0000 Fxxx

1

FB_MdAxis

Applicative axis parameters

0x0000 1xxx

1

FB_MdNc

NC specific parameters, only if Specific.Nc.IsNc = TRUE

0x0000 22xx

1 (0)

FB_MdTrafo

Transformation-specific parameters, only if Specific.Trafo.IsTrafo = TRUE

0x0000 23xx

1 (0)

FB_MdHoming

Parameters for homing the axis

0x0000 3xxx

1

FB_CamAxis 7: Interfaces

Type

Description

I_Base

Standard interface on FB_Base.

I_CamAxis

Standard interface on FB_CamAxis.

I_Axis

Standard interface on FB_Axis.

I_Motion

Standard interface on FB_Motion

I_TwoTaskInterface

Runtime interface for two PLC tasks.

I_BaseMd

Standard interface on FB_BaseMd.

I_BaseDev

Covers all methods and properties of the base class.

I_Comparable

Enables comparisons via _IsMyself() or F_IsSameInstance().

Requirements

Development Environment

Target platform

PLC libraries to include

TwinCAT 4026 >= v3.1.4026.16
TwinCAT 4024 >= v3.1.4024.66

PC or CX (x64, x86)

Tc3_PlasticBaseApplication (>= v12.12.0.0)