KL6301 with CX5120

This example shows how to write a simple PLC program for EIB in TwinCAT and how to link it with the hardware. The task is to change the state of a switching output with a button.

Example: EIB_Sample_KL6301_CX5120.zip

KL6301 with CX5120 1:

The TwinCAT project is available for download as *.zip file. This must first be unpacked locally so that the archive (*.tnzip file) is available for import into the TwinCAT project.

Hardware

Setting up the components

Set up the hardware and the EIB components as described in the associated documentation.

This example assumes that a Set button was connected to the first KL1104 input and a Reset button to the second, and that the EIB group address of the switching output is known.

Software

Creation of the PLC program

Create a new "TwinCAT XAE Project" and create a "Standard PLC Project".
Add the Tc2_EIB library to the PLC project at "References".
Create a global variable list with the name GVL_EIB and create the following variables:

VAR_GLOBAL
    bSet                AT %I* : BOOL;
    bReset              AT %I* : BOOL
    arrKL6301_IN        AT %I* : ARRAY[1..24] OF BYTE;
    arrKL6301_OUT       AT %Q* : ARRAY[1..24] OF BYTE;
    stDataRec                  : EIB_REC;
END_VAR

Name

Type

Description

bSet

BOOL

Input variable for the Set button.

bReset

BOOL

Input variable for the Reset button.

arrKL6301_IN

BYTE

Input variable for the EIB terminal.

arrKL6301_OUT

BYTE

Output variable for the EIB terminal.

stDataRec

EIB_REC

Structure for the communication with EIB.

All EIB function blocks must be called in the same task.

In the MAIN program (ST), call the function block KL6301 and create the following variables.

PROGRAM MAIN
VAR
    fbKL6301       : KL6301;
    iStep          : INT;
END_VAR

In the program part, the KL6301 is initially assigned a physical address and the filter for receiving EIB telegrams is configured. For more information see KL6301.

CASE iStep OF
0:  // Initialising of the physical EIB address; has to be unique in the network
    fbKL6301.EIB_PHYS_ADDR.Area := 2; //EIB Address 2.3.4
    fbKL6301.EIB_PHYS_ADDR.Line := 3;
    fbKL6301.EIB_PHYS_ADDR.Device := 4;

    // Configuration of filters for the group addresses
    // Filter 1   1/1/0 to 1/1/63 equals 64 entries
    fbKL6301.EIB_GROUP_FILTER[1].GROUP_ADDR.MAIN:=1;
    fbKL6301.EIB_GROUP_FILTER[1].GROUP_ADDR.SUB_MAIN:=1;
    fbKL6301.EIB_GROUP_FILTER[1].GROUP_ADDR.NUMBER:=0;
    fbKL6301.EIB_GROUP_FILTER[1].GROUP_LEN:=63;
    // Filter 2   1/2/0 to 1/2/63 equals 64 entries
    fbKL6301.EIB_GROUP_FILTER[2].GROUP_ADDR.MAIN:=1;
    fbKL6301.EIB_GROUP_FILTER[2].GROUP_ADDR.SUB_MAIN:=2;
    fbKL6301.EIB_GROUP_FILTER[2].GROUP_ADDR.NUMBER:=0;
    fbKL6301.EIB_GROUP_FILTER[2].GROUP_LEN:=63;
    //Filter 3   1/4/0 to 1/4/63 equals 64 entries
    fbKL6301.EIB_GROUP_FILTER[3].GROUP_ADDR.MAIN:=1;
    fbKL6301.EIB_GROUP_FILTER[3].GROUP_ADDR.SUB_MAIN:=4;
    fbKL6301.EIB_GROUP_FILTER[3].GROUP_ADDR.NUMBER:=0;
    fbKL6301.EIB_GROUP_FILTER[3].GROUP_LEN:=63;
    //Filter 4   3/1/0 to 3/1/63 equals 64 entries
    fbKL6301.EIB_GROUP_FILTER[4].GROUP_ADDR.MAIN:=3;
    fbKL6301.EIB_GROUP_FILTER[4].GROUP_ADDR.SUB_MAIN:=1;
    fbKL6301.EIB_GROUP_FILTER[4].GROUP_ADDR.NUMBER:=0;
    fbKL6301.EIB_GROUP_FILTER[4].GROUP_LEN:=63;
// bActivate: activates the configuration of the KL6301 and enables the further data exchange
    fbKL6301.bActivate :=TRUE;

    IF fbKL6301.bReady THEN
        IF NOT fbKL6301.bError THEN
            iStep:=1; // EIB functionblock is now ready to send and receive
        ELSE
            iStep:=100; // EIB ERROR
        END_IF
    END_IF
1:  ;        // EIB functionblock is now ready to send and receive
100:  ;      // optional error handling EIB ERROR
END_CASE
//Call communication function block
fbKL6301(
    iMode:= 0,       // 4 filter with 64 entries each
    KL6301_IN:= GVL_EIB.arrKL6301_in, 
    KL6301_OUT:= GVL_EIB.arrKL6301_out,
    str_Data_Rec => GVL_EIB.stDataRec);

//Call programs for reading and sending
EIB_Send_Prg();
EIB_Rec_Prg();

Create an EIB program called EIB_Send_Prg() (CFC), in which the function block EIB_BIT_SEND is called.

Link the local variable bData with the global variables bSet and bReset, then with the input bData of the send block. Link the global variable stDataRec with st_Rec.

KL6301 with CX5120 2:

Create an EIB program called EIB_Rec_Prg() (CFC), in which the function block EIB_BIT_REC is called. In the sample, the pressing of a button is read by the function block. Link the global variable stDataRec with st_Rec.

KL6301 with CX5120 3:

Go to the task configuration and give the task a lower cycle time of 5 ms, for example.

Further conditions can be found in the description of the function block KL6301.

KL6301 with CX5120 4:

I/O configuration

Select the CX as target system and initiate a search for its hardware. In the project instance within the PLC section, you can see that the input and output variables are assigned to the task.

Now link the global variables with the inputs and outputs of the bus terminals.

The linking of the EIB variables is described in detail below.

Right-click the array arrKL6301_in and select "Change Link".

KL6301 with CX5120 5:

Under “I/O Configuration” select the terminal, select “All Types” and “Continuous”, then select “ParameterStatus”, “InputData1” to “InputData22” with the left mouse button and the >SHIFT< key. Then click "OK".

KL6301 with CX5120 6:

You can now check the link. To do this go onto the KL6301 and open it. All terminal data should now show a small arrow. If that is the case, then proceed in exactly the same way with the outputs.

KL6301 with CX5120 7: