Input data
Index 6000 ENC Inputs Ch.1
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
6000:0  | ENC Inputs Ch.1  | Maximum subindex  | UINT8  | RO  | 0x25 (37dec)  | 
6000:01  | The counter value was stored with the zero pulse C input.  | BOOLEAN  | RO  | 0x00 (0dec)  | |
6000:02  | The counter value was stored via the Latch extern input.  | BOOLEAN  | RO  | 0x00 (0dec)  | |
6000:03  | The counter was set.  | BOOLEAN  | RO  | 0x00 (0dec)  | |
6000:04  | The value has fallen below the lower counter limit. The bit is reset when the counter value has fallen below 2/3 of the counting range.  | BOOLEAN  | RO  | 0x00 (0dec)  | |
6000:05  | The upper counter limit was exceeded. The bit is reset when the counter value has exceeded 1/3 of the counting range.  | BOOLEAN  | RO  | 0x00 (0dec)  | |
6000:06  | State of the status input (alarm "input 1")  | BOOLEAN  | RO  | 0x00 (0dec)  | |
6000:07  | Open circuit  | Indicates a wire break.  | BOOLEAN  | RO  | 0x00 (0dec)  | 
6000:08  | Extrapolation stall  | The extrapolated part of the counter is invalid.  | BOOLEAN  | RO  | 0x00 (0dec)  | 
6000:09  | Status of input A  | Status of input A  | BOOLEAN  | RO  | 0x00 (0dec)  | 
6000:0A  | Status of input B  | Status of input B  | BOOLEAN  | RO  | 0x00 (0dec)  | 
6000:0B  | Status of input C  | Status of input C  | BOOLEAN  | RO  | 0x00 (0dec)  | 
6000:0C  | The state of the gate input  | BOOLEAN  | RO  | 0x00 (0dec)  | |
6000:0D  | Status of the Latch extern input  | BOOLEAN  | RO  | 0x00 (0dec)  | |
6000:0E  | Sync Error  | The Sync error bit is only required for DC mode. It indicates whether a synchronization error has occurred during the previous cycle. This means a SYNC signal was triggered in the terminal, although no new process data were available (0 = OK, 1 = NOK).  | BOOLEAN  | RO  | 0x00 (0dec)  | 
6000:0F  | TxPDO State  | Only in Legacy mode: Validity of the data of the associated TxPDO (0 = valid, 1 = invalid).  | BOOLEAN  | RO  | 0x00 (0dec)  | 
6000:10  | TxPDO Toggle  | Only in Legacy mode: The TxPDO Toggle is toggled by the slave when the data of the associated TxPDO is updated.  | BOOLEAN  | RO  | 0x00 (0dec)  | 
6000:11  | Counter value  | UINT32  | RO  | 0x00000000 (0dec)  | |
6000:12  | Latch value  | UINT32  | RO  | 0x00000000 (0dec)  | |
6000:13  | The frequency (setting of the scaling in index 0x8000:13)  | UINT32  | RO  | 0x00000000 (0dec)  | |
6000:14  | The period value (setting of the scaling in index 0x8000:14)  | UINT32  | RO  | 0x00000000 (0dec)  | |
6000:16  | Timestamp of the last counter change  | UINT64  | RO  | 
  | |
6000:1F  | Timestamp of the last registered positive edge of zero pulse C  | UINT64  | RO  | 
  | 
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
6000:20  | Timestamp of the last edge (depending on the parameterization of the Latch input) at Latch extern.  | UINT64  | RO  | 
  | |
6000:21  | When the Gate/Latch input is used as Latch extern 2 input: Timestamp of the last edge (depending on the parameterization of the Gate/Latch input) at the Latch extern 2 input.  | UINT64  | RO  | 
  | |
6000:22  | Latch value of the Latch extern 2 input (Gate input is used as second Latch input)  | UINT32  | RO  | 0x00000000 (0dec)  | |
