S-0-0410 Probe 1 negative latched (Counter)

This parameter indicates whether a positive edge occurred at Probe 1.

Attributes

Name

Value

Datatype

binary

Data length in bit

16

Decimal point

0

Min value

-

Default

0

Max value

-

Unit

-

Changeable in EtherCAT state

No

Cyclic transfer

AT

Device parameter

No

Related to interface revision

No

This parameter can be assigned an IDN, so that a real-time status bit can be assigned to this parameter. The drive only sets bit 0 of this parameter if the command S-0-0170 is enabled, S-0-0405 is set to 1, and the negative edge of S-0-0401 is enabled.

If a negative edge occurs at the input, the drive saves the parameterised source value in S-0-0131. The drive resets this bit, if the controller cancels the command S-0-0170, or if S-0-0405 is reset to 0.

Bit pattern:

Bit

Meaning

0

Probe 1
Probe 1

0 = not enabled
1 = enabled

1 – 15

Reserved

S-0-0410 Probe 1 negative latched (Counter) 1:

For further information please look into the involved IDN:

S-0-0131, S-0-0170, S-0-0179, S-0-0305, S-0-0405

S-0-0410 Probe 1 negative latched (Counter) 2:

Additional functional description

AX5000 / Probe unit