M_TMR_TA_3
Time-tagged message with relative time.
- obj  | 
  | 
  | 
  | 
  | |||||||||
|---  | + head  | 
  | 
  | 
  | Reserved  | ||||||||
|---  | - ident  | 
  | 
  | 
  | |||||||||
|  | |---  | eType  | = 0x2 (2)  | = M_TMR_TA_3  | |||||||||
|  | |---  | bSQ  | 
  | = TRUE  | Sequence of information objects  | ||||||||
|  | |---  | nObj  | 
  | = 1  | Number of objects  | ||||||||
|  | |---  | eCOT  | 
  | 
  | |||||||||
|  | |---  | asduAddr  | 
  | 
  | Common address of asdu  | ||||||||
|  | |---  | eClass  | 
  | 
  | |||||||||
|---  | - info  | 
  | 
  | 
  | |||||||||
  | |---  | fc  | 
  | 
  | |||||||||
  | |---  | n  | 
  | 
  | |||||||||
  | |---  | stream  | 
  | 
  | |||||||||
  | 
  | |---  | length  | = 10  | 
  | ||||||||
  | 
  | |---  | data  | 
  | 7  | 6  | 5  | 4  | 3  | 2  | 1  | 0  | 
  | 
  | 
  | 
  | |---  | data[0] =  | 0  | 0  | 0  | 0  | 0  | 0  | DPI = Double-point information  | ||
  | 
  | 
  | |---  | data[1..2] =  | Relative time  | ||||||||
  | 
  | 
  | |---  | data[3..4] =  | Fault number  | ||||||||
  | 
  | 
  | |---  | data[5..8] =  | Four octets binary time tag  | ||||||||
  | 
  | 
  | |---  | data[9] =  | Supplementary information  | ||||||||
  | 
  | 
  | |---  | data[10..IEC870_MAX_ASDU_DATA_BYTE] =  | 
  | Reserved  | |||||||