Object description EL3208-0010

Object description EL3208-0010 1:

EtherCAT XML Device Description

The display matches that of the CoE objects from the EtherCAT XML Device Description. We recommend downloading the latest XML file from the download area of the Beckhoff website and installing it according to installation instructions.

Object description EL3208-0010 2:

Parameterization via the CoE list (CAN over EtherCAT)

The terminal is parameterized via the CoE - Online tab (double-click on the respective object) or via the Process Data tab (allocation of PDOs). Please note the following general CoE information when using/manipulating the CoE parameters: - Keep a startup list if components have to be replaced - Differentiation between online/offline dictionary, existence of current XML description - Use "CoE reload" for resetting changes

Object description EL3208-0010 3:

Relevant objects

The object description refers to the analog input terminals for Pt100 (RTD) in 1 to 8 channel versions. Observe the indices with regard to the objects relevant for the respective terminal (channel dependent).

Introduction

The CoE overview contains objects for different intended applications:

The following section first describes the objects required for normal operation, followed by a complete overview of missing objects.

Objects for commissioning

Index 1011 Restore default parameters

Index (hex)

Name

Meaning

Data type

Flags

Default value

1011:0

Restore default parameters

Restore default parameters

UINT8

RO

0x01 (1dec)

1011:01

SubIndex 001

If this object is set to "0x64616F6C" in the set value dialog, all backup objects are reset to their delivery state.

UINT32

RW

0x00000000 (0dec)

Index 80n0 RTD settings for 0 ≤ n ≤ 7 (Ch. 1 – 8)

Object description EL3208-0010 4:

The filter properties are set via index 0x8000:15 only

The filter frequencies are set centrally for all channels of the EL32xx terminals via index 0x8000:15 (channel 1).
The corresponding indices 0x80n00:15 of the EL3208-0010 have no parameterization function.

Index (hex)

Name

Meaning

Data type

Flags

Default

80n0:0

RTD Settings

Maximum subindex

UINT8

RO

0x1B (27dec)

80n00:01

Enable user scale

User scaling is active.

BOOLEAN

RW

0x00 (0dec)

80n00:02

Presentation

0: Signed presentation

1: Absolute value with MSB as sign
Signed amount representation

2: High resolution (1/100°C) [default for EL3201/2-00x0 high-precision terminals, see note!

BIT3

RW

0x00 (0dec)

80n00:05

Siemens bits

The S5 bits are shown in the three low-order bits (value 0x60n00:11)

Bit 0 = 1 ("Overange" or "Underrange")
Bit 1 (not used)
Bit 2 (not used)

BOOLEAN

RW

0x00 (0dec)

80n0:0A

Enable user calibration

Enabling of user calibration

BOOLEAN

RW

0x00 (0dec)

80n0:0B

Enable manufacturer calibration

Enabling of the manufacturer calibration

BOOLEAN

RW

0x01 (1dec)

80n00:11

User scale offset

User scaling offset

INT16

RW

0x0000 (0dec)

80n00:12

User scale gain

This is the gain of the user scaling.
The gain has a fixed-point representation with a factor of 2-16.
The value 1 corresponds to 65535 (0x00010000).

INT32

RW

0x00010000 (65536dec)

80n00:15

Filter settings

This object determines the digital filter settings, if it is activated via Enable filter (index 0x80n00:06).

The possible settings are sequentially numbered.

UINT16

RW

0x0000 (0dec)

0: 50/60 Hz 120 ms

1: 4 ms

2: 8 ms

3: 16 ms

4: 32 ms

5: 40 ms

6: 48 ms

7: 60 ms

8: 101 ms

9: 120 ms

10: 50/60 Hz

11: 160 ms

12: 200 ms

13: 240 ms

14: 320 ms

15: 480 ms

80n00:17

User calibration offset

User calibration offset

INT16

RW

0x0000 (0dec)

80n00:18

User calibration gain

User calibration gain

UINT16

RW

0xFFFF (65535dec)

Index (hex)

