Encoder resolution via feed constant denominator (P-AXIS-00363)

P-AXIS-00363

Encoder resolution via feed constant (denominator)

Description

Parameter P-AXIS-00362 and parameter P-AXIS-00363 enable an alternative method to parametrise encoder resolution. If values unequal to 1 (default initialisation) are assigned to parameter P-AXIS-00362 or P-AXIS-00363, encoder resolution is determined by the feed constant.

f: Feed constant (0.1µm / revolution)
P-AXIS-00362 / P-AXIS-00363

 

Parameter

antr.feed_const_denom

Data type

UNS32

Data range

1 = feed_const_denom = MAX(UNS32)

Axis types

T, R, S

Dimension

T: U

R,S: U

Default value

1

Drive types

---

Remarks

When P-AXIS-00362 /P-AXIS-000363 are used, the parameters P-AXIS-00233 and P-AXIS-00234 must be set to 1.

For possible applications, see Settings of position scaling

 

Encoder resolution is calculated using the equation below:

Encoder resolution via feed constant denominator (P-AXIS-00363) 1:

Where:

R: Resulting resolution (increments / 0.1µm)

rMotor: Encoder increments per motor revolution (P-AXIS-00092)

igear: Gear ratio (revolutions gear input / revolutions gear output (P-AXIS-00511/P-AXIS-00512)).

f: Feed constant (0.1µm / revolution) (P-AXIS-00362/P-AXIS-00363)

Encoder resolution via feed constant denominator (P-AXIS-00363) 2: