C_CI_NT_2
Read operational integrated totals of selected time and of selected range of addresses.
|
- obj | |||||||||||||
|
|--- |
+ head |
Reserved | |||||||||||
|
|--- |
- ident | ||||||||||||
|
| |
|--- |
eType |
= 0x7A (122) |
= C_CI_NT_2 | |||||||||
|
| |
|--- |
bSQ |
= FALSE |
Sequence of information objects | |||||||||
|
| |
|--- |
nObj |
= 1 |
Number of objects | |||||||||
|
| |
|--- |
bT |
Test | ||||||||||
|
| |
|--- |
bPN |
Positive/negative confirmation/activation | ||||||||||
|
| |
|--- |
eCOT | |||||||||||
|
| |
|--- |
asduAddr |
Common address of asdu | ||||||||||
|
| |
|--- |
eClass | |||||||||||
|
|--- |
- info | ||||||||||||
|
|--- |
rcdAddr |
Record address of accounting period | |||||||||||
|
|--- |
stream | ||||||||||||
|
|--- |
length |
= 12 | |||||||||||
|
|--- |
data |
7 |
6 |
5 |
4 |
3 |
2 |
1 |
0 | ||||
|
|--- |
data[0] = |
Integrated total address (from) | |||||||||||
|
|--- |
data[1] = |
Integrated total address (to) | |||||||||||
|
|--- |
data[2..6] = |
Five octets binary time tag (from) | |||||||||||
|
|--- |
data[7..11] = |
Five octets binary time tag (to) | |||||||||||
|
|--- |
data[12..IEC870_MAX_ASDU_DATA_BYTE] = |
Reserved | |||||||||||