Short circuit/overload diagnosis of outputs
Each output has its own short circuit/overload diagnosis.
Setting the response time per output | ||||
---|---|---|---|---|
Index (hex) | Name | Value | Name | Reaction time* |
8001:22 8001:23 | Diagnosis output Diagnosis output 2 | 0dec | Disable | Error detection disabled |
1dec | Fast | 10 ms | ||
2dec | Standard (default) | 500 ms | ||
3dec | Slow | 1 s | ||
*The reaction time applies to the LED display, the "Diag Messages" are sent max. every second regardless of the setting. |
If there is a short circuit/overload of the output, this is indicated as follows:
Error diagnosis in case of short circuit/overload of the output | Display |
---|---|
LED: |
|
0xA000:08 "Error output" 0xA000:09 "Error output 2" | TRUE |
DiagMessage, type "Error", text ID 0x8318 | Error output (channel %d, output %d) |