Runtime messages

Value (hex)

Value (dec)

Text ID

Description

 16#0000

 0

NoError

No error.

 16#0001

 1

NoResponseFromTheDALITerminal

No response from the DALI terminal.

 16#0002

 2

NoResponseFromTheDALIDevice

No response from the DALI device.

 16#0003

 3

CommandBufferOverflow

Overflow of the command buffer.

 16#0004

 4

NoAnswerFromTheCommunicationBlock

No answer from the communication block.

 16#0005

 5

DALICollisionDetectedOnTheBackwardChannel

DALI collision detected on the backward channel: during the transfer of a DALI frame, a collision with the send data of another DALI device was detected.

 16#0006

 6

DALICollisionDetectedOnTheForwardChannel

DALI collision detected on the forward channel: during the transfer of a DALI frame, a collision with the send data of another DALI control device was detected. The error also occurs if the 24 V supply is missing at the power contacts of the KL6811.

 16#0007

 7

OverloadOfTheInternalDALIPowerSupplyUnitOfTheBusTerminal_BusUnderVoltage

When using the internal DALI power supply unit of the bus terminal: overload of the internal DALI power supply unit of the bus terminal (bus undervoltage).

 16#0008

 8

PowerSupplyUnitFaultDetected

When using the internal DALI power supply unit: Power supply unit fault detected.

 16#0009

 9

TheProcessImageWasDisabledByDI1OrDI2

The process image was disabled by the DI1 or DI2 inputs of the terminal.

 16#000A

 10

ShortCircuitDetectedOnTheDALIBus

The 24 V DC supply voltage at connections 1 and 5 of the KL6821/EL6821 is missing, or a short circuit has been detected on the DALI bus.

 16#000B

 11

CollisionErrorOnTheDALIBus

Due to collisions on the DALI bus, the DALI command could not be sent.

 16#000C

 12

ItemInReceiveBufferIsInvalid

The item in the receive buffer of the KL6821/EL6821 is invalid.

 16#000D

 13

TheInterfaceToTheCommunicationBufferIsNotInitialized

The interface pointer on the communication block is not initialized.

 16#000E

 14

TheCommandBuffersHaveBeenBlockedForLongerThanPermitted

The command buffer was blocked for longer than is permitted.

 16#000F

 15

TheTerminalHasReturnedAnErrorDuringInternalAddressing

The terminal has returned an error during addressing.

 16#0010

 16

DuringInternalAddressingTheTerminalHasDetectedAShortCircuitOnTheBus

During addressing the terminal has detected a short circuit on the bus.

 16#0011

 17

DuringInternalAddressingTheTerminalHasDetectedThatThereIsNoFurtherShortAddressAvailable

During addressing the terminal has detected that there is no free short address available.

 16#0012

 18

DuringInternalAddressingTheTerminalHasDetectedThatSeveralDevicesHaveTheSameLongAddress

During addressing the terminal has detected that several devices have the same long address.

 16#0013

 19

InternalAddressingHasFailed3Times

The addressing failed three times.

 16#0014

 20

TimeoutDuringInternalAddressing

Timeout for addressing. The terminal has not sent a response following the start of addressing.

 16#0015

 21

NoResponseFromTheDALIDeviceInstance

No response from the instance of the DALI device.

 16#0016

 22

TheKL6811DoesNotSupportThisDALICommand

The KL6811 supports only 16-bit commands (IEC 62386-102 and IEC 62386-2xx).

 16#0017

 23

ErrorDuringTheConfigurationOfTheTerminal

An error occurred during configuration of the terminal.

 16#0018

 24

NoResponseFromTheDALIDevice2

No response from the DALI device.

 16#0019

 25

NoFreeShortAddressAvailable

No more free short addresses are available.

 16#001A

 26

ErrorDuringAddressing

An error occurred during addressing.

 16#001B

 27

InvalidResponseFromTheDALIDevice

The response from the DALI device is invalid.

 16#001C

 28

InvalidResponseFromTheDALIDeviceInstance

Invalid response from the instance of the DALI device.

