Error messages of the real-time driver of mxAutomation

No.

Message text

Cause

Remedy

701

INTERNAL ERROR

Internal exceptional error

Contact KUKA Deutschland GmbH. (>>> KUKA Service)

702

ASSERT FAILED

Internal exceptional error

703

INVALID COMMAND ID

Internal exceptional error

704

INVALID HEADER DATA

Internal exceptional error

709

ERROR READING SOFTPLC

Internal exceptional error

710

ERROR FROM KRC SUBMIT

Internal exceptional error

712

INVALID CHECKSUM PLC -> KRC

The checksum for data transmission from the PLC to the robot controller is invalid.

Contact KUKA Deutschland GmbH. (>>> KUKA Service)

713

INVALID MOVE TYPE

An invalid value has been programmed in a KRC_Move function block for the parameter MoveType.

Contact KUKA Deutschland GmbH. (>>> KUKA Service)

730

INVALID PTP APO

An invalid approximation parameter has been transferred for a PTP motion.

Program a valid value (Approximate parameter).

(>>> APO)

731

INVALID CP APO

An invalid approximation parameter has been transferred for a CP motion (LIN, CIRC).

732

INVALID BASE NUMBER

An invalid number has been programmed for the BASE coordinate system in the KRC_ReadBaseData or KRC_WriteBaseData function block.

Specify the number of the BASE coordinate system that is currently being used in the robot controller (BaseNo parameter).

  • 1 … 32

An invalid number has been programmed for the BASE coordinate system in a KRC_Move or KRC_Jog function block.

Specify the number of the BASE coordinate system that is currently being used in the robot controller (CoordinateSystem – COORDSYS.Base parameter).

(>>> COORDSYS)

733

INVALID TOOL NUMBER

An invalid number has been programmed for the TOOL coordinate system in the KRC_ReadToolData or KRC_WriteToolData function block.

Specify the number of the TOOL coordinate system that is currently being used in the robot controller (ToolNo parameter).

  • 1 … 16

An invalid number has been programmed for the TOOL coordinate system in a KRC_Move or KRC_Jog function block.

Specify the number of the TOOL coordinate system that is currently being used in the robot controller (CoordinateSystem – COORDSYS.Tool parameter).

(>>> COORDSYS)

734

INVALID VELOCITY

An invalid value has been programmed for the speed in a function block.

Program a valid value (Velocity parameter):

  • 0 … 100%
  • 0 … 2 m/s (only with the MC_MoveLinear and MC_MoveCircular blocks)

735

INVALID ACCELERATION

An invalid value has been programmed for the acceleration in a function block.

Program a valid value (Acceleration parameter):

  • 0 … 100%
  • 0 … 2.3 m/s2 (only with the MC_MoveLinear and MC_MoveCircular blocks)

736

INVALID C_PTP

An invalid approximation distance has been transferred for a PTP motion.

Program a valid value (Approximate parameter).

(>>> APO)

737

INVALID C_DIS

An invalid distance parameter has been transferred for an approximate positioning motion.

738

INVALID C_VEL

An invalid speed parameter has been transferred for an approximate positioning motion.

739

INVALID C_ORI

An invalid alignment parameter has been transferred for an approximate positioning motion.

740

INVALID ORI_TYPE

An invalid value has been programmed in a KRC_Move or KRC_Jog function block for the alignment control of the TCP.

Program a valid value (OriType parameter).

(>>> OriType)

741

POSITION DATA NOT INITIALIZED

No target position transferred when calling a KRC_Move function block.

Define at least 1 element of the target position (Position parameter).

(>>> E6POS)

742

AXISPOSITION DATA NOT INITIALIZED

No axis position transferred when calling a KRC_MoveAxis function block.

Define at least 1 axis position (AxisPosition parameter).

(>>> E6AXIS)

743

INVALID TRIGGER DISTANCE

An invalid value has been programmed for the switching point of the switch in a KRC_SetDistanceTrigger function block.

Program a valid value (Distance parameter):

  • 0: Switching action at the start point
  • 1: Switching action at the end point

744

INVALID TRIGGER IO

An invalid output has been programmed in a KRC_SetDistanceTrigger or KRC_SetPathTrigger function block.

Program a valid value (Output parameter):

  • 1 … 2048

745

INVALID TRIGGER PULSE

An invalid value has been programmed in a KRC_SetDistanceTrigger or KRC_SetPathTrigger function block for the pulse length.

Program a valid value (Pulse parameter):

  • 0.1 … 3.0 s
  • 0.0 s (no pulse active)

746

INVALID CIRC_HP

No auxiliary position transferred when calling a KRC_MoveCirc function block.

Define at least 1 element of the auxiliary position (CircHP parameter).

(>>> E6AXIS)

747

INVALID INTERRUPT IO

The number of the digital input for which the interrupt is declared is invalid (KRC_DeclareInterrupt function block).