6000:23  | indicates the ratio of pulse duration / period value.  | UINT16  | RO  | 0x0000 (0dec)  | |
6000:24  | Duty cycle min  | Returns the smallest measured Duty cycle value  | UINT16  | RO  | 0x0000 (0dec)  | 
6000:25  | Duty cycle max  | Returns the largest measured Duty cycle value  | UINT16  | RO  | 0x0000 (0dec)  | 
Index 6002 ENC Inputs status Ch. 1
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
6002:0  | ENC Inputs status Ch. 1  | Maximum subindex  | UINT8  | RO  | 0x15 (21dec)  | 
6002:0D  | Diag  | Indicates that a new message is available in the "Diag History"  | BOOLEAN  | RO  | 0x00 (0dec)  | 
6002:0E  | TxPDO State  | Validity of the data of the associated TxPDO (0 = valid, 1 = invalid)  | BOOLEAN  | RO  | 0x00 (0dec)  | 
6002:0F  | Input cycle counter  | 2-bit counter for synchronization (incremented only if a new value is present)  | BIT2  | RO  | 0x00 (0dec)  | 
6002:11  | Software gate valid  | 0: Counter unlocked (index 0x70n0:09 "Set software gate" = FALSE) 1: Counter locked (index 0x70n0:09 "Set software gate" = TRUE)  | BOOLEAN  | RO  | 0x00 (0dec)  | 
6002:12  | 0: A new counter value can be stored in index 0x6000:22 "Latch value 2". 1: No further counter values are stored in 0x6000:22 "Latch value 2".  | BOOLEAN  | RO  | 0x00 (0dec)  | |
6002:13  | Indicates reversal of the counting direction  | BOOLEAN  | RO  | 0x00 (0dec)  | |
6002:14  | Status of the ext. Latch extern input  | BOOLEAN  | RO  | 0x00 (0dec)  | |
6002:15  | Indicates that the counter value lies outside the parameterized counter limits.  | BOOLEAN  | RO  | 0x00 (0dec)  | 
Index 60n3 ENC Inputs Ch.n (for n = 0 [output 1], n = 1 [output 2])
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
60n3:0  | ENC Inputs Ch.n  | Maximum subindex  | UINT8  | RO  | 0x02 (2dec)  | 
60n3:01  | Status of digital output  | Status of the digital output n  | BOOLEAN  | RO  | 0x00 (0dec)  | 
60n3:02  | Status of tristate  | Tristate status of the digital output n  | BOOLEAN  | RO  | 0x00 (0dec)  | 
Index 60n4 ENC Timestamps Output Ch.n (for n = 0 [output 1], n = 1 [output 2])
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
60n4:0  | ENC Timestamps Output Ch.n  | Maximum subindex  | UINT8  | RO  | 0x18 (24dec)  | 
60n4:11  | Timestamp 1  | Timestamp when switching the output if Threshold 1 is reached  | ULINT64  | RO  | 0x0 (0dec)  | 
60n4:12  | Timestamp 2  | Timestamp when switching the output if Threshold 2 is reached  | ULINT64  | RO  | 0x0 (0dec)  | 
60n4:13  | Timestamp 3  | Timestamp when switching the output if Threshold 3 is reached  | ULINT64  | RO  | 0x0 (0dec)  | 
60n4:14  | Timestamp 4  | Timestamp when switching the output if Threshold 4 is reached  | ULINT64  | RO  | 0x0 (0dec)  | 
60n4:15  | Timestamp 5  | Timestamp when switching the output if Threshold 5 is reached  | ULINT64  | RO  | 0x0 (0dec)  | 
60n4:16  | Timestamp 6  | Timestamp when switching the output if Threshold 6 is reached  | ULINT64  | RO  | 0x0 (0dec)  | 
60n4:17  | Timestamp 7  | Timestamp when switching the output if Threshold 7 is reached  | ULINT64  | RO  | 0x0 (0dec)  | 
60n4:18  | Timestamp 8  | Timestamp when switching the output if Threshold 8 is reached  | ULINT64  | RO  | 0x0 (0dec)  |