ST_TcHydAxRtData (from V3.0)
The variables in this structure indicate the runtime state of the axis.
![]() | The order of the data is not guaranteed. |
Syntax
TYPE ST_TcHydAxRtData :
(* last modification: 02.07.2018 *)
STRUCT
(*-------------------------------*)
fActForce: LREAL := 0.0;
fActiveOverlap: LREAL := 0.0;
fActPos: LREAL := 0.0;
fActPosDelta: LREAL := 0.0;
fActPosOffset: LREAL := 0.0;
fActPressure: LREAL := 0.0;
fActPressureA: LREAL := 0.0;
fActPressureB: LREAL := 0.0;
fActVelo: LREAL := 0.0;
fBrakeOffTimer: LREAL := 0.0;
fBrakeOnTimer: LREAL := 0.0;
fBrakeSafetyTimer: LREAL := 0.0;
fClampingOutput: LREAL := 0.0;
fDestAcc: LREAL := 0.0;
fDestCreepDistanceM: LREAL := 0.0;
fDestCreepDistanceP: LREAL := 0.0;
fDestCreepSpeedM: LREAL := 0.0;
fDestCreepSpeedP: LREAL := 0.0;
fDestDec: LREAL := 0.0;
fDestJerk: LREAL := 0.0;
fDestPos: LREAL := 0.0;
fDestRampEnd: LREAL := 0.0;
fDestSpeed: LREAL := 0.0;
fDistanceToTarget: LREAL := 0.0;
fEnc_RefShift: LREAL := 0.0;
fEnc_ZeroSwap: LREAL := 0.0;
fGearActive: LREAL := 0.0;
fGearSetting: LREAL := 0.0;
fLagCtrlOutput: LREAL := 0.0;
fLatchedPos: LREAL := 0.0;
fOilRequirred_A: LREAL := 0.0;
fOilRequirred_B: LREAL := 0.0;
fOilUsed_A: LREAL := 0.0;
fOilUsed_B: LREAL := 0.0;
fOutput: LREAL := 0.0;
fOverride: LREAL := 1.0;
fParamAccTime: LREAL := 0.0;
fPosError: LREAL := 0.0;
fSetAcc: LREAL := 0.0;
fSetPos: LREAL := 0.0;
fSetPressure: LREAL := 0.0;
fSetSpeed: LREAL := 0.0;
fSetSpeedOld: LREAL := 0.0;
fSetVelo: LREAL := 0.0;
fStartPos: LREAL := 0.0;
fStartRamp: LREAL := 0.0;
fStartRampAnchor: LREAL := 0.0;
fSupplyPressure: LREAL := 0.0;
fTargetPos: LREAL := 0.0;
fTimerPEH: LREAL := 0.0;
fTimerTPM: LREAL := 0.0;
fValvePressure: LREAL := 0.0;
fVeloError: LREAL := 0.0;
fBlockDetectDelay: LREAL := 2.0;
(*------------------------------------------------------*)
nAxisState: DWORD := 0;
nCalibrationState: DWORD := 0;
nDeCtrlDWord: DWORD := 0;
nErrorCode: DWORD := 0;
nStateDWord: DWORD := 0;
udiAmpErrorCode: UDINT;
(*------------------------------------------------------*)
iCurrentStep: E_TcMcCurrentStep;
wEncErrMask: WORD:=0;
wEncErrMaskInv: WORD:=0;
nDrvWcCount: INT:=0;
(**)
nEncWcCount: INT:=0;
nDrvDeviceState: UINT:=0;
nEncDeviceState: INT:=0;
(*------------------------------------------------------*)
bActPosCams: BYTE := 0;
bBrakeOff: BOOL := FALSE;
bBrakeOffInverted: BOOL := FALSE;
bControllable: BOOL := FALSE;
bCountedCycles: BYTE := 1;
bCycleCounter: BYTE := 0;
bDriveResponse: BOOL := FALSE;
bEncDoLatch: BOOL := FALSE;
(**)
bEncoderResponse: BOOL := FALSE;
bEncLatchValid: BOOL := FALSE;
bLocked_Estop: BOOL := FALSE;
bParamsUnsave: BOOL := FALSE;
bReloadParams: BOOL := FALSE;
bTargeting: BOOL := FALSE;
bUnalignedOverlap: BOOL := FALSE;
bActPosOffsetEnable: BOOL := FALSE; (* starting with 09.03.2015 *)
(**)
bDriveStartup: BOOL := FALSE;
bEncAlignRefShift: BOOL := FALSE;
bDrvWcsError: BOOL := FALSE;
bEncWcsError: BOOL := FALSE;
bFirstWcs: BOOL := FALSE;
bChangeCount: BYTE := 0;
bStartAutoIdent: BOOL := FALSE;
bParamFileComplete: BOOL := FALSE;
(*------------------------------------------------------*)
pMasterRtData: POINTER TO BYTE;
pMasterParam: POINTER TO BYTE;
(*------------------------------------------------------*)
udiSercDeviceID: UDINT := 0;
uiSercBoxAddr: UINT := 0;
uiSercPort: UINT := 0;
(*------------------------------------------------------*)
stPosCtrlr: stbkplcinternal_cplxctrl;
stVeloCtrlr: stbkplcinternal_cplxctrl;
(*------------------------------------------------------*)
sTopBlockName: STRING(87) := '';
stHybrid: ST_TcHybridAxRtData;
(*------------------------------------------------------*)
END_STRUCT
END_TYPE
Parameter
Name | Type | Description |
|---|---|---|
fActForce | LREAL | [N, kN] Actual force of the cylinder. This value is usually determined by a function block for acquisition of actual force or pressure values. |
fActiveOverlap | LREAL | [1] The current output of the overlap compensation. An output variable of the profile generators. |
fActPos | LREAL | [mm] The current actual position of the axis. This value is usually determined by an encoder function block. |
fActPosDelta | LREAL | [mm] The change of the actual position relative to the previous cycle. |
