Input signals

AxisGroupIdx

This signal input is used to select the robot system. Up to 5 robot systems can be used.

A robot system is a grouping of axes to form an axis group.

ExecuteCmd

If this signal is set, mxAutomation transfers the associated function block to the robot. The function block is stored in a statement buffer by the robot, provided there is still sufficient space in the buffer.

If this signal input is reset, what happens depends on the status of the Busy output:

BufferMode

Mode in which a statement is executed on the robot controller

Value

Name

Description

0

DIRECT

The statement is executed directly by the submit interpreter (Submit program).

Note: This mode is not available for certain function blocks.

1

ABORTING

The statement is executed immediately by the robot interpreter (main program). First, all active motions and buffered statements are aborted and the robot is braked to a standstill.

2

BUFFERED

The statement is buffered. Buffered statements are executed by the robot interpreter (main program) according to the FIFO principle.