 16#001D

 29

ThisDALICommandIsNotSupportedByTheSimulation

This DALI command is not supported by the simulation.

 16#001E

 30

CommandBuffersBlockedByMutex

Access to the command buffer is not possible due to blocking by the mutex.

 16#001F

 31

ItemInReceiveBufferErrorBitTiming

The item in the receive buffer of the KL6821/EL6821 has a bit timing error.

 16#0020

 32

ItemInReceiveBufferIncorrectNumberOfBits

The item in the receive buffer of the KL6821/EL6821 has an incorrect number of bits.

 16#0021

 33

ItemInReceiveBufferEncodingError

An error has occurred in the item in the receive buffer of the KL6821/EL6821 during decoding.

 16#0022

 34

DuringAddressingTheTerminalHasDetectedMissingResponse

During addressing, the terminal has detected a missing response from a device.

 16#00AC

172

ParameterCommandIsNotValid

Parameter nCommand is no valid command.

 16#00AD

173

ParameterLuxRangeBrightnessLiesOutsideOfTheValidRange

Parameter nLuxRangeBrightness lies outside of the valid range (0…1).

 16#00AE

174

ParameterAlarmEventPriorityLiesOutsideOfTheValidRange

Parameter eAlarmEventPriority lies outside of the valid range (E_DALIEventPriority.Low...E_DALIEventPriority.MiddleHigh).

 16#00AF

175

ParameterAlarmXHysteresisPart306LiesOutsideOfTheValidRange

Parameter nAlarmNHysteresis lies outside of the valid range (0...4194303).

 16#00B0

176

ParameterAlarmXLevelPart306LiesOutsideOfTheValidRange

Parameter nAlarmNLevel lies outside of the valid range (0...4194303).

 16#00B1

177

ParameterAlarmReportTimerPart306LiesOutsideOfTheValidRange

Parameter nAlarmReportTimer lies outside of the valid range (0...1275 s).

 16#00B2

178

ParameterReportTimerPart306LiesOutsideOfTheValidRange

Parameter nReportTimer lies outside of the valid range (0...1275 s).

 16#00B3

179

ParameterAlarmLevelLiesOutsideOfTheValidRange

Parameter nAlarmLevel lies outside of the valid range (0...4194303).

 16#00B4

180

ParameterAlarmHysteresisLiesOutsideOfTheValidRange

Parameter nAlarmHysteresis lies outside of the valid range (0...4194303).

 16#00B5

181

WritingToTheOffsetOfTheMemoryBankWasNotSuccessful

Writing to the offset of a memory bank of a DALI device was not successful.

 16#00B6

182

ParameterColourTypeLiesOutsideOfTheValidRange

Parameter eColourType lies outside of the valid range (E_DALIColourType.XyCoordinate...E_DALIColourType.RGBWAFControl).

 16#00B7

 183

ParameterEmergencyLevelLiesOutsideOfTheValidRange

Parameter nEmergencyLevel lies outside of the valid range (emergencyMinLevel...emergencyMaxLevel, 255).

 16#00B8

 184

ParameterDurationTestIntervalLiesOutsideOfTheValidRange

Parameter nDurationTestInterval lies outside of the valid range (0...97).

 16#00B9

 185

ParameterSensitivityOccupancyPartial3Part303LiesOutsideOfTheValidRange

Parameter nSensitivityN lies outside of the valid range (1…100).

 16#00BA

 186

ParameterSensitivityOccupancyPartial2Part303LiesOutsideOfTheValidRange

Parameter nSensitivityN lies outside of the valid range (0…4).

 16#00BB

 187

ParameterExtendedFadeTimeBaseLiesOutsideOfTheValidRange

Parameter eExtendedFadeTimeBase lies outside of the valid range (E_DALIExtendedFadeTimeBase.Base01...E_DALIExtendedFadeTimeBase.Base16).

 16#00BC

 188

ParameterExtendedFadeTimeMultiplierLiesOutsideOfTheValidRange

Parameter eExtendedFadeTimeMultiplier is out of valid range (E_DALIExtendedFadeTimeMultiplier.Disabled...E_DALIExtendedFadeTimeMultiplier.Multiplier1min).

