Error messages of the mxA interface in the robot interpreter

No.

Message text

Cause

Remedy

0

—

—

—

1

INTERNAL ERROR

Internal exceptional error

Contact KUKA Deutschland GmbH. (>>> KUKA Service)

2

ASSERT FAILED

Internal exceptional error

3

OVERFLOW STATUS RETURN QUEUE (MAIN)

There are more than 100 checkback signals relating to status changes waiting to be transferred from the robot controller to the PLC.

The transmission rate is considerably lower than the processing speed.

Reduce the number of statements to be buffered simultaneously.

If this is not possible, contact KUKA Deutschland GmbH. (>>> KUKA Service)

4

OVERFLOW STATUS RETURN QUEUE (TRIGGER)

5

INVALID COMMAND QUEUE INDEX

Internal exceptional error

Contact KUKA Deutschland GmbH. (>>> KUKA Service)

6

INVALID COMMAND STATE

Internal exceptional error

7

INVALID COMMAND ID

Internal exceptional error

8

INVALID MOVE TYPE

Internal exceptional error

9

OVERFLOW TRIGGER FIFO

Internal exceptional error

10

UNDERFLOW TRIGGER FIFO

Internal exceptional error

11

INVALID TRIGGER FIFO INDEX

Internal exceptional error

12

EXECUTION OF T_AFTER MISSING

Internal exceptional error

13

EXECUTION OF T_START MISSING

Internal exceptional error

14

INVALID ADVANCE_ACT

Internal exceptional error

16

TIMEOUT HEARTBEAT FROM PLC

Connection to PLC interrupted

Restore connection, then acknowledge error.

PLC program stopped

Restart the PLC program.

Connecting cable defective or not correctly connected

Exchange connecting cable or connect it correctly.

17

INVALID ORDERID (INVERSE)

Internal exceptional error

Contact KUKA Deutschland GmbH. (>>> KUKA Service)

30

INVALID PTP APO

An invalid approximation parameter has been transferred for a PTP motion.

Program a valid value (parameter Approximate).

(>>> APO)

31

INVALID CP APO

An invalid approximation parameter has been transferred for a CP motion (LIN, CIRC).

32

INVALID BASE NUMBER

An invalid number has been programmed in the function block KRC_ReadBaseData or KRC_WriteBaseData for the BASE coordinate system.

Specify the number of the BASE coordinate system that is currently being used in the robot controller (parameter BaseNo).

  • 1 … 32

An invalid number has been programmed in a KRC_Move or KRC_Jog function block for the BASE coordinate system.

Specify the number of the BASE coordinate system that is currently being used in the robot controller (parameter CoordinateSystem – COORDSYS.Base).

(>>> COORDSYS)

33

INVALID TOOL NUMBER

An invalid number has been programmed in the function block KRC_ReadToolData or KRC_WriteToolData for the TOOL coordinate system.

Specify the number of the TOOL coordinate system that is currently being used in the robot controller (parameter ToolNo).

  • 1 … 16

An invalid number has been programmed in a KRC_Move or KRC_Jog function block for the TOOL coordinate system.

Specify the number of the TOOL coordinate system that is currently being used in the robot controller (parameter CoordinateSystem – COORDSYS.Tool).

(>>> COORDSYS)

34

INVALID VELOCITY

An invalid value has been programmed in a function block for the speed.

Program a valid value (parameter Velocity):

  • 0 … 100%

35

INVALID ACCELERATION

An invalid value has been programmed in a function block for the acceleration.

Program a valid value (parameter Acceleration):

  • 0 … 100%

36

INVALID C_PTP

An invalid approximation distance has been transferred for a PTP motion.

Program a valid value (parameter Approximate).

(>>> APO)

37

INVALID C_DIS

An invalid distance parameter has been transferred for an approximated motion.

38

INVALID C_VEL

An invalid speed parameter has been transferred for an approximated motion.

39

INVALID C_ORI

An invalid orientation parameter has been transferred for an approximated motion.

40

INVALID ORI_TYPE

An invalid value has been programmed in a KRC_Move or KRC_Jog function block for the orientation control of the TCP.

Program a valid value (parameter OriType).

(>>> OriType)

41

POSITION DATA NOT INITIALIZED

No target position transferred when calling a KRC_Move function block.

Define at least 1 element of the target position (parameter Position).

(>>> E6POS)

42

AXISPOSITION DATA NOT INITIALIZED

No axis position transferred when calling a KRC_MoveAxis function block.

Define at least 1 axis position (parameter AxisPosition).

