Damper

The Damper template displays the damper position graphically and in text form.

Damper 1:

Use

Use on any page where a template of the Damper type is to be displayed.

Compatibility

The BaTemplateDescription supports the following BaObjects.

Two-point

Subelements:

Symbol name

Data type

Required

Description

SwiCls

FB_BA_BI_IO

x

Switch close

SwiOpn

FB_BA_BI_IO

x

Switch open

Hierarchy:

- BaObject

      - SwiCls

      - SwiOpn

Corresponds to the PLC template:

- FB_BA_Dmp2P

Analog

Subelements:

Symbol name

Data type

Required

Description

Mdlt

FB_BA_AO_IO

x

Feedback

Hierarchy:

- BaObject

      - Mdlt

Corresponds to the PLC template

- FB_BA_ActuatorAnalog

Attributes

This template inherits from the UiIconFdbStp control. In addition, there are the following attributes.

Common

DisplayMode

tchmi:framework#/definitions/TcHmi.BuildingAutomation.Templates.Universal.Damper.DisplayMode

Determines the icon to be displayed.

If "Custom" is selected, the icon that was set in the Icon attribute is displayed.

FlapPosition

tchmi:general#/definitions/Number

Position of the flaps in percent (0 is closed).