16-channel digital combi, 24 V DC, 3 ms, 0.5 A

The EtherCAT P Box EPP23x9 has 16 digital channels, each of which can be configured as either an input or an output. A configuration whether a channel is to be used as input or output is not required; the input circuit is internally permanently connected to the output driver so that a set output is automatically displayed in the input process image.

The outputs are short-circuit proof and protected against polarity reversal and process load currents up to 0.5 A, whereby the total current is limited to 3 A. The signals are optionally connected via M8 connectors (EPP23x9-0021) or M12 connectors (EPP23x9-0022). The connectors with spring-loaded technology are available in 1 and 3-pin versions.

The signal state is indicated by means of LEDs.

Sensors are supplied from the peripheral voltage UP.

Notice

Damage to sensitive signal transducers due to current peaks

The protective circuit of a digital input can cause an inrush current peak of well over 2 mA during the switching operation. This current spike can damage sensitive signal transducers such as reed switches.

  • When using sensitive signal transducers, insert a series resistor before the digital input to reduce the inrush current peak. E.g. 1 kΩ