 16#00BD

 189

ParameterDeadtimeLiesOutsideOfTheValidRange

Parameter tDeadtime lies outside of the valid range (2...3600 s).

 16#00BE

 190

ParameterHysteresisLiesOutsideOfTheValidRange2

Parameter nHysteresis lies outside of the valid range (0...25 %).

 16#00BF

 191

ParameterDeadtimeTimerLiesOutsideOfTheValidRange

Parameter nDeadtimeTimer lies outside of the valid range (0...12750 ms).

 16#00C0

 192

ParameterHoldTimerLiesOutsideOfTheValidRange

Parameter nHoldTimer lies outside of the valid range (1...2538 ms).

 16#00C1

 193

ParameterStuckTimerLiesOutsideOfTheValidRange

Parameter nStuckTimer lies outside of the valid range (5...255 s).

 16#00C2

 194

ParameterShortLiesOutsideOfTheValidRange

Parameter nShort lies outside of the valid range (tShortMin...255).

 16#00C3

 195

ParameterShortTimerPart301LiesOutsideOfTheValidRange

Parameter nShortTimerN lies outside of the valid range (tShortMin...5100 ms).

 16#00C4

 196

ParameterShortTimerLiesOutsideOfTheValidRange

Parameter nShortTimer lies outside of the valid range (tShortMin...5100 ms).

 16#00C5

 197

ParameterDoubleTimerPart301LiesOutsideOfTheValidRange

Parameter nDoubleTimerN lies outside of the valid range (0, tDoubleMin...2000 ms).

 16#00C6

 198

ParameterDoubleTimerLiesOutsideOfTheValidRange

Parameter nDoubleTimer lies outside of the valid range (0, tDoubleMin...2000 ms).

 16#00C7

 199

ParameterRepeatTimerLiesOutsideOfTheValidRange

Parameter nRepeatTimer lies outside of the valid range (100...2000 ms).

 16#00C8

 200

ParameterEventSchemeLiesOutsideOfTheValidRange

Parameter eEventScheme lies outside of the valid range (see E_DALIEventScheme).

 16#00C9

 201

ParameterAddressIsAGroupAddressAndLiesOutsideOfTheValidRange2

Parameter nAddress is a group address and lies outside of the valid range (0...31).

 16#00CA

 202

ParameterEventPriorityDeviceLiesOutsideOfTheValidRange

Parameter eEventPriorityN lies outside of the valid range (E_DALIEventPriority.Low...E_DALIEventPriority.MiddleHigh).

 16#00CB

 203

ParameterALSCorrectionFactorPart304LiesOutsideOfTheValidRange

Parameter nALSxCorrectionFactorN lies outside of the valid range (0.1...5.0).

 16#00CC

 204

ParameterRoomCorrectionFactorPart304LiesOutsideOfTheValidRange

Parameter nRoomCorrectionFactorN lies outside of the valid range (5...200).

 16#00CD

 205

ParameterSwitchOnLevelLiesOutsideOfTheValidRange

Parameter nSwitchOnLevel lies outside of the valid range (minLevel...maxLevel).

 16#00CE

 206

ParameterHysteresisPart304LiesOutsideOfTheValidRange

Parameter nHysteresisN lies outside of the valid range (0...25 %).

 16#00CF

 207

ParameterDeadtimeTimerPart304LiesOutsideOfTheValidRange

Parameter nDeadtimeTimerN lies outside of the valid range (0...12750 ms).

 16#00D0

 208

ParameterSensitivityOccupancyPartialPart303LiesOutsideOfTheValidRange

Parameter nSensitivityN lies outside of the valid range (1…5).

 16#00D1

 209

ParameterSensitivityOccupancyPercentPart303LiesOutsideOfTheValidRange

Parameter nSensitivityN lies outside of the valid range (0...100 %).

 16#00D2

 210

ParameterDetectionRangeOccupancyPart303LiesOutsideOfTheValidRange

Parameter nDetectionRangeN lies outside of the valid range (0...100 %).

