Configuration data
Index 8000 ENC Settings 0 Ch.1
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
8000:0 | ENC Settings 0 Ch.1 | Maximum subindex | UINT8 | RO | 0x23 (35dec) |
8000:01 | The counter is reset via the C input. | BOOLEAN | RW | 0x00 (0dec) | |
8000:02 | Enable extern reset | A counter reset is triggered via the external latch input (24 V) | BOOLEAN | RW | 0x00 (0dec) |
8000:04 | 0: Disable gate | BIT2 | RW | 0x01 (1dec) | |
8000:06 | 0: 4-fold (quadruple evaluation) | BIT2 | RW | 0x00 (0dec) | |
8000:08 | 0: Enables input filter (inputs A, /A, B, /B, C, /C only) If a filter is enabled, a signal edge must be present for at least 2.4 µs in order to be counted as an increment. | BOOLEAN | RW | 0x01 (1dec) | |
8000:0A | When enabled, the terminal interpolates microincrements between the integer encoder increments in DC mode. | BOOLEAN | RW | 0x00 (0dec) | |
8000:0B | Error detection A | A wire break or short circuit on track A is indicated in index 0x6000:07 and as process data. Diagnostics is only possible, if the associated input is wired differentially. | BOOLEAN | RW | 0x01 (1dec) |
8000:0C | Error detection B | A wire break or short circuit on track B is indicated in index 0x6000:07 and as process data. Diagnostics is only possible, if the associated input is wired differentially. | BOOLEAN | RW | 0x01 (1dec) |
8000:0D | Error detection C | A wire break or short circuit on track C is indicated in index 0x6000:07 and as process data. Diagnostics is only possible, if the associated input is wired differentially. | BOOLEAN | RW | 0x00 (0dec) |
8000:0E | Activates reversion of rotation | BOOLEAN | RW | 0x00 (0dec) | |
8000:10 | Extern reset polarity | 0: Fall (with the falling edge the counter is set to zero) | BIT1 | RW | 0x01 (1dec) |
8000:11 | This is the minimum time over which the frequency is determined; The frequency is calculated from the number of increments (changes of position value) in the “frequency window” time interval. The determined frequency is output in index 0x6000:13 and as process data. The frequency calculation is carried out locally without distributed clocks function. | UINT16 | RW | 0x2710 (10000dec) | |
8000:13 | Scaling of the frequency measurement (must be divided by this value to obtain the unit in Hz): 100: "0.01 Hz" (default) | UINT32 | RW | 0x00000064 (100dec) | |
8000:14 | Period scaling | Resolution of the period value in the process data: 10: "10 ns" Period duration value is multiple of 10 ns | UINT32 | RW | 0x0000000A (10dec) |
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
8000:17 | Waiting time [ms] for frequency measurement If no full period is detected within the Frequency window, another frequency window is started to record a full period. This happens until the maximum frequency wait time has elapsed. At least double the period value of the minimum frequency to be measured should be entered here. t >= 2* (1 / fmin) | UINT16 | RW | 0x53E2 (21474dec) | |
8000:1D | Frequency numerator, | UINT32 | RW | 0x00000001 (1dec) | |
8000:1E | Frequency denominator, | UINT32 | RW | 0x00000001 (1dec) | |
8000:21 | Activation of plausibility check | BOOLEAN | RW | 0x00 (0dec) | |
8000:22 | FALSE: TRUE: | BOOLEAN | RW | 0x00 (0dec) | |
8000:23 | FALSE: TRUE: | BOOLEAN | RW | 0x00 (0dec) |
Index 8001 ENC Settings 1 Ch.1
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
8001:0 | ENC Settings 1 Ch.1 | Maximum subindex | UINT8 | RO | 0x23 (35dec) |
8001:17 | Setting the encoder supply 50dec: 5.0 V (default) Refer to the Note on setting the encoder supply | UINT32 | RW | 0x00000032 (50dec) | |
8001:19 | Filter settings: 10dec: 10 kHz | UINT32 | RW | 0x00001388 (5000dec) | |
8001:1A | Specifies the value for the upper counter limit. | UINT32 | RW | 0xFFFFFFFF (-1dec) | |
8001:1B | Specifies the value for the lower counter limit. | UINT32 | RW | 0x00000000 (0dec) | |
8001:1C | Enter the hysteresis in number of increments. A value greater than 0 must be selected. If the counter value exceeds the value, the bit in index 0x60n2:13 "Direction inversion detected" is set in the next PLC cycle. | UINT8 | RW | 0x0A (10dec) | |
8001:1D | 0: Encoder RS422 (diff. Input) | UINT32 | RW | 0x00000000 (0dec) | |
8001:1E | Input of the switching characteristics for output 1 0: TRUE=Push, FALSE=Pull | UINT8 | RW | 0x00 (0dec) | |
8001:1F | Input of the switching characteristics for output 2 0: TRUE=Push, FALSE=Pull | UINT8 | RW | 0x00 (0dec) | |
8001:20 | Input of the reference value for the switching value of output 1: 0: Counter value | UINT8 | RW | 0x00 (0dec) | |
8001:21 | Input of the reference value for the switching value of output 2: 0: Counter value | UINT8 | RW | 0x00 (0dec) | |
8001:22 | Setting the response time for short‑circuit/overload diagnostics at output 1 0: Disable | UINT8 | RW | 0x02 (2dec) | |
8001:23 | Setting the response time for short‑circuit/overload diagnostics at output 2 0: Disable | UINT8 | RW | 0x02 (2dec) |
Index 80n0 DIG Safe State Active Ch.n
(n = 2 for Ch.1; n = 3 for Ch.2)
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
80n0:0 | DIG Safe State Active Ch.n | Maximum subindex | UINT8 | RO | 0x01 (1dec) |
80n0:01 | Active | Enabling of the output state defined in index 0x80n1:01 in case of a bus error 0: Output keeps the current state. 1: Output is switched to the state defined in index 0x80n1. | BOOLEAN | RW | 0x01 (1dec) |
Index 80n1 DIG Safe State Value Ch.n
(n = 2 for Ch.1; n = 3 for Ch.2)
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
80n1:0 | DIG Safe State Value Ch.n | Maximum subindex | UINT8 | RO | 0x01 (1dec) |
80n1:01 | Value | Defines the state of the output in case of a bus error: 0: Output off | BOOLEAN | RW | 0x00 (0dec) |