Output data
Index 7000 ENC Outputs Ch.1
Index (hex) | Name | Meaning | Data type | Flags | Default |
---|---|---|---|---|---|
7000:0 | ENC Outputs Ch.1 | Maximum subindex | UINT8 | RO | 0x11 (17dec) |
7000:01 | Enable saving via the zero pulse C input. | BOOLEAN | RO | 0x00 (0dec) | |
7000:02 | Enable saving via the Latch extern input with positive edge. | BOOLEAN | RO | 0x00 (0dec) | |
7000:03 | Set counter value | BOOLEAN | RO | 0x00 (0dec) | |
7000:04 | Enable saving via the Latch extern input with negative edge. | BOOLEAN | RO | 0x00 (0dec) | |
7000:08 | Enable counter value specification via the zero pulse C input | BOOLEAN | RO | 0x00 (0dec) | |
7000:09 | Locks the counter via a PLC variable 0: Counter is unlocked 1: Counter is locked | BOOLEAN | RO | 0x00 (0dec) | |
7000:0A | Activates the counter value specification via a positive edge at the Latch extern input. | BOOLEAN | RO | 0x00 (0dec) | |
7000:0B | Activates the counter value specification via a negative edge at the Latch extern input. | BOOLEAN | RO | 0x00 (0dec) | |
7000:0C | Enable saving via the Gate/Latch input with positive edge. | BOOLEAN | RO | 0x00 (0dec) | |
7000:0D | Enable saving via the Gate/Latch input with negative edge. | BOOLEAN | RO | 0x00 (0dec) | |
7000:11 | The counter value to be set via "Set counter" (index 0x7000:03). | UINT32 | RO | 0x00000000 (0dec) |
Index 70n1 ENC Control Output Ch.n (for n = 0 [output 1], n = 1 [output 2])
Index (hex) | Name | Meaning | Data type | Flags | Default |
---|---|---|---|---|---|
70n1:0 | ENC Control Output Ch.n | Maximum subindex | UINT8 | RO | 0x05 (5dec) |
70n1:01 | Set output via PLC | BOOLEAN | RO | 0x00 (0dec) | |
70n1:02 | Enable automatic switching function for the output. As soon as this is enabled, the preset switching state is ignored via the PLC variable. | BOOLEAN | RO | 0x00 (0dec) | |
70n1:03 | Set output via PLC | BOOLEAN | RO | 0x00 (0dec) | |
70n1:04 | Setting the bit disables the counting direction (forward): 0: Counting direction active (default) | BOOLEAN | RO | 0x00 (0dec) | |
70n1:05 | By setting the bit, the counting direction (backward) is disabled: 0: Counting direction active (default) | BOOLEAN | RO | 0x00 (0dec) |
Index 70n2 ENC Control 2 Output Ch.n (for n = 0 [output 1], n = 1 [output 2])
Index (hex) | Name | Meaning | Data type | Flags | Default |
---|---|---|---|---|---|
70n2:0 | ENC Control 2 Output Ch.n | Maximum subindex | UINT8 | RO | 0x11 (17dec) |
70n2:11 | Number of output events | Enter the number of currently valid threshold values. The value should be ≥ 1 to activate the first threshold. | UINT8 | RO | 0x00 (0dec) |
Index 70n3 ENC Output States Ch.n (for n = 0 [output 1], n = 1 [output 2])
Index (hex) | Name | Meaning | Data type | Flags | Default |
---|---|---|---|---|---|
70n3:0 | ENC Output states Ch.n | Maximum subindex | UINT8 | RO | 0x08 (8dec) |
70n3:01 | Input of the status which the output should assume when "Threshold 1” (0x70n4:11) is reached. | BOOLEAN | RO | 0x00 (0dec) | |
70n3:02 | Input of the status which the output should assume when "Threshold 2” (0x70n4:12) is reached. | BOOLEAN | RO | 0x00 (0dec) | |
70n3:03 | Input of the status which the output should assume when "Threshold 3" (0x70n4:13) is reached. | BOOLEAN | RO | 0x00 (0dec) | |
70n3:04 | Input of the status which the output should assume when "Threshold 4" (0x70n4:14) is reached. | BOOLEAN | RO | 0x00 (0dec) | |
70n3:05 | Input of the status which the output is to assume when "Threshold 5" is reached. | BOOLEAN | RO | 0x00 (0dec) | |
70n3:06 | Input of the status which the output is to assume when "Threshold 6" is reached. | BOOLEAN | RO | 0x00 (0dec) | |