 16#00D3

 211

ParameterHoldTimerPart303LiesOutsideOfTheValidRange

Parameter nHoldTimerN lies outside of the valid range (1...2538 ms).

 16#00D4

 212

ParameterDeadtimeTimerPart303LiesOutsideOfTheValidRange

Parameter nDeadtimeTimerN lies outside of the valid range (0...12750 ms).

 16#00D5

 213

ParameterHysteresisLiesOutsideOfTheValidRange3

Parameter nHysteresis lies outside of the valid range (1...65535).

 16#00D6

 214

ParameterDeadtimeTimerPart302LiesOutsideOfTheValidRange

Parameter nDeadtimeTimerN lies outside of the valid range (0...12750 ms).

 16#00D7

 215

ParameterStuckTimerPart301LiesOutsideOfTheValidRange

Parameter nStuckTimerN lies outside of the valid range (5...255 ms).

 16#00D8

 216

ParameterRepeatTimerPart301LiesOutsideOfTheValidRange

Parameter nRepeatTimerN lies outside of the valid range (100...2000 ms).

 16#00D9

 217

ParameterUpSwitchOffThresholdLiesOutsideOfTheValidRange

Parameter nUpSwitchOffThreshold lies outside of the valid range (1...255).

 16#00DA

 218

ParameterUpSwitchOnThresholdLiesOutsideOfTheValidRange

Parameter nUpSwitchOnThreshold lies outside of the valid range (1...255).

 16#00DB

 219

ParameterLevelMemoryModeLiesOutsideOfTheValidRange

Parameter nLevelMemoryMode lies outside of the valid range (1…254).

 16#00DC

 220

ParameterMinLevelIsGreaterThanMaxLevel

Parameter nMinLevel is greater than nMaxLevel.

 16#00DD

 221

ParameterReferenceDeviceAddressLiesOutsideOfTheValidRange

Parameter nReferenceDeviceAddress lies outside of the valid range (0...63).

 16#00DE

 222

ErrorDuringReadingOffsetFromMemoryBank

An error occurred while reading an offset from the memory bank.

 16#00DF

 223

ParameterSubRangeStartLiesOutsideOfTheValidRange

Parameter nSubRangeStart lies outside of the valid range.

 16#00E0

 224

ErrorReadingMemoryBankDTR0IsWrong

An error occurred while reading out a memory bank. The value of DTR0 is not as expected.

 16#00E1

 225

ParameterSubRangeEndLiesOutsideOfTheValidRange

Parameter nSubRangeEnd lies outside of the valid range.

 16#00E2

 226

ReadCommandReturnedTMASK

The DALI device returns TMASK. The value is not currently available.

 16#00E3

 227

ReadCommandReturnedMASK

The DALI device returns MASK. The value is not available.

 16#00E4

 228

ParameterInternalControlGearReferenceTemperatureLiesOutsideOfTheValidRange

Parameter nInternalControlGearReferenceTemperature lies outside of the valid range (-60…193 °C).

 16#00E5

 229

ParameterLightSourceOnTimeResettableLiesOutsideOfTheValidRange

Parameter nLightSourceOnTimeResettable lies outside of the valid range (0…4294967293 s).

 16#00E6

 230

ParameterLightSourceStartCounterResettableLiesOutsideOfTheValidRange

Parameter nLightSourceStartCounterResettable lies outside of the valid range (0…16777213).

 16#00E7

 231

ParameterRatedMedianUsefulLifeOfLuminaireLiesOutsideOfTheValidRange

Parameter nRatedMedianUsefulLifeOfLuminaire lies outside of the valid range (0…253).

 16#00E8

 232

ParameterRatedMedianUsefulLightSourceStartsLiesOutsideOfTheValidRange

Parameter nRatedMedianUsefulLightSourceStarts lies outside of the valid range (0…65533)

 16#00E9

 233

ParameterInstanceNumberLiesOutsideOfTheValidRange

Parameter nInstanceNumber lies outside of the valid range (0…31).