(>>> E6AXIS)

43

INVALID TRIGGER DISTANCE

An invalid value has been programmed in a KRC_SetDistanceTrigger function block for the switching point of the trigger.

Program a valid value (parameter Distance):

  • 0: Switching action at the start point
  • 1: Switching action at the end point

44

INVALID TRIGGER IO

An invalid output has been programmed in a KRC_SetDistanceTrigger or KRC_SetPathTrigger function block.

Program a valid value (parameter Output):

  • 1 … 2 048

45

INVALID TRIGGER PULSE

An invalid value has been programmed in a KRC_SetDistanceTrigger or KRC_SetPathTrigger function block for the length of the pulse.

Program a valid value (parameter Pulse):

  • 0.1 … 3.0 s
  • 0.0 s (No pulse active)

46

INVALID CIRC_HP

No auxiliary position transferred when calling a KRC_MoveCirc function block.

Define at least 1 element of the auxiliary position (parameter CircHP).

(>>> E6AXIS)

47

INVALID INTERRUPT IO

The number of the digital input to which the interrupt is declared is invalid (function block KRC_DeclareInterrupt).

Program a valid value (parameter Input):

  • 1 … 2 048

48

INVALID INTERRUPT PRIORITY

An invalid number was transferred when calling a KRC_…Interrupt function block.

Program a valid value (parameter Interrupt):

  • 1 … 8

49

INTERRUPT NOT DECLARED

Interrupt has not been declared.

Declare interrupt.

(>>> Declaring interrupts)

50

INVALID INTERRUPT ACTION

The interrupt reaction programmed when the interrupt was declared is invalid.

Program a valid reaction (parameter Reaction)

(>>> Declaring interrupts)

51

INVALID IO NUMBER

The number of the digital input to which the interrupt is declared is invalid (function block KRC_DeclareInterrupt).

Program a valid value (parameter Input):

  • 1 … 2 048

52

INVALID PULSE DURATION

An invalid value has been programmed in the function block KRC_WriteDigitalOutput for the length of the pulse.

Program a valid value (parameter Pulse):

  • 0.1 … 3.0 s
  • 0.0 s (No pulse active)

53

INVALID BUFFER_MODE

An invalid BufferMode has been programmed in a function block. For example , DIRECT mode is not available for some function blocks.

Program a valid BufferMode.

(>>> BufferMode)

54

INVALID TOOL NUMBER FOR LOAD_DATA

An invalid number has been programmed in the function block KRC_ReadLoadData or KRC_WriteLoadData for reading or writing the load data or supplementary load data.

Program a valid value (parameter Tool).

(>>> Reading the load data)

(>>> Writing load data)

55

INVALID ANALOG IO NUMBER

An invalid value has been programmed in a function block for the analog input or output.

Program a valid value (parameter Number):

  • 1 … 32

56

INVALID IPO_MODE

An invalid value has been programmed in a function block for the interpolation mode, e.g. in a KRC_Move function block.

Program a valid value (parameter CoordinateSystem – COORDSYS.IPO_MODE).

(>>> COORDSYS)

57

INVALID CIRC_TYPE

An invalid value has been programmed in a KRC_MoveCirc function block for the orientation control during the circular motion.

Program a valid value (parameter CircType).

(>>> CircType)

58

INVALID FRAME DATA

Invalid TOOL or BASE data have been programmed in a KRC_WriteToolData or KRC_WriteBaseData function block.

Program valid data (parameter ToolData or BaseData).

(>>> Writing TOOL data)

(>>> Writing BASE data)

59

INVALID LOAD DATA

Invalid load data have been programmed in a KRC_WriteLoadData function block.

Program valid data.

(>>> Writing load data)

60

INVALID SOFT_END (REVERSED)

Error writing the software limit switches: positive software limit switch < negative software limit switch (function block KRC_WriteSoftEnd or KRC_WriteSoftEndEx)

Program lower values for the negative software limit switch than for the positive software limit switch.

61

INVALID INTERRUPT STATE

Internal exceptional error

Contact KUKA Deutschland GmbH. (>>> KUKA Service)

62

INVALID SYS VAR INDEX

An index for which no system variable is stored has been transferred in a KRC_ReadSysVar or KRC_WriteSysVar function block.

Program a valid value (parameter Index).

(>>> Reading system variables)

(>>> Writing system variables)

63

INVALID SYS VAR VALUE

An invalid value has been programmed in a KRC_WriteSysVar function block for the system variable.

Program a valid value (parameter Value1 … Value10).