Name

Meaning

Data type

Flags

Default

80n00:19

RTD element

RTD element

UINT16

RW

0x0000 (0dec)

2: Pt1000
-50°C to 150°C

3: Pt500
-50°C to 150°C

5: Ni1000
-50°C to 150°C

6: Ni1000
TK5000,
100°C: 1500 ohm (-30°C to 150°C)

8: Output in ohm
Resolution 1/16 ohm (0 .. 4096 ohm)***

50: NTC1K8
-40°C to 130°C
R0^C=4940 ohm

51: NTC1K8 TK
-30°C to 150°C
R0^C=5200 ohm

52: NTC2K2
-50°C to 130°C
R0^C=7373 ohm

53: NTC3K
-30°C to 80°C
R0^C=9822 ohm

54: NTC5K
-40°C to 100°C
R0^C=9822 ohm

55: NTC10K
-30°C to 150°C
R0^C=32650 ohm

56: NTC10K PRE
-30°C to 150°C
R0^C=29490 ohm

57: NTC10k 3204
-40°C to 110°C
R0^C=27080 ohm

58: NTC10k Type 2
-50°C to 130°C
R0^C=32770 ohm

59: NTC10k Type 3
-50°C to 130°C
R0^C=29588 ohm

60: NTC10K Dale
-50°C to 130°C
R0^C=32660 ohm

61: NTC10K 3A221
-40°C to 130°C
R0^C=32639 ohm

62: NTC20K
-20 to 150°C
R0^C=70200 ohm

99: B-parameter equation

100: potentiometer 0.1 ohm 0..5k

101: potentiometer 1 ohm res

102: potentiometer 10 ohm res

103: potentiometer 20 ohm res

200: NTC100K
R0^C=3266 kΩ

UINT16

RW

0x0002 (0dec)

80n0:1A

Connection technology

Connection technology

0: 2-wire connection

UINT16

RW

0x0000 (0dec)

80n0:1B

Wire calibration 1/32 ohm

Calibration of the supply lines

INT16

RW

0x0000 (0dec)

Index 8002 B-Parameter Equation

Index (hex)

Name

Meaning

Data type

Flags

Default value

8002:0

B_parameter Equation

Max. subindex

UINT8

RO

0x05 (5dec)

8002:01

Min Temperature

 

UINT16

RW

- 50

8002:02

Max Temperature

 

UINT16

RW

150

8002:03

Rn 10 Ohm res.

 

UINT16

RW

1000

8002:04

Tn

 

UINT16

RW

25

8002:05

B-Parameter

 

UINT32

RO

3710.000000

Complete overview

Standard objects (0x1000-0x1FFF)

The standard objects have the same meaning for all EtherCAT slaves.

Index 1000 Device type

Index (hex)

Name

Meaning

Data type

Flags

Default value

1000:0

Device type

Device type of the EtherCAT slave: the Lo-Word contains the CoE profile used (5001). The Hi-Word contains the module profile according to the modular device profile.

UINT32

RO

( )

Index 1008 Device name

Index (hex)

Name

Meaning

Data type

Flags

Default value

1008:0

Device name

Device name of the EtherCAT slave

STRING

RO

( )

Index 1009 Hardware version

Index (hex)

Name

Meaning

Data type

Flags

Default value

1009:0

Hardware version

Hardware version of the EtherCAT slave

STRING

RO

00

Index 100A Software version

Index (hex)

Name

Meaning

Data type

Flags

Default value

100A:0

Software version

Firmware version of the EtherCAT slave

STRING

RO

01

Index 1018 Identity

Index (hex)

Name

Meaning

Data type

Flags

Default value

1018:0

Identity

Information for identifying the slave

UINT8

RO

0x04 (4dec)

1018:01

Vendor ID

Vendor ID of the EtherCAT slave

UINT32

RO

0x00000002 (2dec)

1018:02

Product code

Product code of the EtherCAT slave

UINT32

RO

( )

1018:03

Revision

Revision number of the EtherCAT slave; the low word (bit 0-15) indicates the special terminal number, the high word (bit 16-31) refers to the device description

