FB_MBUS_REL_PadPulsM1

The function block FB_MBUS_REL_PadPulsM1 is used to read energy meters with pulse output from Relay:
-PadPuls M1
-PadPuls M1C
The function block can only be executed together with the function block FB_MBUSKL6781().
![]()  | Further information  | 
 Inputs
VAR_INPUT
  usiAddress   : USINT;
  stSecAdr     : ST_MBUS_SecAdr;
  eBaudrate    : E_MBUS_Baudrate := eMBUS_Baud2400;
  bStart       : BOOL;
  bSND_NKE     : BOOL := TRUE;
  bReadInit    : BOOL := TRUE;
  tMinSendTime : TIME := t#2s;
  usiUnit      : USINT;
  bDisabled    : BOOL := FALSE;
END_VARName  | Type  | Description  | 
|---|---|---|
usiAddress  | USINT  | Primary address of the meter to be read with this function block.  | 
stSecAdr  | Secondary address of the meter to be read with this function block.  | |
eBaudrate  | 300, 2400, 9600 baud  | |
bStart  | BOOL  | All meters are read once on the positive edge of this input.  | 
bSND_NKE  | BOOL  | TRUE initializes the meter for each read operation and sets the meter to the first telegram (SND_NKE).  | 
bReadInit  | BOOL  | If the PLC is restarted, the meter is read once.  | 
tMinSendTime  | TIME  | Default t#2s. The meter is read again, once the time set here has elapsed. If t#0s the meter is not read and can be read manually with bStart.  | 
usiUnit  | USINT  | Unit of the energy values to be output by the function block. 0=W(h) / 1=KW(h) / 2 =MW(h) / 3=GW(h).  | 
bDisabled  | BOOL  | TRUE = deselection of the function block  | 
 Inputs/outputs
VAR_IN_OUT
  stCom : ST_MBUS_Communication;
END_VARName  | Type  | Description  | 
|---|---|---|
stCom  | This structure is used to link the function block FB_MBUSKL6781() with the meter blocks.  | 
 Outputs
VAR_OUTPUT
  bBusy            : BOOL;
  bReady           : BOOL;
  bError           : BOOL;
  eError           : E_MBUS_ERROR;
  dwIdNumber       : DWORD;
  byStatus         : BYTE;
  byGEN            : BYTE;
  byCounter        : BYTE;
  usiRecivedAdr    : USINT;
  eMedium          : E_MBUS_Medium;
  sMan             : STRING(3);
  stValue          : ST_MBus_Info;
  byNumerator      : BYTE;
  byDenominator    : BYTE;
END_VARName  | Type  | Description  | 
|---|---|---|
bBusy  | BOOL  | The bBusy output is TRUE as long as the meter is being read.  | 
bReady  | BOOL  | The bReady output is TRUE for one cycle, once meter reading is completed.  | 
bError  | BOOL  | This output goes TRUE as soon as an error occurs. This error is described via the eError variable.  | 
eError  | This output outputs an error code in the event of an error. bError goes TRUE at the same time.  | |
dwIdNumber  | DWORD  | Serial number of the meter (secondary address)  | 
byStatus  | BYTE  | Device status  | 
byGEN  | BYTE  | Software version of the device  | 
byCounter  | BYTE  | Number of times the master has accessed data of the respective slave  | 
usiRecivedAdr  | USINT  | Received primary address (0-250)  | 
eMedium  | Medium  | |
sMan  | STRING  | Manufacturer sign  | 
stValue  | Meter reading  | |
byNumerator  | BYTE  | Pulse value numerator (range 1..255)  | 
byDenominator  | BYTE  | Pulse value denominator (range 1..255)  | 
Requirements
Development Environment  | PLC library to include  | 
|---|---|
TwinCAT from v3.1.4020.14  | Tc2_MBus from 3.3.5.0  | 