FB_MBUS_EMU_3_5_Allrounder
This block is used to read electricity meters from EMU.
The block can only be executed together with the block FB_MBUSKL6781().
VAR_INPUT
usiAddress : USINT;
stSecAdr : ST_MBUS_SecAdr;
eBaudrate : E_MBUS_Baudrate := eMBUS_Baud2400;
bStart : BOOL;
bSND_NKE : BOOL := TRUE;
bReadInit : BOOL := TRUE;
tMinSendTime : TIME := t#2s;
bDisabled : BOOL := FALSE;
usiAddress: Primary address of the meter to be read with this block.
stSecAdr: Secondary address of the meter to be read with this block (see ST_MBUS_SecAdr).
eBaudrate: 300..9600 baud (see E_MBUS_Baudrate).
bStart: A positive edge of this input triggers one reading of the meter.
bSND_NKE: TRUE initializes the meter for each read operation and sets the meter to the first telegram (SND_NKE).
bReadInit: If the PLC is restarted, the meter is read once.
tMinSendTime: Standard t#2s. The meter is read again, once the time set here has elapsed. If t#0s the meter is not read and can be read manually with bStart.
bDisabled: TRUE = deselection of the block.
VAR_OUTPUT
bBusy : BOOL;
bReady : BOOL;
bError : BOOL;
eError : E_MBUS_ERROR;
dwIdNumber : DWORD;
byStatus : BYTE;
byGEN : BYTE;
byCounter : BYTE;
usiRecivedAdr : USINT;
eMedium : E_MBUS_Medium;
sMan : STRING(3);
stActiveEnergyTariff1 : ST_MBus_Info;
stActiveEnergyTariff2 : ST_MBus_Info;
stActivePowerL1 : ST_MBus_Info;
stActivePowerL2 : ST_MBus_Info;
stActivePowerL3 : ST_MBus_Info;
stActivePowerTotal : ST_MBus_Info;
stVoltageL1 : ST_MBus_Info;
stVoltageL2 : ST_MBus_Info;
stVoltageL3 : ST_MBus_Info;
stCurrentL1 : ST_MBus_Info;
stCurrentL2 : ST_MBus_Info;
stCurrentL3 : ST_MBus_Info;
stCurrentTotal : ST_MBus_Info;
stDeviceError : ST_MBus_Info;
bBusy: The bBusy output is TRUE while the meter is being read.
bReady: The bReady output is TRUE for one cycle, once meter reading is completed.
bError: this output goes TRUE as soon as an error occurs. This error is described via the variable eError.
eError: In the event of an error the output issues an error code (see E_MBUS_ERROR). bError goes TRUE at the same time.
dwIdNumber: Serial number of the meter (secondary address).
byStatus: Device status.
byGEN: Software version of the device.
byCounter: Number of times the master has accessed data of the respective slave.
usiRecivedAdr: Received primary address (0-250).
eMedium: Medium (see E_MBUS_Medium).
sMan: Manufacturer code.
stActiveEnergyTariff1: Active energy tariff 1 (see ST_MBus_Info).
stActiveEnergyTariff2: Active energy tariff 2 (see ST_MBus_Info).
stActivePowerL1: Effective power L1 (see ST_MBus_Info).
stActivePowerL2: Effective power L2 (see ST_MBus_Info).
stActivePowerL3: Effective power L3 (see ST_MBus_Info).
stActivePowerTotal: Total effective power (see ST_MBus_Info).
stVoltageL1: Voltage L1 (see ST_MBus_Info).
stVoltageL2: Voltage L2 (see ST_MBus_Info).
stVoltageL3: Voltage L3 (see ST_MBus_Info).
stCurrentL1: Current intensity L1 (see ST_MBus_Info).
stCurrentL2: Current intensity L2 (see ST_MBus_Info).
stCurrentL3: Current intensity L3 (see ST_MBus_Info).
stCurrentTotal: Total current intensity (see ST_MBus_Info).
stDeviceError: Error message from device (see ST_MBus_Info).
VAR_IN_OUT
stCom : ST_MBUS_Communication;
stCom: This structure is used to link the block FB_MBUSKL6781() with the meter blocks (see ST_MBUS_Communication).
Requirements
Development environment | required TC3 PLC library |
---|---|
TwinCAT from v3.1.4020.14 | Tc2_MBus from 3.3.4.0 |