UINT32

RO

( )

1018:04

Serial number

Serial number of the EtherCAT slave; the low byte (bit 0-7) of the low word contains the year of production, the high byte (bit 8-15) of the low word contains the week of production, the high word (bit 16-31) is 0

UINT32

RO

( )

Index 10F0 Backup parameter handling

Index (hex)

Name

Meaning

Data type

Flags

Default

10F0:0

Backup parameter handling

Information for standardized loading and saving of backup entries

UINT8

RO

0x01 (1dec)

10F0:01

Checksum

Checksum across all backup entries of the EtherCAT slave

UINT32

RO

0x00000000 (0dec)

Index 1A0n TxPDO Map for 0 ≤ n ≤ 7 (Ch. 1 - 8)

Index (hex)

Name

Meaning

Data type

Flags

Default value

1A0n:0

TxPDO Map Ch.1

PDO Mapping TxPDO 1

UINT8

RW

0x09 (9dec)

1A0n:01

SubIndex 001

1. PDO Mapping entry (object 0x60n0 (RTD Inputs Ch.[n+1]), entry 0x01 (Underrange))

UINT32

RW

0x60n0:01, 1

1A0n:02

SubIndex 002

2. PDO Mapping entry (object 0x60n0 (RTD Inputs Ch.[n+1]), entry 0x02 (Overrange))

UINT32

RW

0x60n0:02, 1

1A0n:03

SubIndex 003

3. PDO Mapping entry (4 bits align)

UINT32

RW

0x0000:00, 4

1A0n:04

SubIndex 004

4. PDO Mapping entry (object 0x60n0 (RTD Inputs Ch.[n+1]), entry 0x07 (Error))

UINT32

RW

0x60n0:07, 1

1A0n:05

SubIndex 005

5. PDO Mapping entry (7 bits align)

UINT32

RW

0x0000:00, 7

1A0n:06

SubIndex 006

6. PDO Mapping entry (object 0x180n (TxPDO-Par Ch.[n+1]), entry 0x07 (TxPDO-State))

UINT32

RW

0x180n:07, 1

1A0n:07

SubIndex 007

7. PDO Mapping entry (object 0x180n (TxPDO-Par Ch.[n+1]), entry 0x09 (TxPDO-Toggle))

UINT32

RW

0x180n:09, 1

1A0n:08

SubIndex 008

8. PDO Mapping entry (object 0x60n0 (RTD Inputs Ch.[n+1]), entry 0x11 (Value))

UINT32

RW

0x60n0:11, 16

Index 1C00 Sync manager type

Index (hex)

Name

Meaning

Data type

Flags

Default value

1C00:0

Sync manager type

Using the sync managers

UINT8

RO

0x04 (4dec)

1C00:01

SubIndex 001

Sync-Manager Type Channel 1: Mailbox Write

UINT8

RO

0x01 (1dec)

1C00:02

SubIndex 002

Sync-Manager Type Channel 2: Mailbox Read

UINT8

RO

0x02 (2dec)

1C00:03

SubIndex 003

Sync-Manager Type Channel 3: Process Data Write (Outputs)

UINT8

RO

0x03 (3dec)

1C00:04

SubIndex 004

Sync-Manager Type Channel 4: Process Data Read (Inputs)

UINT8

RO

0x04 (4dec)

Index 1C12 RxPDO assign

Index (hex)

Name

Meaning

Data type

Flags

Default value

1C12:0

RxPDO assign

PDO Assign Outputs

UINT8

RW

0x00 (0dec)

Index 1C13 TxPDO assign

Index (hex)

Name

Meaning

Data type

Flags

Default value

1C13:0

TxPDO assign

PDO Assign Inputs

UINT8

RW

0x08 (8dec)

1C13:01

Subindex 001

1. allocated TxPDO (contains the index of the associated TxPDO mapping object)

UINT16

RW

0x1A00 (6656dec)

1C13:02

Subindex 002

2. allocated TxPDO (contains the index of the associated TxPDO mapping object)

UINT16

RW

0x1A01 (6657dec)

