Parallel use for redundancy
Recommendations for the construction of redundant power supply systems:
- Power supplies that contain a DC-OK signal contact are best suited for the construction of redundant power supply systems.
 - Use this DC-OK signal contact to monitor the individual power supplies.
 - For the power supplies with EtherCAT (e.g. PS2001-2420-1001) the DC-OK bit can be used for monitoring.
 - Use separate grids for each power supply whenever possible.
 - It is recommended to set the output voltages of all devices to the same value (±100 mV) or to leave them at the factory setting.
 
- In addition, parallel use must be enabled via the "PSU Features" object in index 0x8001:01 "Parallel use", see chapter "Parallel Use".
 