ST_IEC870_5_101AcquisitionParams
From product version:
- TwinCAT PLC Library IEC60870-5-104 controlling station v1.0.0 and higher;
- TwinCAT PLC Library IEC60870-5-101 controlling station v1.0.1 and higher.
Configuration parameters for cyclic data acquisition. The initialisation sequence commands configured in the arrInitSeq array are executed once after receipt of M_EI_NA_1 (end of initialisation) or after the connection is established. The cyclic commands configured via the structure parameters testCmd, clockSync, arrGenro, arrCoro or genCmd are then executed.
TYPE ST_IEC870_5_101AcquisitionParams :
STRUCT
(* Initialization sequence steps *)
arrInitSeq : ARRAY[IEC870_MIN_ISTEP..IEC870_MAX_ISTEP] OF E_IEC870_5_101InitSeqStep :=
eIEC870_ISTEP_TEST, (* Send test command *)
eIEC870_ISTEP_CLOCK, (* Send clock synchronization command *)
eIEC870_ISTEP_GENRO, (* Send general interrogation command *)
eIEC870_ISTEP_CORO, (* Send counter interrogation command *)
eIEC870_ISTEP_UNUSED; (* Reserved *)(* Test command polling settings *)
testCmd : ST_IEC870_5_101TestPollParams := (
asduAddr := IEC870_ASDUADDR_SYSPARA,
tPollCycle := T#60s,
bEnable := TRUE );
(* Clock synchronisation polling settings *)
clockSync : ST_IEC870_5_101ClockPollParams := (
asduAddr := IEC870_ASDUADDR_SYSPARA,
tPollCycle := T#60s,
bEnable := TRUE );
(* Station interrogation polling settings *)
arrGenro : ARRAY[0..16] OF ST_IEC870_5_101GenroPollParams := (
asduAddr := IEC870_ASDUADDR_SYSPARA,
tPollCycle := T#60s,
eQOI := eIEC870_QOI_INROGEN,
bEnable := TRUE );
(* Counter interrogation polling settings *)
arrCoro : ARRAY[0..4] OF ST_IEC870_5_101CoroPollParams := (
asduAddr := IEC870_ASDUADDR_SYSPARA,
tPollCycle := T#60s,
eRQT := eIEC870_RQT_REQCOGEN,
eFRZ := eIEC870_FRZ_READ,
bEnable := TRUE );
(* General command acquisition settings *)
genCmd : ST_IEC870_5_101GenCmdPollParams := (
tPollCycle := T#1h,
bEnable := FALSE );
(* Delay command acquisition settings *)
delayCmd : ST_IEC870_5_101DelayPollParams := (
tDelay := T#5s );
eAODBType : E_IEC870_5_101AODBType := eIEC870_AODB_STATIC;
END_STRUCT
END_TYPE
arrInitSeq: Initialisation sequence. The initialisation sequence is always executed once after receipt of M_EI_NA_1 (end of initialisation) or after the connection is established.
testCmd: Parameter for cyclic test commands. Default: One test command every 60 seconds.
clockSync: Parameter for cyclic time synchronization commands. Default: Time synchronisation every 60 s.
arrGenro: Parameter for cyclic station query commands. Station queries for up to 17 datapoint groups may be configured. Default: One station query from the 'General' group every 60 s.
arrCoro: Parameter for cyclic counter query commands. Counter queries for up to 5 counter groups may be configured. Default: One counter query from the 'General' group every 60 s.
genCmd: Parameter for cyclic transmission of data points in controlling direction (single-commands, double-commands, setpoint-commands and so forth). Default: Execute all commands every 60 minutes.
delayCmd: Parameter for delay commands. Execution delay time of the next initialization step command. Default: Delay time = 5 s.
eAODBType: Application database type. This parameter defines how the data points are stored in the application database.
Example in ST:
In the following program section cyclic data acquisition is configured as follows: All initialisation steps are deactivated. The cyclic test command and time synchronisation command are also deactivated. In addition to the standard station query a further station query from group 1 is configured (every 100 s). In addition to the standard counter query, a counter query (freezing) from counter group 1 is configured (every 200 s).
PROGRAM P_AcquisitionConfig
VAR_IN_OUT
acqPara : ST_IEC870_5_101AcquisitionParams;
END_VAR
acqPara.arrInitSeq[0] := eIEC870_ISTEP_UNUSED;
acqPara.arrInitSeq[1] := eIEC870_ISTEP_UNUSED;
acqPara.arrInitSeq[2] := eIEC870_ISTEP_UNUSED;
acqPara.arrInitSeq[3] := eIEC870_ISTEP_UNUSED;
acqPara.arrInitSeq[4] := eIEC870_ISTEP_UNUSED;
acqPara.testCmd.bEnable := FALSE;
acqPara.clockSync.bEnable := FALSE;
acqPara.arrGenro[1].asduAddr := IEC870_ASDUADDR_SYSPARA;
acqPara.arrGenro[1].eQOI := eIEC870_QOI_INRO1;
acqPara.arrGenro[1].tPollCycle := T#100s;
acqPara.arrGenro[1].bEnable := TRUE;
acqPara.arrCoro[1].asduAddr := IEC870_ASDUADDR_SYSPARA;
acqPara.arrCoro[1].eFRZ := eIEC870_FRZ_FREEZE;
acqPara.arrCoro[1].eRQT := eIEC870_RQT_REQCO1;
acqpara.arrCoro[1].tPollCycle := T#200s;
acqPara.arrCoro[1].bEnable := TRUE;
Requirements
Development Environment | Target System | PLC Libraries to include |
|---|---|---|
TwinCAT v2.10.0 Build >= 1301 | PC or CX (x86, ARM) | TcIEC870_5_101.Lib |