FB_MBUS_ABB_DZ

The function block FB_MBUS_ABB_DZ is used to read electricity meters from ABB:
-DELTAplus DZ+
The function block can only be executed together with the function block FB_MBUSKL6781().
|  | Further information | 
 Inputs
 Inputs
VAR_INPUT
  usiAddress   : USINT;
  stSecAdr     : ST_MBUS_SecAdr;
  eBaudrate    : E_MBUS_Baudrate := eMBUS_Baud2400;
  bStart       : BOOL;
  bSND_NKE     : BOOL := TRUE;
  bReadInit    : BOOL := TRUE;
  tMinSendTime : TIME := t#2s;
  usiUnit      : USINT;
  bDisabled    : BOOL := FALSE;
END_VAR| Name | Type | Description | 
|---|---|---|
| usiAddress | USINT | Primary address of the meter to be read with this function block. | 
| stSecAdr | Secondary address of the meter to be read with this function block. | |
| eBaudrate | 300, 600, 1200, 2400, 4800, 9600 baud | |
| bStart | BOOL | All meters are read once on the positive edge of this input. | 
| bSND_NKE | BOOL | TRUE initializes the meter for each read operation and sets the meter to the first telegram (SND_NKE). | 
| bReadInit | BOOL | If the PLC is restarted, the meter is read once. | 
| tMinSendTime | TIME | Default t#2s. The meter is read again, once the time set here has elapsed. If t#0s the meter is not read and can be read manually with bStart. | 
| usiUnit | USINT | Unit of the energy values to be output by the function block. 0=W(h) / 1=KW(h) / 2 =MW(h) / 3=GW(h). | 
| bDisabled | BOOL | TRUE = deselection of the function block | 
 Inputs/outputs
 Inputs/outputs
VAR_IN_OUT
  stCom : ST_MBUS_Communication;
END_VAR| Name | Type | Description | 
|---|---|---|
| stCom | This structure is used to link the function block FB_MBUSKL6781() with the meter blocks. | 
 Outputs
 Outputs
VAR_OUTPUT
  bBusy           : BOOL;
  bReady          : BOOL;
  bError          : BOOL;
  eError          : E_MBUS_ERROR;
  dwIdNumber      : DWORD;
  byStatus        : BYTE;
  byGEN           : BYTE;
  byCounter       : BYTE;
  usiRecivedAdr   : USINT;
  eMedium         : E_MBUS_Medium;
  sMan            : STRING(3);
  stActiveEnergy  : ST_MBus_Info;
  stReactiveEnergy: ST_MBus_Info;
  stActivePower   : ST_MBus_Info;
  stReactivePower : ST_MBus_Info;
  stCurrentL1     : ST_MBus_Info;
  stCurrentL2     : ST_MBus_Info;
  stCurrentL3     : ST_MBus_Info;
  stPowerFactor   : ST_MBus_Info;
END_VAR| Name | Type | Description | 
|---|---|---|
| bBusy | BOOL | The bBusy output is TRUE as long as the meter is being read. | 
| bReady | BOOL | The bReady output is TRUE for one cycle, once meter reading is completed. | 
| bError | BOOL | This output goes TRUE as soon as an error occurs. This error is described via the eError variable. | 
| eError | This output outputs an error code in the event of an error. bError goes TRUE at the same time. | |
| dwIdNumber | DWORD | Serial number of the meter (secondary address) | 
| byStatus | BYTE | Device status | 
| byGEN | BYTE | Software version of the device | 
| byCounter | BYTE | Number of times the master has accessed data of the respective slave | 
| usiRecivedAdr | USINT | Received primary address (0-250) | 
| eMedium | Medium | |
| sMan | STRING | Manufacturer sign | 
| stActiveEnergy | Meter reading, total active energy | |
| stReactiveEnergy | Meter reading, total reactive energy | |
| stActivePower | Current consumption, total active power | |
| stReactivePower | Current consumption, total reactive power | |
| stCurrentL1 | Current L1 | |
| stCurrentL2 | Current L2 | |
| stCurrentL3 | Current L3 | |
| stPowerFactor | Total power factor | 
Requirements
| Development Environment | PLC library to include | 
|---|---|
| TwinCAT from v3.1.4020.14 | Tc2_MBus from 3.3.5.0 |