 16#00EA

 234

ParameterShortAddressLiesOutsideOfTheValidRange2

Parameter nShortAddress lies outside of the valid range (0…63).

 16#00EB

 235

ParameterSubRangeEndIsLessThanSubRangeStart

Parameter nSubRangeEnd is smaller than nSubRangeStart.

16#00EC

 236

ParameterFastFadeTimeLiesOutsideOfTheValidRange

Parameter eFastFadeTime is out of valid range (E_DALIFastFadeTime.Disabled...E_DALIFastFadeTime.T700ms).

16#00ED

 237

ParameterDimmingCurveLiesOutsideOfTheValidRange

Parameter eDimmingCurve lies outside of the valid range (see E_DALIDimmingCurve).

 16#00EE

 238

ParameterEventPriorityLiesOutsideOfTheValidRange

Parameter eEventPriority lies outside of the valid range (E_DALIEventPriority.Low...E_DALIEventPriority.MiddleHigh).

 16#00EF

 239

ParameterShortAddressLiesOutsideOfTheValidRange

Parameter nShortAddress lies outside of the valid range (0…63, 255).

 16#00F0

 240

ParameterAddressInfoInstanceGroupLiesOutsideOfTheValidRange

Parameter nAddressInfo1/nAddressInfo2 defines an instance group and lies outside of the valid range (0…31).

 16#00F1

 241

ParameterAddressInfoDeviceGroupLiesOutsideOfTheValidRange

Parameter nAddressInfo1/nAddressInfo2 defines a device group and lies outside of the valid range (0…31).

 16#00F2

 242

ParameterAddressInfoShortAddressLiesOutsideOfTheValidRange

Parameter nAddressInfo1/nAddressInfo2 defines a short address and lies outside of the valid range (0…63).

 16#00F3

 243

ParameterAddressInfoInstanceNumberLiesOutsideOfTheValidRange

Parameter nAddressInfo1/nAddressInfo2 defines an instance number and lies outside of the valid range (0…31).

 16#00F4

 244

ParameterAddressInfoInstanceTypeLiesOutsideOfTheValidRange

Parameter nAddressInfo1/nAddressInfo2 defines an instance type and lies outside of the valid range (0…31).

 16#00F5

 245

ParameterHysteresisLiesOutsideOfTheValidRange

Parameter nHysteresis lies outside of the valid range (0...25).

 16#00F6

 246

ParameterHoldLiesOutsideOfTheValidRange

Parameter nHold lies outside of the valid range (0…254).

 16#00F7

 247

ParameterDoubleLiesOutsideOfTheValidRange

Parameter nDouble lies outside of the valid range (0, tDoubleMin…100).

 16#00F8

 248

ParameterRepeatLiesOutsideOfTheValidRange

Parameter nRepeat lies outside of the valid range (5…100).

 16#00F9

 249

ParameterStuckLiesOutsideOfTheValidRange

Parameter nStuck lies outside of the valid range (5…255).

 16#00FA

 250

ParameterResolutionLiesOutsideOfTheValidRange

Parameter nResolution lies outside of the valid range (1…64).

 16#00FB

 251

ParameterEventFilterLiesOutsideOfTheValidRange

Parameter nEventFilter lies outside of the valid range (16#00_0000…16#FF_FFFF).

 16#00FC

 252

ParameterChangeAddressListIsEmpty

Parameter aChangeAddressList is empty.

 16#00FD

 253

ParameterChangeAddressListContainsAnInvalidShortAddressEntry

Parameter aChangeAddressList contains an invalid short address entry.

 16#00FE

 254

ParameterChangeAddressListContainsADoubleListEntryInTheShortAddresses

Parameter aChangeAddressList contains a double list entry in the short addresses.

 16#00FF

 255

ParameterChangeAddressListContainsAnEntryForANewShortAddressWhichIsAlreadyAssigned

Parameter aChangeAddressList contains an entry for a new short address which is already assigned to a device that is not affected by changes. The addresses have been changed back.

 16#0100

 256

ParameterMaxResponseTableEntriesLiesOutsideOfTheValidRange

Parameter cMaxResponseTableEntries lies outside of the valid range (2…250).

