ANOUT1

ASCII - Command

ANOUT1

 

 

Syntax Transmit

ANOUT1 [Data]

 

Syntax Receive

ANOUT1 <Data>

Available in

 

Type

Variable rw

MMI

Yes

ASCII Format

Integer8

CANBus Object Number

350D (hex)

DIM

-

PROFIBUS PNU

1613 (dec) IND = 0000xxxx (bin)

Range

0 .. 8

DPR

13 (dec)

Default

1

 

Opmode

All

Data Type Bus/DPR

Integer8

Drive State

Disabled + Reset (Coldstart)

Weightning

 

Start Firmware

1.20

 

Configuration

Yes

Revision

1.8

Function Group

Analog I/O

EEPROM

Yes

Short Description

Configuration of the Analog Output 1

Description

Configuration of analog output 1. The actual value is read via MONITOR1. The output provides various analog setpoint values or actual values, depending on the selection in the operator software. Output resistor 2.2kOhm. Resolution 10 bit.

Status

Description

ANOUT1=0

No output voltage at Analog Output 1.

ANOUT1=1

Outputs the actual velocity (10V = VLIM).

ANOUT1=2

Outputs the actual current (10V = IPEAK).

ANOUT1=3

Outputs the velocity setpoint (10V = VLIM).

ANOUT1=4

Outputs the current setpoint (10V = IPEAK).

ANOUT1=5

Outputs the actual contouring error (10V = PEMAX).

ANOUT1=6

Outputs a value given by a option DPR-slotboard.
If a Device-Net option board is plugged in the drive, this setting enables access of Device-Net to analog output 1

ANOUT1=7

The actual position is at the analog output.
The scaling is reffered to the Modulo axes defined by SRND and ERND. This output makes sense, using the modulo axes type (POSCNFG=2).

ANOUT1=8

The analog output gives a constant voltage. The voltage can be set by using the help variable AN1TRIG in mV (starting with firmware 4.91)