FB_BA_PIDCtrl

FB_BA_PIDCtrl 1:

The FB_BA_PIDCtrl function block is a universal PID controller. It can be used to control individual independent controlled systems and as part of a control sequence.

The controller is divided internally into two consecutive parts:

Operating mode “Upstream P component”:

(eOperationMode = E_BA_PIDMode.eP1ID)

FB_BA_PIDCtrl 2:

“Parallel structure” operating mode:

(eOperationMode = E_BA_PIDMode.ePID )

FB_BA_PIDCtrl 3:

Control direction

If bActn = FALSE, the control direction of the controller is reversed so that a control deviation of less than 0 causes a change in the control value in the positive direction. This is achieved by a negative calculation of the control deviation:

bActn

fE (control deviation)

Control direction

TRUE

fX-fW (actual value-setpoint)

direct (cooling)

FALSE

fW-fX (setpoint-actual value)

indirect (heating)

Passive behavior (bEn = FALSE)

The outputs are set as follows:

fY

0.0

fE

current control deviation, see control direction.

The internal values for the P, I, and D parts are set to 0, also the values for the I and D components of the preceding cycle. In case of a restart the control value is thus calculated in the first cycle without past values.

Active behavior (bEn = TRUE)

In the first cycle, the I and D components are calculated without historical values, as already mentioned.

Anti-Reset-Windup

If the I component is active, the controller ensures that it is retained, if the controller output rY is about to move beyond the limits fYMin or fYMax. A preliminary calculation of the controller output takes place inside the controller in every cycle.

Anti-reset windup at min limit

If the precalculation is smaller than the lower output limit fYMin, the I component is prevented from falling further and is limited to the value of the last PLC cycle. However, an increase in the I part remains possible.

Anti-reset windup at max limit

On the other hand, if the precalculation is greater than the upper limit fYMax, the I component is prevented from increasing further and is also limited to the value of the last PLC cycle. In this case, a drop in the I component remains possible.

Synchronizations

There are several cases where controller output must not only be limited, but also synchronized to a new value by manipulating the I component (if not active, then the D or the P component). These cases are prioritized because of the potential for simultaneity:

Prio

Description

Conditions

Comments

1

Synchronization via bSync/fSync

Controller enabled - bEn = TRUE

A positive signal on bSync sets the I component so that the control value assumes the value fSync. If bEn and bSync are set at the same time, this method can be used to set an initial value from which the controller starts. If the I component is not active, the D part is set accordingly. Note that only the rising edge of bSync is evaluated internally as this is a setting action. A TRUE signal must be applied again to the input bSync for renewed synchronization, for instance with a transfer value.

2

Range synchronization fYMin

Controller enabled – bEn = TRUE

fYMin <> fYMin_1 (last cycle)

fY_Test < fYMin

If the lower range limit has changed and the precalculated controller output is now smaller than fYMin , then synchronization is performed to fYMin.

3

Range synchronization fYMax

Controller enabled – bEn = TRUE

fYMax <> fYMax_1 (last cycle)

fY_Test > fYMax

If the upper range limit has changed and the precalculated controller output is now greater than fYMax, then synchronization is performed to fYMax

4

Synchronization with reversal of the control direction

Controller enabled – bEn = TRUE

eActn <> eActn_1 (last cycle)

It is synchronized so that the output holds the value BEFORE the reversal:
fY = fY_1 (last cycle)

5

Anti-Reset-Windup

Controller enabled – bEn = TRUE

If the precomputed controller output is limited by fYMin or fYMax, the I-component remains at the value from the last cycle. Only one move back into the permitted range remains possible.

Stop the controller

By applying a TRUE signal to the bHold input, the controller interrupts its internal P, I and D component calculation. This freezes the fY output as long as bHold is TRUE.

This can be used to prevent the controller from reacting to predictable events, such as the opening and closing of an airlock and the resulting drop and rise in pressure. The controller cannot detect this event and would otherwise have to unnecessarily build up and reduce the I component.

