BAC_BV_01

Functional description

The template determines a process value from several, prioritised set values (priority matrix, template inputs).
The template is used for output of a binary process value or display of the state of a unit.

Interface

BAC_BV_01 1:

Block diagram

BAC_BV_01 2:

VAR_INPUT

bEnSfty    : BOOL;
bValSfty   : BOOL;
bEnDst     : BOOL;
bValDst    : BOOL;
bEnLoc     : BOOL;
bValLoc    : BOOL;
bEnPgm     : BOOL;
bValPgm    : BOOL;

bEnSfty: Safety priority enable

bValSfty: Digital value safety priority

bEnDst: Enable fault priority.

bValDst: Digital value fault priority.

bEnLoc: Enable priority manual intervention

bValLoc: Digital value priority manual intervention

bEnPgm: Enable program priority

bValPgm: Digital value program priority

VAR_OUTPUT

bPrVal    : BOOL;

bPrVal: current value of the binary value object.

VAR CONSTANT

PLT_NUM    : BYTE := 1;

PLT_NUM: all alarms and events of all plant components within a controller are included in a global alarm and event list. The assignment of events and alarms to a plant is defined by the assignment of a PLT_NUM plant number.
The recording and processing of an alarm from an aggregate or a device takes place within the templates by means of the alarm function block FB_BA_Alarm.
The evaluation of the alarms of a plant, e.g. for the generation of a collective message or for plant shutdown in case of relevant faults, takes place within the template BAC_PltAlm_01 by means of the function block FB_BA_AlarmPlt.
The evaluation of different plant events within the templates of a plant, takes place within the template BAC_PltComnMsg_01 by means of the function block FB_BA_ComnMsg.

Important! The assignment and evaluation of the alarms and events of a plant can only be done correctly if all templates of a plant have the same plant number!

The plant number can be assigned in the Project Builder in the parameter menu for the templates or via a column in the Excel import.

Program description

Instance

Type

optional

Task

BV

FB_BACnetBV1205

 

BV object for output or display of a process value

 

 

 

Priority:

Enable

Value

PRIO_SAFETY (1)

Input bEnSfty

Input bValSfty

PRIO_DISTURBANCE (3)

Input bEnDst

Input bValDst

PRIO_LOCAL (8)

Input bEnLoc

Input bValLoc

PRIO_PROGRAM (15)

Input bEnPgm

Input bValPgm

Version history

Version number

Comments

1.0.1

First release