Features CoE

Notice

Features CoE 1:

Parameterization via the CoE list (CAN over EtherCAT)

The EtherCAT device is parameterized via the CoE - Online tab (with a double click on the respective object) or via the Process Data tab (assignment of PDOs). A detailed description can be found in the EtherCAT System-Documentation in chapter “EtherCAT subscriber configuration”

Please note the general CoE notes in the EtherCAT System Documentation in chapter “CoE-interface” when using/manipulating the CoE parameters:
- Keep a startup list if components have to be replaced
- Differentiation between online/offline dictionary,
- existence of current XML description
- use “CoE reload” for resetting changes

Depending on the main PDO/optional PDOs further settings can be selected in the CoE (CAN over EtherCAT list).

The following CoE settings from objects 0x8000 and 0x8001 are possible and are shown below in their default settings:

Features CoE 2:
Fig.38: “CoE-Online” tab

The parameters are described on page object description and parameterization.

“Register Reload”

If “Register Reload” is enabled in CoE object 0x8000:01, the counter value is set

“Index Reset”

If “Index Reset” is enabled in CoE object 0x8000:02, input C resets the counter to 0.

Features CoE 3:

“Register Reload” and “Index Reset”

“Register Reload” and “Index Reset” cannot be operated simultaneously.

Forward/backward counter “Enable FWD count”

If “Enable FWD Count” is activated in CoE object 0x8000:03, the EL5101 operates as counter on channel A. Channel B indicates the counting direction: B = TRUE forward, B = FALSE backward.
The counter can be locked via the gate input (24 V).

Frequency

Features CoE 4:
Fig.39: Frequency measurement principle in normal operation mode

Period calculation

Features CoE 5:

Frequency and period measurement

From the explanatory notes above it is apparent that the frequency measurement can measure the current axis status (velocity) significantly more accurately than the period measurement. Frequency measurement is therefore preferable, if possible.

Latch

Latch control is implemented via the control and status word.