Objects for commissioning

Index 4061 Feature bits (EL5001 only)

Index (hex)

Name

Meaning

Data type

Flags

Default

4061:0

Feature bits

Length of this object

UINT8

RO

0x04 (4dec)

4061:01

disable frame error

0: Frame error is not suppressed
1: Frame error is suppressed

BOOLEAN

RW

0x00 (0dec)

4061:02

enable power failure bit

0: Power failure bit is not active
1: Power failure bit is active: The last bit of the data frame (encoder-specific error bit) is shown as error bit in Bit 2 of the status word.

BOOLEAN

RW

0x00 (0dec)

4061:03

enable inhibit time

0: Inhibit time is not active
1: Inhibit time is active

BOOLEAN

RW

0x00 (0dec)

4061:04

enable test mode

0: Test mode is not active
1: Test mode is active

BOOLEAN

RW

0x00 (0dec)

Index 4066 SSI coding (only EL5001)

Index (hex)

Name

Meaning

Data type

Flags

Default

4066:0

SSI coding

0: Binary code active
1: Gray code active

UINT16

RW

0x0001 (1dec)

Index 4067 SSI baud rate (only EL5001)

Index (hex)

Name

Meaning

Data type

Flags

Default

4067:0

SSI baud rate

0: reserved
1: 1250 kbaud
2: 1000 kbaud
3: 500 kbaud
4: 250 kbaud
5: 125 kbaud
6 - 65535: reserved

UINT16

RW

0x0003 (3dec)

Index 4068 SSI frame type (only EL5001)

Index (hex)

Name

Meaning

Data type

Flags

Default

4068:0

SSI-frame type

0: Multi-turn analysis is active (25-bit data frame)
1: Single-turn-analysis is active (13-bit data frame)
2: Variable analysis is active. The length of the data frame (1 to 32 bit) is specified via object 0x4069.

UINT16

RW

0x0000 (0dec)

Index 4069 SSI frame size (only EL5001)

Index (hex)

Name

Meaning

Data type

Flags

Default

4069:0

SSI frame size

Length of the SSI data frame (in bits)

Min. : 0dec
Max.: 32dec

UINT16

RW

0x0019 (25dec)

Index 406A data length (only EL5001)

Index (hex)

Name

Meaning

Data type

Flags

Default

406A:0

Data length

Data length

Min. : 0dec
Max.: 32dec

UINT16

RW

0x0018 (24dec)

Index 406B min. inhibit time [µs] (only EL5001)

Index (hex)

Name

Meaning

Data type

Flags

Default

406B:0

Min. inhibit time[µs]

Minimum inhibit time in µs (1 to 65535)

UINT16

RW

0x0000 (0dec)

Index 80n0 SSI settings (only EL5002), with n = 0 (Ch.1), n = 1 (Ch.2)

Index (hex)

Name

Meaning

Data type

Flags

Default

80n0:0

SSI settings

Length of this object

UINT8

RO

0x13 (19dec)

80n0:01

Disable frame error

0: Frame error is not suppressed
1: Frame error is suppressed

BOOLEAN

RW

0x00 (0dec)

80n0:02

Enable power failure bit

0: Power failure bit is not active
1: Power failure bit is active: The last bit of the data frame (encoder-specific error bit) is shown as error bit in 0x60n0:03 of the status word.

BOOLEAN

RW

0x00 (0dec)

80n0:03

Enable inhibit time

0: Inhibit time is not active
1: Inhibit time is active

BOOLEAN

RW

0x00 (0dec)

80n0:04

Enable test mode

0: Test mode is not active
1: Test mode is active

BOOLEAN

RW

0x00 (0dec)

80n0:06

SSI coding

0: Binary code active
1: Gray code active

BIT1

RW

0x01 (1dec)

80n0:09

SSI baud rate

0: reserved
1: 1250 kbaud
2: 1000 kbaud
3: 500 kbaud
4: 250 kbaud
5: 125 kbaud
6 - 65535: reserved

BIT3

RW

0x03 (3dec)

80n0:0C***

Enable SSI clock jitter compensation***

0: SSI clock jitter compensation is disabled (default)
1: SSI clock jitter compensation is enabled

BIT3

RW

0x00 (0dec)

80n0:0F

SSI-frame type

0: Multi-turn analysis is active (25‑bit data frame)
1: Single-turn-analysis is active (13-bit data frame)
2: Variable analysis is active. The length of the data frame (1 to 32 bit) is specified via object 0x80n0:11.

BIT2

RW

0x00 (0dec)

80n0:11

SSI frame size

Length of the SSI data frame (in bits)

Min. : 0dec
Max.: 32dec

UINT16

RW

0x0019 (25dec)

80n0:12

SSI data length

Data length

Min. : 0dec
Max.: 32dec

UINT16

RW

0x0018 (24dec)

80n0:13

Min. inhibit time[µs]

Minimum inhibit time in µs (1 to 65535)

UINT16

RW

0x0000 (0dec)

80n0:14***

Number of clock bursts***

Number of clock bursts
1: single transmission is active (Default)
2: multiple transmission with 2 clock bursts
3: multiple transmission with 3 clock bursts

UINT16

RW

0x0000 (0dec)

***) from FW03

Index 8010 SSI settings (from FW11 in the case of EL5001)

Index (hex)

Name

Meaning

Data type

Flags

Default

8010:0

SSI settings

Length of this object

UINT8

RO

0x13 (19dec)

8010:01

Disable frame error

0: Frame error is not suppressed
1: Frame error is suppressed

BOOLEAN

RW

0x00 (0dec)

8010:02

Enable power failure bit

0: Power failure bit is not active
1: Power failure bit is active: the last bit of the data frame (encoder-specific error bit) is shown as an error bit in object 0x6010:03 and bit 2 of the status word.

BOOLEAN

RW

0x00 (0dec)

8010:03

Enable inhibit time

0: Inhibit time is not active
1: Inhibit time is active

BOOLEAN

RW

0x00 (0dec)

8010:04

Enable test mode

0: Test mode is not active
1: Test mode is active

BOOLEAN

RW

0x00 (0dec)

8010:06

SSI coding

0: Binary code active
1: Gray code active

BIT1

RW

0x01 (1dec)

8010:09

SSI baud rate

0: reserved
1: 1250 kbaud
2: 1000 kbaud
3: 500 kbaud
4: 250 kbaud
5: 125 kbaud
6 - 65535: reserved

BIT3

RW

0x03 (3dec)

8010:0F

SSI-frame type

0: Multi-turn analysis is active (25‑bit data frame)
1: Single-turn-analysis is active (13‑bit data frame)
2: Variable analysis is active. The length of the data frame (1 to 32 bit) is specified via object 0x8010:11.

BIT2

RW

0x00 (0dec)

8010:11

SSI frame size

Length of the SSI data frame (in bits)

UINT16

RW

0x0019 (25dec)

8010:12

SSI data length

Data length

UINT16

RW

0x0018 (24dec)

8010:13

Min. inhibit time[µs]

Minimum inhibit time in µs (1 to 65535)

UINT16

RW

0x0000 (0dec)