C_CI_NG_2
Read periodically reset accounting integrated totals of a specific past integration period.
|
- obj | |||||||||||||
|
|--- |
+ head |
Reserved | |||||||||||
|
|--- |
- ident | ||||||||||||
|
| |
|--- |
eType |
= 0x6E (110) |
= C_CI_NG_2 | |||||||||
|
| |
|--- |
bSQ |
= FALSE |
Sequence of information objects | |||||||||
|
| |
|--- |
nObj |
= 1 |
Number of objects | |||||||||
|
| |
|--- |
bT |
Test | ||||||||||
|
| |
|--- |
bPN |
Positive/negative confirmation/activation | ||||||||||
|
| |
|--- |
eCOT | |||||||||||
|
| |
|--- |
asduAddr |
Common address of asdu | ||||||||||
|
| |
|--- |
eClass | |||||||||||
|
|--- |
- info | ||||||||||||
|
|--- |
rcdAddr |
Record address of accounting period | |||||||||||
|
|--- |
stream | ||||||||||||
|
|--- |
length |
= 5 | |||||||||||
|
|--- |
data |
7 |
6 |
5 |
4 |
3 |
2 |
1 |
0 | ||||
|
|--- |
data[0..4] = |
Five octets binary time tag | |||||||||||
|
|--- |
data[5..IEC870_MAX_ASDU_DATA_BYTE] = |
Reserved | |||||||||||