Technical data

All values are typical values over the entire temperature range, unless stated otherwise.

IO-Link

Connection

1 x M12 plug, 5-pin, A-coded

Data transfer rate

230.4 kbaud (COM 3)

Specification version

IO-Link V1.1, Class B

Requirements for IO-Link master

V1.1

Current consumption from L+

100 mA

Current consumption from P24

Current for sensor supply

Electrical isolation L+ / P24

yes

Analog inputs

Number

8

Connection

8 x M12 socket, 5-pin

Cable length to the sensor

max. 30 m

Input type

Single-ended

Measuring range

Individually adjustable for each channel:

Digital resolution

16 bits, including sign

Measurement uncertainty

max 0.3 %, relative to the full scale value

See chapter Measurement error/measurement deviation/measurement uncertainty, output uncertainty.

Input resistance

Voltage measurement: min. 200 kΩ

Current measurement: 85 Ω + diode voltage

Dielectric strength

max. 30 V

Conversion time

approx. 100 µs

Input filter limit frequency

5 kHz

Input filter characteristic

Adjustable

Sensor power supply

0 … 30 VDC from P24, short-circuit proof

Housing data

Dimensions W x H x D

60 mm x 126 mm x 26.5 mm (without plug connectors)

Weight

approx. 250 g

Installation position

variable

Material

PA6 (polyamide)

Environmental conditions

Ambient temperature during operation

-25 … +60 °C
-25 … +55 °C according to cURus

Ambient temperature during storage

-40 … +85 °C

Vibration resistance, shock resistance

conforms to EN 60068-2-6 / EN 60068-2-27
Additional checks

EMC immunity / emission

conforms to EN 61000-6-2 / EN 61000-6-4

Protection class

IP65, IP66, IP67 (conforms to EN 60529)

Approvals/markings

Approvals/markings *)

CE, cURus

*) Real applicable approvals/markings see type plate on the side (product marking).