(>>> Writing system variables)

64

SYS VAR NOT WRITEABLE

An error occurred when writing a system variable.

The specified system variable does not exist or may not be written in the current operating state.

65

INVALID REAL VALUE

The programmed Real value is invalid.

Program a valid value:

  • -2147483500 … +2147483500

66

ERROR SETTING OUTPUT

Error writing a digital output. The output may already be assigned by the system.

Use a different digital output (parameter Number):

  • 1 … 2 048

67

ERROR SETTING SOFTEND

Error writing the software limit switches: One possible error, for example, is writing a rotational axis with a value outside the range +/-360°.

Program valid values for the software limit switches (see machine data).

68

INVALID TECH FUNCTION INDEX

A TechFunctionID for which no technology function is stored has been transferred in a KRC_TechFunction function block.

Contact KUKA Deutschland GmbH. (>>> KUKA Service)

69

INVALID TECH FUNCTION PARAMETER

An invalid value has been programmed in a KRC_TechFunction function block for a parameter.

Contact KUKA Deutschland GmbH. (>>> KUKA Service)

70

INVALID PARAMETER VALUE

An invalid value has been programmed in the called function block for one or more parameters.

Program valid values for the parameters.

71

CONVEYOR ALARM DISTANCE

Component has reached the alarm distance on the conveyor.

To continue the execution:

  1. Perform a reset using the function blocks KRC_AutoStart and KRC_ConvInit.
  2. Execute the next command.

Possible remedies to prevent the problem from recurring:

  • Increase the conveyor alarm distance.
  • Reduce conveyor speed.
  • Optimize programming. The robot must be able to reach the component before it reaches the alarm distance.
  • If no stop is desired when the alarm distance is reached:

72

CONVEYOR END OF WORK AREA

Component has reached the end of the work area on the conveyor.

To continue the execution:

  1. Perform a reset using the function blocks KRC_AutoStart and KRC_ConvInit.
  2. Execute the next command.

Possible remedies to prevent the problem from recurring:

  • Increase the conveyor end of work area limit.
  • Reduce conveyor speed.
  • Optimize programming. The robot must be able to reach the component before it reaches the end of the work area.

73

CONVEYOR STOP SIGNAL

During conveyor operation, a $STOPMESS fault occurred (e.g. EMERGENCY STOP).

To continue the execution if $STOPMESS is no longer present:

  1. Perform a reset using the function blocks KRC_AutoStart and KRC_ConvInit.
  2. Execute the next command.

74

CONVEYOR EXTERNAL QUIT

During conveyor operation, an external cancel was triggered (e.g. via a configured input signal or cyclical flag).

To continue the execution:

  1. Perform a reset using the function blocks KRC_AutoStart and KRC_ConvInit.
  2. Execute the next command.

75

CONVEYOR WAIT FOR SCENE TIMEOUT

Timeout reached while waiting for the selected scene to be present on the conveyor.

To continue the execution:

  1. Perform a reset using the function blocks KRC_AutoStart and KRC_ConvInit.
  2. Execute the next command.

Possible remedies to prevent the problem from recurring:

  • Increase conveyor speed.
  • Optimize programming. The robot must be able to detect the desired scene in time.
  • Optimize the parameters of the KRC_ConvTrackingOn function block to be able to detect the desired scene in time.

76

CONVEYOR WAIT FOR SCENE INPUT

Waiting for the selected scene on the conveyor was cancelled because the input for wait cancellation changed to logic level TRUE.

To continue the execution:

  1. Perform a reset using the function blocks KRC_AutoStart and KRC_ConvInit.
  2. Execute the next command.

77

CONVEYOR WAIT FOR SCENE CYCFLAG

Waiting for the selected scene on the conveyor was cancelled because the cyclical flag for wait cancellation changed to logic level TRUE.

To continue the execution:

  1. Perform a reset using the function blocks KRC_AutoStart and KRC_ConvInit.
  2. Execute the next command.

78

CONVEYOR WAIT FOR SCENE SYNCEND

Waiting for the selected scene on the conveyor was cancelled because the end of the synchronization area had already been exceeded.

To continue the execution:

  1. Perform a reset using the function blocks KRC_AutoStart and KRC_ConvInit.
  2. Execute the next command.

Possible remedies to prevent the problem from recurring:

  • Optimize programming. The robot must be able to detect the desired scene before it reaches the end of the synchronization area.
  • Optimize the parameters of the KRC_ConvTrackingOn function block to be able to detect the desired scene before it reaches the end of the synchronization area.