Set values of the sequence controllers
In the sequence controllers the setpoints must be monotonically increasing: [Sp1] <= [Sp2] <= [Sp3] <= [Sp4] <= [Sp5] <=...<= [Spn]

[Sp1] | rPrSpHtg | Heating setpoint |
[Sp2] | rPrSpHtg | Heating setpoint |
[Sp3] | rPrSpErc | Setpoint for mixed air dampers |
[Sp4] | rPrSpErc | Setpoint for energy recovery |
[Sp5] | rPrSpCol | Cooling setpoint |