Process data
Main PDO
Selection of basic process data:
Fig.34: “Process data” tabA: Selection of data direction: input or output
B: Selection of (optional) PDOs (process data objects)
C: Explanatory notes for PDOs
Optional PDOs
Optional PDOs, in addition to the main PDO:
- PDO 1 (0x1A02):
- The frequency is determined over 10 ms (fixed) as a number of increments.
- The period (time interval between two positive edges of input A) is determined as often as possible in the unit 500 ns/digit. If no increment event occurs for approx.1.6 seconds, the frequency/period is set to 0.
- Window: A user-defined time window can be parameterized via CoE object 0x8001:02 with the unit 16 µs/digit. During this window time the encoder increments are counted and output in the process record window.
Process data description
Fig.35: Process data descriptionThe process data are generated from CoE objects 0x6000 (inputs) and 0x7000 (outputs).
- Status: Status bits (see section Control and status word)
- Value: Encoder position
- Latch: Latch position
- Frequency: Current calculated frequency
- Period: Period of the last possible measurement
The refresh rate depends on the cycle time and the applied frequency - Window: Number of edges counted during the timeframe
- Ctrl: Control bits (see section Control and status word)
- Value: Relevant counter value
![]() | Process data can be read via CoE but cannot be set. In the following descriptions, the corresponding CoE index is always included as a reference in addition to the name of the process data.
|
Further Information