fActPosOffset | LREAL | [mm] The offset used to influence the actual value. If bActPosOffsetEnable is TRUE, this offset is added to fActPos. If fActPosOffset changes, fActVelo is unaffected. If bActPosOffsetEnable is TRUE, fActPosOffset takes effect immediately and without ramp. Example: If the reference position is 100.0 mm and the offset is 1.0 mm, the actual position at the point of the zero pulse is set to 101.0 mm. If influencing is subsequently disabled or set to 0.0, the actual position at the point of the zero pulse shows the value 100.0 mm, just like it would have done during homing without influencing. |
fActPressure | LREAL | [bar] Actual pressure in the cylinder. This value is usually determined by a function block for acquisition of actual force or pressure values. |
fActPressureA | LREAL | [bar] Actual pressure on the A-side of the cylinder. This value is usually determined by a function block for acquisition of actual force or pressure values. |
fActPressureB | LREAL | [bar] Actual pressure on the B-side of the cylinder. This value is usually determined by a function block for acquisition of actual force or pressure values. |
fActVelo | LREAL | [mm/s] The current actual velocity of the axis. This value is usually determined by an encoder function block. |
fBrakeOffTimer | LREAL |
|
fBrakeOnTimer | LREAL |
|
fBrakeSafetyTimer | LREAL |
|
fClampingOutput | LREAL | [V] An output variable of the profile generators. |
fDestAcc | LREAL | [mm/s2] The acceleration specified by the current or last executed motion command. |
fDestCreepDistance | LREAL | [mm] Up to V3.0.7: The creep distance. |
fDestCreepDistanceM | LREAL | [mm] Up to V3.0.8: The creep distance in negative direction. |
fDestCreepDistanceP | LREAL | [mm] Up to V3.0.8: The creep distance in positive direction. |
fDestCreepSpeed | LREAL | [mm/s] Up to V3.0.7: The creep speed. |
fDestCreepSpeedM | LREAL | From V3.0.8: The creep speed in negative direction. |
fDestCreepSpeedP | LREAL | [mm/s] From V3.0.8: The creep speed in positive direction. |
fDestDec | LREAL | [mm/s2] The deceleration specified by the current or last executed motion command. |
fDestJerk | LREAL | [mm/s3] The jerk specified by the current or last executed motion command. |
fDestPos | LREAL | [mm] The currently active target position. |
fDestRampEnd | LREAL |
|
fDestSpeed | LREAL | [mm/s] The velocity specified by the current or last executed motion command. |
fDistanceToTarget | LREAL | [mm] The current remaining distance of the axis. This value is usually determined by a generator function block. |
fEnc_RefShift | LREAL | [mm] The offset between the converted (perhaps internal extended) counter value of an incremental encoder input terminal and the actual position of the axis. This offset is determined through homing, e.g. with an MC_Home_BkPlcMc function block, or manipulated with an MC_SetPosition_BkPlcMc function block. |
fEnc_ZeroSwap | LREAL |
|
fGearActive | LREAL |
|
fGearSetting | LREAL |
|
fLagCtrlOutput | LREAL | [1] The normalized output of the position controller. An output variable of the profile generators. |
fLatchedPos | LREAL | [mm] The position (taking into account current offsets) at which homing took place or where the components of the actual value acquisition (encoder, I/O electronics) were switched on. |
fOilRequirred_A | LREAL | [l/min] The oil consumption on the A-side, calculated taking into account the set velocity. |
fOilRequirred_B | LREAL | [l/min] The oil consumption on the B-side, calculated taking into account the set velocity. |
fOilUsed_A | LREAL | [l/min] The oil consumption on the A-side, calculated taking into account the actual velocity. |
fOilUsed_B | LREAL | [l/min] The oil consumption on the B-side, calculated taking into account the actual velocity. |
fOutput | LREAL | [1] The control value to be output. This variable is used for communication between the MC_AxRtFinish_BkPlcMc and MC_AxRtDrive_BkPlcMc function blocks. |
fOverride | LREAL | [1] The current axis velocity override. |
fParamAccTime | LREAL |
|
fPosError | LREAL | [mm] The current position error of the axis. |
fSetAcc | LREAL | [mm/s2] The current acceleration control value. An output variable of the profile generators. |
fSetPos | LREAL | [mm] The current position command value of the axis. |
fSetPressure | LREAL | [bar] The setpoint for an optional pressure or force control must be stored here. |
fSetSpeed | LREAL | [mm/s] The normalized set velocity of the axis. An output variable of the profile generators. |
fSetSpeedOld | LREAL |
|
fSetVelo | LREAL |
|