Program a valid value (Input parameter):

  • 1 … 2048

748

INVALID INTERRUPT PRIORITY

An invalid number was transferred when calling a KRC_…Interrupt function block.

Program a valid value (Interrupt parameter):

  • 1 … 8

750

INVALID INTERRUPT ACTION

The interrupt reaction programmed during the declaration of the interrupt is invalid.

Program a valid reaction (Reaction parameter).

(>>> Declaring interrupts)

751

INVALID IO NUMBER

The number of the digital input for which the interrupt is declared is invalid (KRC_DeclareInterrupt function block).

Program a valid value (Input parameter):

  • 1 … 2048

752

INVALID PULSE DURATION

An invalid value has been programmed for the pulse length in the KRC_WriteDigitalOutput function block.

Program a valid value (Pulse parameter):

  • 0.1 … 3.0 s
  • 0.0 s (no pulse active)

753

INVALID BUFFER_MODE

An invalid BufferMode has been programmed in a function block, e.g. DIRECT mode is not available for certain function blocks.

Program a valid BufferMode.

(>>> BufferMode)

754

INVALID TOOL NUMBER FOR LOAD_DATA

An invalid number has been programmed in the KRC_ReadLoadData or KRC_WriteLoadData function block for reading or writing the load data or supplementary load data.

Program a valid value (Tool parameter).

(>>> Reading the load data)

(>>> Writing load data)

755

INVALID ANALOG IO NUMBER

An invalid value has been programmed in a function block for the analog input or output.

Program a valid value (Number parameter):

  • 1 … 32

756

INVALID IPO_MODE

An invalid value has been programmed in a function block for the interpolation type, e.g. KRC_Move.

Program a valid value (CoordinateSystem – COORDSYS.IPO_MODE parameter).

(>>> COORDSYS)

757

INVALID CIRC_TYPE

An invalid value has been programmed in a KRC_MoveCirc function block for the alignment control during the circular motion.

Program a valid value (CircType parameter).

(>>> CircType)

758

INVALID FRAME DATA

Invalid TOOL or BASE data have been programmed in a KRC_WriteToolData or KRC_WriteBaseData function block.

Program valid data (parameter ToolData or BaseData).

(>>> Writing TOOL data)

(>>> Writing BASE data)

759

INVALID LOAD DATA

Invalid load data have been programmed in a KRC_WriteLoadData function block.

Program valid data.

(>>> Writing load data)

760

INVALID SOFT_END (REVERSED)

Error when writing the software limit switches: positive software limit switch < negative software limit switch (KRC_WriteSoftEnd or KRC_WriteSoftEndEx function block)

Program lower values for the negative software limit switch than for the positive software limit switch.

765

INVALID REAL VALUE

The programmed Real value is invalid.

  • -2147483500 … +2147483500

770

INVALID PARAMETER VALUE

An invalid value has been programmed in the called function block for one or more parameters.

Program valid values for the parameters.

771

INVALID ADVANCE COUNT

In the KRC_SetAdvance function block, an invalid value has been programmed for the number of functions that are to be transferred prior to the first robot motion.

Program a valid value (Count parameter):

  • 1 … 50

772

INVALID MAXWAITTIME

In the KRC_SetAdvance function block, an invalid value has been programmed for the maximum delay time before the start of the program execution if the specified number of functions in the Count parameter is not reached.

Program a valid value (MaxWaitTime parameter):

  • 1 … 32 767 ms

773

INVALID ADVANCE MODE

In the KRC_SetAdvance function block, an invalid value has been programmed for wait mode.

Program a valid value (Mode parameter):

  • 0 … 2

774

INVALID DI STARTNUMBER

In the KRC_ReadDigitalInputArray function block, an invalid value has been programmed for the number of the first digital input that is called.

Program a valid value (Startnumber parameter):

  • 1 … 2048

775

INVALID DI LENGTH

In the function block KRC_ReadDigitalInputArray, an invalid value has been programmed for the number of inputs that are polled.

Program a valid value (Length parameter):

  • 1 … 200

780

INVALID WORKSPACENO

In the called function block, an invalid number has been programmed for the number of the workspace.

Program a valid value (WorkspaceNo parameter):

  • 1 … 8

781

INVALID WORKSPACEMODE

In the called function block, an invalid number has been programmed for the mode for workspaces.

Program a valid value (WorkspaceMode parameter):

  • 0 … 4

782

INVALID WORKSPACEPART

Internal exceptional error

Contact KUKA Deutschland GmbH. (>>> KUKA Service)

783

UDP CONNECTION TIMEOUT

Connection timeout during UDP communication

Check the IP addresses of the two connection points and the cable between them. Define a longer value for the timeout in the mxa_config.dat file.

801

STOPMESS ACTIVE

Group error that prevents motion enable

Check how the error was triggered and correct the error.

  • Analyze the messages in the message window of the iiQKA.OS2 user interface.
  • Read the current error state of the robot controller with the KRC_ReadKRCError function block.