Measuring range -20 … +20 mA
| Technical data | Measuring range | 
|---|---|
| Input resistance | typ. 85 Ω | 
| Measuring range, nominal | -20…+20 mA | 
| Measuring range, end value (full scale value) | 20 mA | 
| Measuring range, technically usable | -21.474…+21.474 mA, overcurrent-protected | 
| Fuse protection | Internal overload limiting, continuous current resistant | 
| PDO resolution | 16-bit, including sign | 
| PDO LSB (Extended Range) | 655.35 nA | 
| PDO LSB (Legacy Range) | 610.37 nA | 
Factory setting: "Extended Range" mode