The fE output, which continuously displays the control deviation, is excluded from the hold function.

Neutral zone

A value of fNeutralZone > 0.0 enables the function of the neutral zone (deadband). A value equal to zero disables the deadband element and the values at the input are passed directly through.

If, for the active controller, the change at the input of the element in a PLC cycle is smaller than fNeutralZone / 2 in comparison with the previous PLC cycle, then the output is held at the value of the previous cycle until the change is larger than or equal to fNeutralZone / 2.

This function is intended to avoid an unnecessarily large number of actuating pulses.

Syntax

VAR_INPUT
  bEn                      : BOOL;
  fW                       : REAL;
  fX                       : REAL;
  eActn                    : E_BA_Action := E_BA_Action.eReverse;
  fYMax                    : REAL := 100;
  fYMin                    : REAL := 0;
  bSync                    : BOOL;
  fSync                    : REAL;
  bHold                    : BOOL;
END_VAR
VAR_INPUT CONSTANT PERSISTENT
  nCycleCall               : UDINT := 5;
  eOperationMode           : E_BA_PIDMode := E_BA_PIDMode.eP1ID;
  fProportionalConstant    : REAL;
  tIntegralTime            : TIME;
  tDerivativeTime          : TIME;
  tDampingTime             : TIME;
  fNeutralZone             : REAL := 0.0;
END_VAR
VAR_OUTPUT
  fY                       : REAL;
  fE                       : REAL;
END_VAR

FB_BA_PIDCtrl 4: Inputs

Name

Type

Description

bEn

BOOL

Controller enable.

fW

REAL

Setpoint of the controlled system.

fX

REAL

Actual value of the controlled system.

eActn

E_BA_Action

Control direction of the controller.

fYMax

REAL

Upper output limit of the controller [%].

fYMin

REAL

Lower output limit of the controller [%].
The value of fYMin is capped at fYMax.

bSync

BOOL

Synchronizes the controller to the value of fSync.

fSync

REAL

Synchronization value. The value fSync is internally limited to values from fYMin to fYMax.

bHold

BOOL

By applying a TRUE signal to the bHold input, the controller interrupts its internal P, I and D component calculation. This freezes the fY output as long as bHold is TRUE.

The fE output, which continuously displays the control deviation, is excluded from this.

FB_BA_PIDCtrl 5: Inputs CONSTANT PERSISTENT

Name

Type

Description

nCycleCall

UDINT

Call cycle of the function block as a multiple of the cycle time. Internally limited to a minimum value of 1.

eOperationMode

E_BA_PIDMode

Mode of operation of the controller: PID mode or P-ID mode

fProportionalConstant

REAL

Controller gain. Only affects the P part. Internally limited to a minimum value of 0.

TIntegralTime

TIME

Integral action time of the I part [ms]. A null value at this parameter disables the I part.

tDerivativeTime

TIME

Rate time of the D part [ms]. A null value at this parameter disables the D part.

tDampingTime

TIME

Damping time of the D part [s].

fNeutralZone

REAL

Dead zone

FB_BA_PIDCtrl 6: Outputs

Name

Type

Description

fY

REAL

Control value. Range limited by fYMin and fYMax.

fE

REAL

Control deviation (The calculation depends on the control direction).

FB_BA_PIDCtrl 7: Properties

Name

Type

Access

Description

ActiveCycle

BOOL

Get

The nCycleCall parameter can be used to set the number of PLC cycles after which the internal controller calculation will run (e.g., nCycleCall = 3: every third PLC cycle). The ActiveCycle property indicates whether the controller is currently undergoing a calculation cycle.

AntiResetWindup

BOOL

Get

The controller is in anti-reset windup status.

ControlDeviation

REAL

Get

Control deviation

HasDemand

BOOL

Get

If the controller is active (bEn = TRUE) and the control deviation is greater than zero, the value of this property is TRUE.

IsMaxLimit

BOOL

Get

The controller output fY is at the upper output limit fYMax.

IsMinLimit

BOOL

Get

The controller output fY is at the lower output limit fYMin.