1C13:03

Subindex 003

3. allocated TxPDO (contains the index of the associated TxPDO mapping object)

UINT16

RW

0x1A02 (6658dec)

1C13:04

Subindex 004

4. allocated TxPDO (contains the index of the associated TxPDO mapping object)

UINT16

RW

0x1A03 (6659dec)

1C13:05

Subindex 005

5. allocated TxPDO (contains the index of the associated TxPDO mapping object)

UINT16

RW

0x1A04 (6660dec)

1C32:06

Subindex 006

6. allocated TxPDO (contains the index of the associated TxPDO mapping object)

UINT16

RW

0x1A05 (6661dec)

1C13:07

Subindex 007

7. allocated TxPDO (contains the index of the associated TxPDO mapping object)

UINT16

RW

0x1A06 (6662dec)

1C13:08

Subindex 008

8. allocated TxPDO (contains the index of the associated TxPDO mapping object)

UINT16

RW

0x1A07 (6663dec)

Index 1C33 SM input parameter

Index (hex)

Name

Meaning

Data type

Flags

Default value

1C33:0

SM input parameter

Synchronization parameters for the inputs

UINT8

RO

0x20 (32dec)

1C33:01

Sync mode

Current synchronization mode:

  • 0: Free Run
  • 1: Synchronous with SM 3 event (no outputs available)
  • 2: DC - Synchronous with SYNC0 Event
  • 3: DC - Synchronous with SYNC1 Event
  • 34: Synchronous with SM 2 event (outputs available)

UINT16

RW

0x0000 (0dec)

1C33:02

Cycle time

Cycle time (in ns):

  • Free Run: Cycle time of the local timer
  • Synchronous with SM 2 event: Master cycle time
  • DC-Mode: SYNC0/SYNC1 Cycle Time

UINT32

RW

0x00000000 (0dec)

1C33:03

Shift time

Time between SYNC0 event and reading of the inputs (in ns, only DC mode)

UINT32

RW

0x00000000 (0dec)

1C33:04

Sync modes supported

Supported synchronization modes:

  • Bit 0: free run is supported
  • Bit 1: synchronous with SM 2 event is supported (outputs available)
  • Bit 1: synchronous with SM 3 event is supported (no outputs available)
  • Bit 2-3 = 01: DC mode is supported
  • Bit 4-5 = 01: input shift through local event (outputs available)
  • Bit 4-5 = 10: input shift with SYNC1 event (no outputs available)
  • Bit 14 = 1: dynamic times (measurement through writing of 0x1C33:08)

UINT16

RO

0x8007 (32775dec)

1C33:05

Minimum cycle time

Minimum cycle time (in ns)

UINT32

RO

0x00000000 (0dec)

1C33:06

Calc and copy time

Time between reading of the inputs and availability of the inputs for the master (in ns, only DC mode)

UINT32

RO

0x00000000 (0dec)

1C33:08

Command

  • 0: Measurement of the local cycle time is stopped
  • 1: Measurement of the local cycle time is started

The entries 0x1C33:03, 0x1C33:06, 0x1C33:09 are updated with the maximum measured values.
For a subsequent measurement the measured values are reset

UINT16

RW

0x0000 (0dec)

1C33:09

Delay time

Time between SYNC1 event and reading of the inputs (in ns, only DC mode)

UINT32

RO

0x00000000 (0dec)

1C33:0B

SM event missed counter

Number of missed SM events in OPERATIONAL (DC mode only)

UINT16

RO

0x0000 (0dec)

1C33:0C

Cycle exceeded counter

Number of occasions the cycle time was exceeded in OPERATIONAL (cycle was not completed in time or the next cycle began too early)

UINT16

RO

0x0000 (0dec)

1C33:0D

Shift too short counter

Number of occasions that the interval between SYNC0 and SYNC1 event was too short (DC mode only)

UINT16

RO

0x0000 (0dec)

1C33:20

Sync error

The synchronization was not correct in the last cycle (outputs were output too late; DC mode only)

BOOLEAN

RO

0x00 (0dec)

Profile-specific objects (0x6000-0xFFFF)

The profile-specific objects have the same meaning for all EtherCAT slaves that support the profile 5001.

