S-0-0011 Class 1 diagnostic (C1D)

The parameter contains error groups that trigger a "drive shut down" error.

Attributes

Name

Value

Datatype

binary

Data length in bit

16

Decimal point

0

Min value

-

Default

0

Max value

-

Unit

-

Changeable in EtherCAT state

No

Cyclic transfer

AT

Device parameter

No

Related to interface revision

No

Drive shut-down error. A drive error situation of class C1D leads to the following: A best case deceleration followed by torque/force release at nmin. The drive shut-down error bit for C1D is set to '1' in the drive status (bit 13). The error bit is reset to '0' by the drive only when no errors of C1D exists and after the command 'reset class 1 diagnostic' (IDN S-0-0099) has been received by the drive.

Bit pattern:

Bit

Meaning

0

Motor overload shut down
Motor overload shut down

0 = no error
1 = error

1

Heatsink overtemperature shut down
Amplifier overtemperature shut down

0 = no error
1 = error

2

Motor overtemperature shut down
Motor overtemperature shut down

0 = no error
1 = error

3

Drive overtemperature shut down
Drive overtemperature shut down

0 = no error
1 = error

4

Control voltage error
Control voltage error

0 = no error
1 = error

5

Feedback error
Feedback error

0 = no error
1 = error

6

Commutation error
Commutation error

0 = no error
1 = error

7

Overcurrent error
Overcurrent error

0 = no error
1 = error

8

Overvoltage error
Overvoltage error

0 = no error
1 = error

Bit

Meaning

9

Undervoltage error
Undervoltage error

0 = no error
1 = error

10

Power supply phase error
Power supply phase error

0 = no error
1 = error

11

Excessive position deviation
Excessive position deviation

0 = no error
1 = error

12

Communication error
Communication error bit

0 = no error
1 = error

13

Overtravel limit exceeded
Overtravel limit exceeded (shut down)

0 = no error
1 = error

14

Reserved

15

Manufacturer specific error
Manufacturer specific error

0 = no error
1 = error

S-0-0011 Class 1 diagnostic (C1D) 1:

IDN P-0-0350 - Error reaction check word

With this IDN you can parameterise a general reaction to an error and/or influence the behaviour of the two axes in the case of a 2-channel AX5000.

S-0-0011 Class 1 diagnostic (C1D) 2:

For further information please look into the involved IDN:

S-0-0135, S-0-0099, P-0-0350