Electrical installation

WARNING

Avoid contact with DC link DC+ and DC-

Measure the voltage on the DC link test contacts DC+ and DC-. Wait 30 minutes after disconnecting from the mains supply.

There is still a life-threatening voltage of > 848 V DC on the capacitors after disconnection from the supply network. Serious or even fatal injuries may result if this is ignored.

Notice

Damage to the product and EMC interference emission

Improper grounding or faulty contacting can lead to damage to the multi-axis servo system or to EMC interference emissions. The shields on the pre-assembled motor cables are intended solely to return the commutation currents directly to the servo drives and to prevent electromagnetic interference. Additional shield windows or shield connections on the motor cable can cause unwanted interference.

  • Follow the guidelines for EMC-compliant wiring
  • For separate protective conductors, use the minimum cross-sectional areas specified in DIN EN 61439-1.

Requirements for electromagnetic compatibility (EMC)

►Original Beckhoff motor cables should be used, as EMC tests have been conducted successfully using these cables.
►Establish a conductive connection of all components
►Only use shielded cables
►Ground the devices' PE connections via the mounting plate, and position the star point centrally on the unpainted mounting plate.
►For larger applications, implement the potential equalization via PE rails
►For separate protective conductors, use the minimum cross-sectional areas specified in DIN EN 61439-1.
►Ensure that all relevant components are grounded using a connection with the largest possible cross-sectional area, low impedance, a large contact area, and a short path
►Ground the shield of the motor cable only at the cable ends: at the servo drive using the shield clamps, which are connected directly to the conductive device housing. On the motor side, via the motor connector and the motor housing.
►Make a connection between the motor flange and the grounded machine bed with as low an impedance as possible and over a large area.
►Do not add any additional shield windows or shielding connections.