FB_BA_ActuatorCmdTLog

The FB_BA_ActuatorCmdTLog template is used to control binary aggregates. It essentially consists of a BO object for controlling an aggregate and the function block PlantLock, which collects all safety-relevant faults.
The switching command of the BO object is recorded by a trend object.
Each template is available in 2 different configurations regarding the connection to the I/O process level, see I/O mapping. This documentation refers to the RAW variant.
![]() | The initialization of the template takes place within the method FB_Init. |
Block diagram

Syntax
FUNCTION_BLOCK FB_BA_ActuatorCmd EXTENDS FB_BA_View
VAR_OUTPUT
stCmd : ST_BA_Binary;
END_VAR
VAR_OUTPUT
bCmd : BOOL;
bDst : BOOL;
eActivePrio : E_BA_Priority;
END_VAR
VAR_INPUT CONSTANT
Cmd : FB_BA_BO_Raw;
TLogCmd : FB_BA_Trend;
PlantLock : FB_BA_PlantLock;
END_VAR
VAR
bPrioSfty : BOOL;
bPrioCrit : BOOL;
TrigTLogCmd : FB_BA_RFTrig;
END_VAR
Outputs
Name | Type | Description |
|---|---|---|
stCmd | The enables and switching values of the priorities are transmitted to the template via the stCmd command structure. The command with the highest priority is output to the binary output object Cmd. | |
bCmd | BOOL | Current value of the binary output object. |
bDst | BOOL | The variable is an evaluation of the lock priorities "Safety" and "Critical" of the project structure and indicates a triggered event. |
eActivePrio | Display of the active priority. |
Inputs CONSTANT
Name | Type | Description |
|---|---|---|
Cmd | The binary output object is used to output a switching command and transmit it to the I/O level. | |
TLogCmd | Trend logging of the control value of the Cmd object. | |
PlantLock | PlantLock collects all event-capable objects on this and lower levels of the project structure. The events of the objects often signal a relevant malfunction, which requires targeted switching operations to be performed on aggregates or plants. |
Variables
Name | Type | Description |
|---|---|---|
bPrioSfty | BOOL | The variable is an evaluation of the "Safety" lock priority of the project structure. |
bPrioCrit | BOOL | The variable is an evaluation of the "Critical" lock priority of the project structure. |
TrigTLogCmd | The function block generates a pulse from the output signal of the binary output object Cmd when the value changes. |