Index 60n0 RTD Inputs for 0 ≤ n ≤ 7 (Ch. 1 - 8)

Index (hex)

Name

Meaning

Data type

Flags

Default value

60n0:0

RTD Inputs

Maximum subindex

UINT8

RO

0x11 (17dec)

60n0:01

Underrange

The measuring range is undershot.

BOOLEAN

RO

0x00 (0dec)

60n0:02

Overrange

The measuring range is overshot.
(“open circuit” detection if “error” [index 0x60n0:07]) is set

BOOLEAN

RO

0x00 (0dec)

60n0:07

Error

The error bit is set if the data is invalid.

BOOLEAN

RO

0x00 (0dec)

60n0:0F

TxPDO State

Validity of the data of the associated TxPDO (0 = valid, 1 = invalid).

BOOLEAN

RO

0x00 (0dec)

60n0:10

TxPDO Toggle

The TxPDO toggle is toggled by the slave when the data of the associated TxPDO is updated.

BOOLEAN

RO

0x00 (0dec)

60n0:11

Value

The analog input data

INT16

RO

0x0000 (0dec)

Index 80nE RTD Internal data for 0 ≤ n ≤ 7 (Ch. 1 - 8)

Index (hex)

Name

Meaning

Data type

Flags

Default value

80nE:0

RTD Internal data

Maximum subindex

UINT8

RO

0x04 (4dec)

80nE:01

ADC raw value 1

ADC raw value 1

INT32

RO

0x00000000 (0dec)

80nE:02

Resistor 1

Resistance 1 (measured value of resistance sensor, resolution 1/32 Ohm)

UINT16

RO

0x0000 (0dec)

Index 80nF RTD Vendor data for 0 ≤ n ≤ 7 (Ch. 1 - 8)

Index (hex)

Name

Meaning

Data type

Flags

Default

80nF:0

RTD Vendor data

Max. subindex

UINT8

RO

-

80nF:01

Calibration offset

Vendor offset calibration

INT16

RW

-

80nF:02

Calibration gain

Vendor gain calibration

UINT16

RW

-

80nF:03

Calibration offset NTC1

Vendor offset calibration NTC1

INT16

RW

-

80nF:04

Calibration gain
NTC1

Vendor gain calibration NTC1

UINT16

RW

-

80nF:05

Calibration offset NTC2

Vendor offset calibration NTC2

INT16

RW

-

80nF:06

Calibration gain
NTC2

Vendor gain calibration NTC2

UINT16

RW

-

80nF:07

RefA_5k

Extended vendor calibration reference resistor 5k

UINT16

RW

-

80nF:08

RefC_5k

Extended vendor calibration reference resistor 5k

UINT16

RW

-

80nF:09

RefA_35k

Extended vendor calibration reference resistor 35k

UINT16

RW

-

80nF:0A

RefC_35k

Extended vendor calibration reference resistor 35k

UINT16

RW

-

Index F000 Modular device profile

Index (hex)

Name

Meaning

Data type

Flags

Default value

F000:0

Modular device profile

General information for the modular device profile

UINT8

RO

0x02 (2dec)

F000:01

Module index distance

Index spacing of the objects of the individual channels

UINT16

RO

0x0010 (16dec)

F000:02

Maximum number of modules

Number of channels

UINT16

RO

0x0008 (8dec)

Index F008 Code word

Index (hex)

Name

Meaning

Data type

Flags

Default value

F008:0

Code word

currently reserved

UINT32

RW

0x00000000 (0dec)

Index F010 Module list [for {n=1} (1-channel) to {n=1,..,n=8} (8-channel)]

Index (hex)

Name

Meaning

Data type

Flags

Default value

F010:0

Module list

Maximum subindex

UINT8

RO

0x08 (ndec)

F010:0n

Subindex 00n

Profile 320

INT32

RO

0x00000140 (320dec)