Operating modes
Permissible operating modes for the EL5151
The following modes are available for the EL5151. They apply both for the encoder analysis and counter terminal mode.
The combinations of DC, PDO and CoE settings listed below are permissible per mode. Other settings can lead to irregular process data and error messages in the TwinCAT System Manager Logger window.
Mode | DC | Main PDO | Optional PDO 1 | Optional PDO 2 | Features CoE |
|---|---|---|---|---|---|
1 | FreeRun | Predefined PDO Assignment: “Standard 32‑bit (MDP 511)”: | CoE combinations
| ||
0x1A00 Inputs: + 0x1600 Outputs: | --
| ||||
2 | FreeRun | Predefined PDO Assignment: “Standard 16‑bit (MDP 511)”: | CoE combinations
| ||
0x1A01 Inputs: + 0x1601 Outputs: | -
| ||||
3 | DC/DCi | Predefined PDO Assignment: | CoE combinations
| ||
0x1A00 Inputs: + 0x1600 Outputs: | 0x1A04
| ||||
4 | DC/DCi | Predefined PDO Assignment: | CoE combinations
| ||
0x1A01 Inputs: + 0x1601 Outputs: | 0x1A04
| ||||
Permissible operating modes for the EL5152
The following modes are available for the EL5152. They apply both for the encoder analysis and counter terminal mode.
The combinations of DC, PDO and CoE settings listed below are permissible per mode. Other settings can lead to irregular process data and error messages in the TwinCAT System Manager Logger window.
Mode | DC | Main PDO | Optional PDO 1 | Features CoE |
|---|---|---|---|---|
1 | FreeRun | Predefined PDO Assignment: “Standard 32‑bit (MDP 511)”: | CoE combinations | |
Channel 1 / Channel 2 0x1A00 / 0x1A04 Status: + 0x1600 / 0x1602Control: | ||||
2 | FreeRun | Predefined PDO Assignment: “Standard 16 Bit (MDP 511)”: | CoE combinations | |
Channel 1/ Channel 2 0x1A01 / 0x1A05 Status compact: + 0x1601 / 0x1603 Control compact: | ||||
3 | DC/DCi | Predefined PDO Assignment: “Standard 32 Bit (MDP 511)”: | CoE combinations | |
Channel 1 / Channel 2 0x1A00 / 0x1A04 Status: + 0x1600 / 0x1602Control: | ||||
4 | DC/DCi | Predefined PDO Assignment: “Standard 16 Bit (MDP 511)”: | CoE combinations | |
Channel 1/ Channel 2 0x1A01 / 0x1A05 Status compact: + 0x1601 / 0x1603 Control compact: | ||||
![]() | Parameterization of the EL515x
|