IP5209-Bxxx

1 channel SinCos encoder interface

The IP5209 Sinus/Cosinus module functions as a interface to the higher level fieldbus for direct connection of an measuring sensor, such as a sensing switch or encoder with 1Vss sinusoidal voltage output. The measuring signal is processed, interpolated and made available as a 32 bit value. The signal period resolution is 10 bit, i.e. 1024 steps. The interpolation rate can be changed via the register R35. The change of counting direction is set via R32. The reference mark (Latch) is also stored in a 32 bit value. The current value of the counter and the value of the reference mark can be read and can be set. The maximum  frequency for the signal input is 100 kHz.

The input frequency and therefore the velocity of the sensor, can be checked against a preset limit. If this limit is exceeded, an error bit in the Status byte will be set!

IP5209-Bxxx 1:

 

Technical data

IP5209-Bxxx

Number of counters

1

Encoder connection

M23 screw-in, 12-pin

Sensor supply

5 VDC from the control voltage, max. 0.5 A

Limit frequency

100 kHz (scanning of the input signals with 500 kHz)

Resolution

10 bit, 1024 steps per period

Commands

Clear/set counter value, reference mark – latch, counting direction, scaling

Power supply

Feed: 1 x M8 connector, 4-pin; downstream connection: 1 x M8 socket, 4-pin

Bits in process image

I/O: 2(1) x 32 bit data (1 x 8 bit control/status)

Electrical isolation

depends on the bus system

Permissible ambient temperature during operation

0°C ... +55°C

Permissible ambient temperature during storage

-25 °C ... +85°C

Vibration / shock resistance

conforms to EN 60068-2-6 / EN 60068-2-27

EMC resistance burst / ESD

conforms to EN 61000-6-2 / EN 61000-6-4

Protection class

IP65, IP66, IP67 (conforms to EN 60529)

Installation position

variable

See the connection diagram for the connector pin assignment.

See the parameterization description for details of the parameterization.

See the mapping description for details of the mapping.

See dimension page for weight and dimensions.