 16#0101

 257

ParameterMaxEventTableEntriesLiesOutsideOfTheValidRange

Parameter cMaxEventTableEntries lies outside of the valid range (2…250).

 16#0102

 258

ParameterTimeoutTransactionLiesOutsideOfTheValidRange

Parameter cTimeoutTransaction lies outside of the valid range (2…120 s).

 16#0103

 259

ParameterMaxCommandBufferEntriesLiesOutsideOfTheValidRange

Parameter cMaxCommandBufferEntries lies outside of the valid range (2…250).

 16#0104

 260

ParameterDataFrameTypeLiesOutsideTheValidRange

Parameter eDataFrameType lies outside of the valid range (see E_DALIDataFrameType).

 16#0105

 261

ParameterAddressTypeLiesOutsideOfTheValidRange

Parameter eAddressType lies outside of the valid range (see E_DALIAddressType).

 16#0106

 262

ParameterAddressIsAShortAddressAndLiesOutsideOfTheValidRange

Parameter nAddress is a short address and lies outside of the valid range (0...63).

 16#0107

 263

ParameterAddressIsAGroupAddressAndLiesOutsideOfTheValidRange

Parameter nAddress is a group address and lies outside of the valid range (0…15).

 16#0108

 264

ParameterCommandPriorityLiesOutsideOfTheValidRange

Parameter eCommandPriority lies outside the valid range (E_DALICommandPriority.Low...E_DALICommandPriority.High).

 16#0109

 265

ParameterInstanceAddressTypeLiesOutsideTheValidRange

Parameter eInstanceAddressType lies outside of the valid range (see E_DALIInstanceAddressType).

 16#010A

 266

ParameterInstanceAddressIsAInstanceNumberAndLiesOutsideOfTheValidRange

Parameter nInstanceAddress is an instance number and lies outside of the valid range (0…31).

 16#010B

 267

ParameterInstanceAddressIsAInstanceGroupAndLiesOutsideOfTheValidRange

Parameter nInstanceAddress is an instance group and lies outside of the valid range (0…31).

 16#010C

 268

ParameterInstanceAddressIsAInstanceTypeAndLiesOutsideOfTheValidRange

Parameter nInstanceAddress is an instance type and lies outside of the valid range (0…31).

 16#010D

 269

ParameterInstanceAddressIsAFeatureOnInstanceNumberLevelAndLiesOutsideOfTheValidRange

Parameter nInstanceAddress is a feature on instance number level and lies outside of the valid range (0…31).

 16#010E

 270

ParameterInstanceAddressIsAFeatureOnInstanceGroupLevelAndLiesOutsideOfTheValidRange

Parameter nInstanceAddress is a feature on instance group level and lies outside of the valid range (0…31).

 16#010F

 271

ParameterInstanceAddressIsAFeatureOnInstanceTypeLevelAndLiesOutsideOfTheValidRange

Parameter nInstanceAddress is a feature on instance type level and lies outside the valid range (0…31).

 16#0110

 272

ParameterGroupLiesOutsideOfTheValidRange

Parameter nGroup lies outside of the valid range (0…15).

 16#0111

 273

ParameterSceneLiesOutsideOfTheValidRange

Parameter nScene lies outside of the valid range (0…15).

 16#0112

 274

ParameterFadeTimeLiesOutsideOfTheValidRange

Parameter eFadeTime is out of valid range (E_DALIFadeTime.Disabled...E_DALIFadeTime.T90500ms).

 16#0113

 275

ParameterFadeRateLiesOutsideOfTheValidRange

Parameter eFadeRate is out of valid range (E_DALIFadeRate.N003StepsPerSec...E_DALIFadeRate.N358StepsPerSec).

 16#0114

 276

ParameterNewShortAddressLiesOutsideOfTheValidRange

Parameter nNewShortAddress lies outside of the valid range (0…63, 255).

 16#0115

 277

ParameterStartWithShortAddressLiesOutsideOfTheValidRange

Parameter nStartWithShortAddress lies outside of the valid range (0…63).