Information / diagnostic data (channel specific)

Index 9010 STM Info data Ch.1

Index (hex)

Name

Meaning

Data type

Flags

Default

9010:0

STM Info data Ch.1

Maximum subindex

UINT8

RO

0x01 (1dec)

9010:01

Status word

Status word (see index 0xA010)

UINT16

RO

0x0000 (0dec)

Index A010 STM Diag data Ch.1

Index (hex)

Name

Meaning

Data type

Flags

Default

A010:0

STM Diag data Ch.1

Maximum subindex

UINT8

RO

0x11 (17dec)

A010:02

Over temperature

Internal terminal temperature is higher than 80°C (see subindex 0xF80F:04)

BOOLEAN

RO

0x00 (0dec)

A010:04

Under voltage

Motor supply voltage is 20% lower than the configured nominal voltage (warning), or

Motor supply voltage is less than 8 V (error, see 0xA010:09)

BOOLEAN

RO

0x00 (0dec)

A010:05

Over voltage

Motor supply voltage is 10% higher than the configured nominal voltage

BOOLEAN

RO

0x00 (0dec)

A010:08

No control power

Control voltage at the power contacts is less than 12 V

BOOLEAN

RO

0x00 (0dec)

A010:09

Misc error

Terminal initialization failed, or
supply voltage is less than 8 V, or
internal terminal temperature is higher than 100°C (see subindex 0xF80F:05)

BOOLEAN

RO

0x00 (0dec)

A010:0A

Open load A

Open load, bridge A (the terminal switches the motor off automatically).
ATTENTION: This error message must be acknowledged by the user (index 0x7010:02)!

BOOLEAN

RO

0x00 (0dec)

A010:0B

Open load B

Open load, bridge B (the terminal switches the motor off automatically).
ATTENTION: This error message must be acknowledged by the user (index 0x7010:02)!

BOOLEAN

RO

0x00 (0dec)

A010:0C

Over current A

Overcurrent, bridge A (the terminal switches the motor off automatically).
ATTENTION: This error message must be acknowledged by the user (index 0x7010:02)!

BOOLEAN

RO

0x00 (0dec)

A010:0D

Over current B

Overcurrent, bridge B (the terminal switches the motor off automatically).
ATTENTION: This error message must be acknowledged by the user (index 0x7010:02)!

BOOLEAN

RO

0x00 (0dec)

A010:11

Actual operation mode

Current operation mode (relevant for activated automatic mode, see 0x8012:01)

BIT4

RO

0x00 (0dec)