fStartPos | LREAL | [mm] The start position of the current or last processed motion command. |
fStartRamp | LREAL |
|
fStartRampAnchor | LREAL |
|
fSupplyPressure | LREAL | [bar] Supply pressure. This value is usually determined by a function block for acquisition of actual force or pressure values. |
fTargetPos | LREAL | [mm] The target position specified by the current or last processed motion command. |
fTimerPEH | LREAL |
|
fTimerTPM | LREAL |
|
fValvePressure | LREAL | [bar] Pressure drop at the valve. This value is usually determined by a function block for acquisition of actual force or pressure values. |
fVeloError | LREAL |
|
fBlockDetectDelay | LREAL | [s] The delay time for the detection of the function block during homing on block. This value is initialized with 2.0 seconds to reflect the default behavior of previous versions. If a different time is required, it must be updated before homing commences. If a value of less than the cycle time is detected when homing commences, the default value of 2.0 seconds is entered automatically. This value is not saved as a parameter. This variable has been available under TC2 in V3.0.41 from 12 October 2017. |
nAxisState | DWORD | The motion state of the axis. |
nCalibrationState | DWORD | The current homing state. |
nDeCtrlDWord | DWORD | The control signals of the axis. |
nErrorCode | DWORD | The current ErrorCode of the axis. |
nStateDWord | DWORD | The state signals of the axis. |
udiAmpErrorCode | UDINT |
|
iCurrentStep | E_TcMcCurrentStep | The internal state of the control value generators. Values from E_TcMcCurrentStep. |
wEncErrMask | WORD |
|
wEncErrMaskInv | WORD |
|
nDrvWcCount | INT |
|
nEncWcCount | INT |
|
nDrvDeviceState | UINT |
|
nEncDeviceState | INT |
|
bActPosCams | BYTE | The current position cam of the axis. This value is only used, if iTcMc_EncoderDigCam is set as encoder type. |
bBrakeOff | BOOL | The control signal for an external brake. An output variable of the profile generators. |
bBrakeOffInverted | BOOL | The inverted bBrakeOff signal. |
bControllable | BOOL |
|
bCountedCycles | BYTE |
|
bCycleCounter | BYTE |
|
bDriveResponse | BOOL |
|
bEncDoLatch | BOOL | This signal is used for communication by the MC_Home_BkPlcMc and MC_AxRtEncoder_BkPlcMc function blocks of the axis during homing. |
bEncoderResponse | BOOL |
|
bEncLatchValid | BOOL | This signal is used for communication by the MC_Home_BkPlcMc and MC_AxRtEncoder_BkPlcMc function blocks of the axis during homing. |
bLocked_Estop | BOOL | A TRUE in this variable prevents the control value generators from exiting the state iTcHydStateEmergencyBreak / McState_Errorstop, despite the fact that the drive outputs are reduced to 0. Used by MC_EmergencyStop_BkPlcMc and MC_ImediateStop_BkPlcMc. |
bParamsUnsave | BOOL | The function blocks MC_WriteParameter_BkPlcMc and MC_WriteBoolParameter_BkPlcMc set this flag if they change a parameter value. An MC_AxParamSave_BkPlcMc function block clears the flag when the parameters are successfully saved. In online mode of the PlcMcManager, this flag is used for the state display. |
bReloadParams | BOOL |
|
bTargeting | BOOL |
|
bUnalignedOverlap | BOOL | The characteristic of the overlap compensation is defined here. |
bActPosOffsetEnable | BOOL | A TRUE in this variable activates actual value influencing. See also under fActPosOffset. |
bDriveStartup | BOOL |
|
bEncAlignRefShift | BOOL | reserved. |
bDrvWcsError | BOOL |
|
bEncWcsError | BOOL |
|
bFirstWcs | BOOL |
|
bChangeCount | BYTE | This value is incremented with each parameter change. |
bStartAutoIdent | BOOL |
|
bParamFileComplete | BOOL | This flag is set if a corresponding identifier was found at the end of the file when the parameters were loaded and the CRC check was successful. |
pMasterRtData | POINTER TO BYTE |
|
pMasterParam | POINTER TO BYTE |
|
udiSercDeviceID | UDINT |
|
uiSercBoxAddr | UINT |
|
uiSercPort | UINT |
|
stPosCtrlr | stbkplcinternal_cplxctrl |
|
stVeloCtrlr | stbkplcinternal_cplxctrl |
|
sTopBlockName | STRING | Most of the library function blocks called directly by application enter a debug ID here. |
stHybrid | ST_TcHybridAxRtData | Extended status data for servo-electric/hydraulic hybrid axes. |
![]() | Information for fActPosOffset
|
![]() | All other elements of this structure are reserved for internal use. They are not guaranteed and must not be used or modified by the application. |
