Programming

Syntax for Select by specifying the position of the workpiece surface:

<axis_name> [DIST_CTRL [WAIT] ON | DRYRUN [ SET_POS=.. ] ]

Syntax for Select by specifying a constant distance to the workpiece surface:

<axis_name> [DIST_CTRL [WAIT] ON | DRYRUN CONST_DIST [ SET_DIST=.. ] ]

Syntax for Deselect or Freeze offset

<axis_name> [DIST_CTRL [WAIT] [ OFF [ NO_MOVE ] ] | FREEZE ]

Syntax for Check sensor position or home sensor:

<axis_name> [DIST_CTRL CHECK_POS | REF ]

Optionally, the following parameters can also be programmed in combination with select/deselect:

Syntax for Additional sensor parameters:

<axis_name> [DIST_CTRL [SENSOR_SOURCE=<ident> SENSOR_VAR=..] [ VAL1=.. - VAL5=.. ] { \ } ]

Syntax for Additional control parameters:

<axis_name> [DIST_CTRL [ KP=.. ] [ I_TN=.. ] [ D_TV=.. ] { \ } ]

Syntax for Additional parameters for smoothing sensor signal:

<axis_name> [DIST_CTRL [ FILTER_TYPE=.. ] [ N_CYCLES=.. ] [ FG_F0=.. ] [ ORDER=.. ]
                        [ SMOOTH_FACT=.. ] [ KALMAN_SIGMA=.. ] { \ } ]

Syntax for Additional parameterisation for a wait condition with WAIT

<axis_name> [DIST_CTRL [WINDOW=..] [CYCLES_IN_WINDOW=..]{ \ } ]

<axis_name>

Name of the axis supporting the tool.

DIST_CTRL

Identifier for the "Sensed spindles” function. Must always be programmed as the first keyword.

ON

Activate distance control specifying the position of the workpiece surface. A set position at activation must be set with SET_POS.

SET_POS=..

Specify the position of the workpiece surface in [mm, inch] (absolute position). In the event of reset or program end, the parameter is reset, i.e. a new parameter must be specified before distance control is reactivated.

CONST_DIST

Activate distance control in combination with ON by specifying a constant distance to the workpiece surface. A distance must be set with SET_DIST at activation. [as of V2.11.2804.03]

SET_DIST=..

Specify the constant distance to the workpiece surface in [mm, inch]. In the event of reset or program end, the distance is reset, i.e. a new distance must be specified before distance control is reactivated.

DRYRUN

In combination with ON, the axis is not tracked in DRYRUN mode when there are changes in the workpiece surface. This allows data to be evaluated without feedback from the controller (e.g. filter effect). [as of V3.1.3079.23]

When distance control is activated specifying the position of the workpiece surface, a set position must be set with SET_POS.

When distance control is activated specifying a constant distance to the workpiece surface, a set distance must be set with SET_DIST.

OFF

Deactivate distance control.

NO_MOVE

By default, the resulting correction offset is executed when distance control is switched off. This motion can be suppressed by specifying NO_MOVE in combination with OFF. The channel is initialised with the changed axis position. The position offset is only executed at the next axis motion programmed in the NC program.

FREEZE

Freeze the compensated control distance across the workpiece. The axis position or the output compensation value is maintained. Axis tracking is interrupted.

CHECK_POS

Check whether position is within the tolerance window.

REF

Reference measuring system (sensor) (only if there is no absolute measuring system).

SENSOR_SOURCE=<ident>

Specify the source of the sensor signal [as of V3.1.3080.12 or V3.1.3107.45]. The following sources can be set for channel-specific distance control. Valid identifiers:

DEFAULT: IF “DEFAULT” is selected as the sensor source, the CNC automatically sets to the “SECOND_ENCODER” sensor source internally.

VARIABLE: The sensor signal is transferred to the CNC by a V.E. variable. In addition, the name of the V.E. variable must also be specified by the parameter “SENSOR_VAR”.

SECOND_ENCODER: Make sure that the first configured encoder (P-AXIS-00823) is used for axis position control and the second encoder (P-AXIS-00824) for distance control.

SENSOR_VAR=..

Name of the V.E. variable used to transmit the sensor signal to the CNC.
[as of V3.1.3080.12 or V3.1.3107.45]
Unit of variable transferred:
[0.1 µm]

VAL1=..-VAL5=..

Five freely assignable values in real format.

KP=..

Weighting the distance control output values. Parameterisation can be executed analogous to P-AXIS-00759. The value range is limited to 0.0 < KP <= 2.0. For KP values less than 1.0, the distance control dynamics are reduced; for KP values greater than 1.0, the dynamics are increased.

A KP factor less than 1 reduces a possible distance control oscillation and steadies control in the event of minor distance errors.
[as of V2.11.2809.06 or V3.1.3079.06]

I_TN=..

