Set position value

The position value (0x60n1:01 "Position") can be set to a specified position value at runtime. The default can be enabled as follows:

Setting the position value via a PLC variable ("Set position value", index 0x70n0:11)

The position value can be set to a specified value at runtime via the process data. In the PLC this bit can be linked to a digital input, for example, or used directly as a variable.

Set position value via digital input ("Set position on digital input", index 0x70n0:02)

Set position value 1:

Parameterization of the digital input

The parameterization of the digital input via the indices 0x80n1:1BDigital input latch polarity” and 0x80n0:06Enable continuous digital input” also applies to the functions “Set position on digital input” index 0x70n0:02 and “Enable latch on digital input” index 0x70n0:03.

Saving the offset value ("Set Position Offset", index 0x90n0:11

An inductive measuring probe provides an absolute measured value, i.e. the position value does not have to be referenced after a voltage interruption.

Command

Description

0x8010

Deleting the offset value for both position values

0x8011

Deleting the offset value for position value of channel 1

0x8012

Deleting the offset value for position value of channel 2

Set position value 2:

Command entry via the System Manager

If the command input is written via the System Manager, the value must be entered in the "Binary" field (LOWBYTE first). If the command is initiated via the PLC, then this takes place automatically.