IP5009-Bxxx, IE5009

1 channel SSI sensor interface

The IP5009 SSI interface module allows an SSI sensor to be connected directly. The sensor is powered via the SSI interface. The interface circuit generates a pulse for reading the sensor, and makes the incoming data stream available to the controller as a data word in the process image. The module can optionally provide the data as binary numbers or as a Gray code. Adaptation for the direction of rotation can be configured. Various operating modes, transmission frequencies and bit widths can be permanently stored in a control register.

IP5009-Bxxx, IE5009 1:

Technical data

IP5009-Bxxx / IE5009

Number of channels

1

Encoder connection

M23 screw-in, 12-pin

Signal type

Differential signal (RS485)

Sensor supply

24 VDC, from load voltage

Data transfer rate

adjustable up to 1 MHz, 250 kHz preset

Serial input

24 bits (adjustable)

Data direction

read

Power supply

Feed: 1 x M8 connector, 4-pin; downstream connection: 1 x M8 socket, 4-pin

Bits in process image

32 input bits for process data,
Optional: 8 output bits for control byte and 8 input bits for status byte

Electrical isolation

depends on the bus system

Permissible ambient temperature during operation

0°C ... +55°C

Permissible ambient temperature during storage

-25 °C ... +85°C

Vibration / shock resistance

conforms to EN 60068-2-6 / EN 60068-2-27

EMC resistance burst / ESD

conforms to EN 61000-6-2 / EN 61000-6-4

Protection class

IP65, IP66, IP67 (conforms to EN 60529)

Installation position

variable

See the connection diagram for the connector pin assignment.

See the parameterization description for details of the parameterization.

See the mapping description for details of the mapping.

See the derating description for details of the output current vs. frequency.

See dimension page for weight and dimensions.