Integral action time of the PID controller in [s]. The integral action time defines the time after which the P and I components of the manipulated variable are equal. Parameterisation can be executed analogous to P-AXIS-00764. The value range is limited to 0.0 <= I_TN <= 50.0. A large integral action time produces greater control stability. The shorter the integration action time, the greater the I component and the faster the control. A short integral action time excites oscillations more strongly.
[as of V2.11.2809.06 or V3.1.3079.06]

D_TV=..

Derivative action time of the PID controller in [s]. The derivative action time defines the time after which the P and D components of the manipulated variable are equal. Parameterisation can be executed analogous to P-AXIS-00765. The value range is limited to 0.0 <= D_TV <= 2.0. The larger the derivative action time, the stronger the D component.
[as of V2.11.2809.06 or V3.1.3079.06]

FILTER_TYPE=..

Filter type to filter encoder values as specified in P-AXIS-00782.
[as of V3.1.3079.23]

N_CYCLES=..

Number of measured values used for filtering as specified in P-AXIS-00413.
[as of V3.1.3079.23]

FG_F0=..

Cut-off frequency of the low-pass filter in [Hz] as specified in P-AXIS-00508.
[as of V3.1.3079.23]

ORDER=..

Order of the low-pass filter according to P-AXIS-00507.
[as of V3.1.3079.23]

SMOOTH_FACT=..

Smoothing factor of the exponential averaging filter according to P-AXIS-00784. Specifies the weighting of the current measured value.

KALMAN_SIGMA=..

Uncertainty of logged measured values as specified in P-AXIS-00783.
[as of V3.1.3079.23]

BOTH_ENCODER=..

Mode for reducing oscillation tendency as specified in P-AXIS-00500.
[as of V3.1.3125]

WAIT

In the WAIT option, a command waits before execution until the waiting condition of distance control was fulfilled before the next NC command is executed:

WAIT OFF: Wait until the existing distance control offset was completely executed.

WAIT ON/SET_DIST/.. .: Wait until the control deviation of distance control has been in a defined window (WINDOW=...) for a defined period of time (CYCLES_IN_WINDOW=...).

An active wait condition is indicated in
gpCh[channel_idx]^.bahn_state.stop_conditions_rt.

WINDOW=..

Defines the tolerance window of the control deviation in [mm] required to fulfil the waiting condition triggered by the “WAIT” command.

CYCLES_IN_WINDOW=..

Defines the number of cycles that the control deviation must be in the tolerance window in order to fulfil the waiting condition triggered by the “WAIT” command.

\

Separator ("backslash") for clear programming of the command over multiple lines.

If distance control is still active at program end, it is not automatically deselected.

When a reset or axis error occurs, active distance control is always deselected automatically.

Parameters of the PID controller are not reset at program end.

Programming Example

Programming examples for distance control

%DIST_1
;Set expected position of the workpiece surface
N10 Z[DIST_CTRL SET_POS=30]
N20 Z[DIST_CTRL ON]          ;Select
; …
Nxx Z[DIST_CTRL OFF]         ;Deselect
N999 M30
%DIST_2
;Select + set expected position of the workpiece surface
N10 Z[DIST_CTRL ON SET_POS=30]
; …
Nxx Z[DIST_CTRL FREEZE]      ;Hold position
; …
Nxx Z[DIST_CTRL OFF]         ;Deselect
N999 M30
%DIST_3
;Select + set expected position of the workpiece surface
N10 Z[DIST_CTRL ON SET_POS=50]
;Deactivate distance control; Z axis does not move
Nxx Z[DIST_CTRL OFF NO_MOVE]
;The generated compensation offset is included for Move to target point
;100
Nxx G0 Z100
N999 M30
%DIST_4
;Set distance parameters
N10 Z[DIST_CTRL SET_POS=30]
;Select specifying the position of the workpiece surface (SET_POS)
N20 Z[DIST_CTRL ON]
; …
Nxx Z[DIST_CTRL OFF]         ;Deselect
; …
;Select specifying the workpiece surface (SET_DIST)
Nxx Z[DIST_CTRL SET_DIST=10]
Nxx Z[DIST_CTRL ON CONST_DIST]
; …
Nxx Z[DIST_CTRL OFF]         ;Deselect
N999 M30
%DIST_5
;Select filter type
N10Z[DIST_CTRL FILTER_TYPE=KALMAN_MA]
;Parametrise filter
N20 Z[DIST_CTRL N_CYCLES=30 KALMAN_SIGMA=1000]
;Check the filter effect on the sensor signal
N30 Z[DIST_CTRL DRYRUN]
;…
;Parameterise the PID controller
Nxx Z[DIST_CTRL KP=0.3 I_TN=0 D_TV=0.01]
;Activate distance control
Nxx Z[DIST_CTRL ON CONST_DIST SET_DIST=1]
; …
;Change filter
Nxx Z[DIST_CTRL FILTER_TYPE=KALMAN_EXPO SMOOTH_FACT=0.3]
; …
Nxx Z[DIST_CTRL OFF];        Deselect
N999 M30