Quick start

Table of contents

EL3692 default setting

The default state for both EL3692 channels is

Quick start 1:

Time behavior in Autorange mode

In standard measuring mode the EL3692 keeps switching between the two channels. Depending on the connected measuring object significant charging effects may occur, which may not be completed within the specified measuring time. In Autorange mode, with significant changes in resistance and associated changes in measuring range, this may result in the correct measuring range not being reached, which would impair the measuring accuracy.
By extending the delay before the measurement, sufficient time for charging processes can be made available to ensure that the correct measuring range is reached in Autorange mode. Should the automatic setting be inadequate, the user can change the measuring time in the CoE, 0x80n0:31.

Step-by-step instructions

Proceed as follows for commissioning with the above-mentioned settings:

  1. Install the EL3692 as described in section Installation and wiring.
  2. Activate the EtherCAT master and start the terminal in OP state. In the input variables the EL3692 must supply state=OP and WC=0.
  3. Connect the resistance in 2-wire or 4-wire mode according to the figure below
  4. Quick start 2:Fig.138: Connection examples
  5. In TwinCAT the EL3692 appears as follows (channel 1 red grouped, channel 2 blue grouped):
Quick start 3:Fig.139: EL3692 representation in the TwinCAT System Manager

Please note the information relating to the process data.

5. for 2-wire measurement: In CoE entry x80n0:0D set the mode to 2 (n stands for the channel: 0 = channel 1, 1 = channel 2).
If necessary the EL3692 can be reset to the factory settings via a CoE reset.

Quick start 4:

Measured value display

The EL3692 can output the current channel-based measured value depending on the PDO option "Predefined PDO assignment" in 2 different ways. As "fixpoint" and "float". See following explanation:

Input resistance

 

32-bit value

Interpretation

Status bits

0 Ω

 

x00 00 00 00

0

Extended Range = 0

Overrange = 0

10 Ω

Nominal measuring range end value

x00 7F FF FF

8.388.607

extended range = 1 "extended measuring range"

Overrange = 0

10 .. 11 Ω

extended measuring range

 

 

Extended Range = 1

Overrange = 0

> 11 Ω

 

x00 8C CC CB

9.227.467

Extended Range = 0

Overrange = 1

Please note that the relative measurement error is very large at the lower end of the measuring range. When measuring in the range < 10% of the nominal measuring range end value, the next lower measuring range should therefore be used. The autorange function works accordingly.

6. You have to check the correct operation of the range change function in the autorange opration mode for all test specimens. This is mandatory in the special case, if test specimens with very different resistance/capacity/inductive values are connected to channel 1 and 2 (> 3 measuring ranges). An unoccupied channel will measure in the measuring range 7 (1 MΩ .. 10 MΩ).
This can be compensated channel-wise by the extension of the delay time (CoE 0x80n0:31), if the automatic setting is not sufficient. The delay time should be increased stepwise for the channel, which has not the optimal range setting.

7. During the operation, the channel-wise process data value has to be verified by checking of the state variables Error, DataInvalid  and SteadyState.

For further configuration in TwinCAT please refer to sections Process data and Important CoE entries.