FB_BA_SunBldScn

FB_BA_SunBldScn 1:

The function block FB_BA_SunBldScn represents an extension of the manual operation FB_BA_SunBldSw by a scene memory and a call function. The blind actuator FB_BA_SunBldActr or the roller blind actuator FB_BA_RolBldActr can thus be controlled in manual operation mode and can also drive directly to previously saved positions (scenes). Up to 21 scenes can be saved.

Operation

In manual mode, the function block controls the blind function block FB_BA_SunBldActr or the roller blind function block FB_BA_RolBldActr via the command inputs bUp and bDwn; bUp has priority. The commands are passed on to the respective commands bManUp and bManDwn of the positioning telegram. If a command input is activated for longer than the entered time nSwiOvrTi [ms], the corresponding control command latches. Activating a command input again releases this latch.

A rising edge on bSavScn saves the current position and lamella angle in the scene selected in nSlcdScn. This procedure is possible at any time, even during active positioning.

A rising edge at bClScn calls the scene that is present at input nSlcdScn. This scene call can be interrupted by manual commands to bUp and bDwn.

Manual control and scene positioning are each carried out with the priority that is preselected under ePrio.

If the function is no longer active due to the resetting of bEn, then the active flag in the positioning telegram stSunBld is reset and the positions for height and angle are set to "0". The priority function block (e.g. FB_BA_SunBldPrioSwi4) enables a function with lower priority to take over the control by resetting.

Linking to the blind function block

Like the "normal" manual mode function block FB_BA_SunBldSwi, the scene selection function block can be connected either via an upstream priority control FB_BA_SunBldPrioSwi4 or FB_BA_SunBldPrioSwi8, or directly via the blind function block. The connection is established via the positioning telegram ST_BA_Sunbld. Furthermore the scene function block requires the current positions from the blind function block for the reference blind:

Use of a priority controller:

FB_BA_SunBldScn 2:

Direct connection:

FB_BA_SunBldScn 3:

FB_BA_SunBldScn 4: Inputs

VAR_INPUT
  bEn            : BOOL;
  bUp            : BOOL;
  bDwn           : BOOL;
  nSwiOvrTi      : UDINT;
  nSlcdScn       : UDINT;
  bClScn         : BOOL;
  bSavScn        : BOOL;
  fSpPos         : REAL;
  fSpAngl        : REAL;
END_VAR

Name

Type

Description

bEn

BOOL

The function block has no function if this input is FALSE. 0 is output for the position and the angle in the positioning telegram ST_BA_Sunbld - bManMod and bActv are set to FALSE. For a connection with priority controller this means that another functionality takes over control of the blind. Conversely, a direct connection allows the blind to drive directly to the 0 position, i.e. fully up, since the actuator function block does not evaluate the bit bActv itself.

bUp

BOOL

Command input for blind up.

bDwn

BOOL

Command input for blind down.

nSwiOvrTi

UDINT

Time [ms] until the corresponding manual command in the positioning telegram ST_BA_Sunbld switches to latching mode, if the command input is activated permanently. Internally limited to a minimum value of 0.

nSlcdScn

UDINT

Selected scene which should either be saved (bSavScn) or called (bClScn). Internally limited to a minimum value from 0 to BA_Param.nSunPrt_MaxSunBldScn

bClScn

BOOL

Call selected scene.

bSavScn

BOOL

Save selected scene.

fSpPos

REAL

Set position [%] that is to be saved in the selected scene. This must be linked to the actual position of the actuator function block FB_BA_SunBldActr or FB_BA_RolBldActr of the reference blind/roller blind, in order to be able to save a position that was previously approached manually. Internally limited to values between 0 and 100.

fSpAngl

REAL

ditto lamella angle [°].

FB_BA_SunBldScn 5: Inputs CONSTANT PERSISTENT

VAR_INPUT CONSTANT PERSISTENT
  ePrio    : E_BA_SunBldPrio := E_BA_SunBldPrio.eScene1;
END_VAR

Name

Type

Description

ePrio

E_BA_SunBldPrio

Priority of the active telegram.

FB_BA_SunBldScn 6: / FB_BA_SunBldScn 7: Inputs/Outputs

VAR_IN_OUT
  aSunBldScn : ARRAY[0..BA_Param.nSunPrt_MaxSunBldScn] OF ST_BA_SunBldScn;
END_VAR

Name

Type

Description

aSunBldScn

ARRAY OF ST_BA_SunBldScn

Table with the scene entries.

FB_BA_SunBldScn 8: Outputs

VAR_OUTPUT
  stSunBld      : ST_BA_SunBld;
  bActv         : BOOL;
  fActlScnPos   : REAL;
  fActlScnAngl  : REAL;
END_VAR

Name

Type

Description

stSunBld

ST_BA_SunBld

Output telegram, for the position and angle of the lamella.

bActv

BOOL

Corresponds to the boolean value bActv in the blind telegram ST_BA_SunBld and is solely used to indicate whether the function block sends an active telegram.

fActlScnPos

REAL

Indicates the saved relative blind height position [%] for the currently selected scene.

fActlScnAngl

REAL

ditto lamella angle [°].

Requirements

Development environment

Required PLC library

TwinCAT from v3.1.4024.22

Tc3_BA2 from v5.2.5.0