70n3:07 | Input of the status which the output is to assume when "Threshold 7" is reached. | BOOLEAN | RO | 0x00 (0dec) | |
70n3:08 | Input of the status which the output is to assume when "Threshold 8" is reached. | BOOLEAN | RO | 0x00 (0dec) |
Index 70n4 ENC Threshold Output Ch.n (for n = 0 [output 1], n = 1 [output 2])
Index (hex) | Name | Meaning | Data type | Flags | Default |
---|---|---|---|---|---|
70n4:0 | ENC Threshold Output Ch.n | Maximum subindex | UINT8 | RO | 0x11 (17dec) |
70n4:11 | Threshold value 1 (32-bit) | UINT32 | RO | 0x00000000 (0dec) | |
70n4:12 | Threshold value 2 (32-bit) | UINT32 | RO | 0x00000000 (0dec) | |
70n4:13 | Threshold value 3 (32-bit) | UINT32 | RO | 0x00000000 (0dec) | |
70n4:14 | Threshold value 4 (32-bit) | UINT32 | RO | 0x00000000 (0dec) | |
70n4:15 | Threshold value 5 (32-bit) | UINT32 | RO | 0x00000000 (0dec) | |
70n4:16 | Threshold value 6 (32-bit) | UINT32 | RO | 0x00000000 (0dec) | |
70n4:17 | Threshold value 7 (32-bit) | UINT32 | RO | 0x00000000 (0dec) | |
70n4:18 | Threshold value 8 (32-bit) | UINT32 | RO | 0x00000000 (0dec) |
Index 70n5 ENC Duration Output Ch.n (for n = 0 [output 1], n = 1 [output 2])
Index (hex) | Name | Meaning | Data type | Flags | Default |
---|---|---|---|---|---|
70n5:0 | ENC Duration Output Ch.n | Maximum subindex | UINT8 | RO | 0x11 (17dec) |
70n5:11 | Switching duration in µs for which the output is to be switched when the value specified in "Threshold 1" (0x70n4:11) has been reached. 0: Status of the output remains until the next "Threshold" value is reached. Maximum switching duration: 24,000 µs | UINT32 | RO | 0x00000000 (0dec) | |
70n5:12 | Switching duration in µs for which the output is to be switched when the value specified in "Threshold 2" (0x70n4:12) has been reached. 0: Status of the output remains until the next "Threshold" value is reached. Maximum switching duration: 24,000 µs | UINT32 | RO | 0x00000000 (0dec) | |
70n5:13 | Switching duration in µs for which the output is to be switched when the value specified in "Threshold 3" (0x70n4:13) has been reached. 0: Status of the output remains until the next "Threshold" value is reached. Maximum switching duration: 24,000 µs | UINT32 | RO | 0x00000000 (0dec) | |
70n5:14 | Switching duration in µs for which the output is to be switched when the value specified in "Threshold 4" (0x70n4:14) has been reached. 0: Status of the output remains until the next "Threshold" value is reached. Maximum switching duration: 24,000 µs | UINT32 | RO | 0x00000000 (0dec) | |
70n5:15 | Switching duration in µs for which the output is to be switched when the value specified in "Threshold 5" (0x70n4:15) has been reached. 0: Status of the output remains until the next "Threshold" value is reached. Maximum switching duration: 24,000 µs | UINT32 | RO | 0x00000000 (0dec) | |
70n5:16 | Switching duration in µs for which the output is to be switched when the value specified in "Threshold 6" (0x70n4:16) has been reached. 0: Status of the output remains until the next "Threshold" value is reached. Maximum switching duration: 24,000 µs | UINT32 | RO | 0x00000000 (0dec) | |
70n5:17 | Switching duration in µs for which the output is to be switched when the value specified in "Threshold 7" (0x70n4:17) has been reached. 0: Status of the output remains until the next "Threshold" value is reached. Maximum switching duration: 24,000 µs | UINT32 | RO | 0x00000000 (0dec) | |
70n5:18 | Switching duration in µs for which the output is to be switched when the value specified in "Threshold 8" (0x70n4:18) has been reached. 0: Status of the output remains until the next "Threshold" value is reached. Maximum switching duration: 24,000 µs | UINT32 | RO | 0x00000000 (0dec) |