Migrated NC commands
![]() | The table below lists commands which were transferred to a new NC syntax as a result of advanced functional developments or for syntax reasons. Previous commands may still be used for programming (downwards compatibility) but they should no longer be used to generate new NC programs. |
Old syntax: | New syntax | from version |
#SET DEC LR SOLL #VECTORVEL ON / OFF #VECTORACC ON / OFF #INIT MAKRO TAB | V2.10.1504.00 V2.10.1507.02 V2.10.1507.02 V2.11.2010.02 | |
G200 #ACHSE […] G201 #ACHSE […] G202 #ACHSE […] | V2.11.2010.02 V2.11.2010.02 V2.11.2010.02 | |
#GET IPO OFFSET #SET OFFSET [...] X #SET HR [...] X #SET TIP [...] X | V2.11.2010.02 V2.11.2010.02 V2.11.2010.02 V2.11.2010.02 | |
#SET JOG [...] X #SET IPO SOLLPOS […] #SET SLOPE PROFIL […] | V2.11.2010.02 V2.11.2010.02 V2.11.2010.02 | |
#SET ASPLINE STARTTANG X.. Y.. #SET ASPLINE ZIELTANG X.. Y.. #SET ASPLINE MODE [...] | V2.11.2010.02 V2.11.2010.02 V2.11.2010.02 | |
#SET CORNER PARAM [...] | V2.11.2010.02 | |
#SET TANGFEED RMIN [...] | V2.11.2010.02 | |
#SET SPLINE ON / OFF | V2.11.2010.02 | |
#SET SPLINETYPE AKIMA | V2.11.2010.02 | |
#SET SPLINETYPE BSPLINE | V2.11.2010.02 | |
#RTCP ON / OFF | all versions |