Parameterization with KS2000

Connect the configuration interface of your Fieldbus Coupler with the serial interface of your PC via the configuration cable and start the KS2000 Configuration Software.

Click on the Login button. The configuration software will now load the information for the connected fieldbus station.
In the example shown, this is

  • a BK9000 Bus Coupler for Ethernet
  • a KL1xx2 digital input terminal
  • a KL9060 Adapter Terminal for connecting power terminals (which is not yet displayed by some versions of KS2000)
  • a KL8001 Power Terminal for connecting Siemens contactors of the Sirius R3 series
  • a ZS1010-1610 bus end plug (some versions of KS2000 still show the bus end plug as the KL9010 End Terminal)
Display of the fieldbus station in KS2000

The left-hand KS2000 window displays the terminals of the fieldbus station in a tree structure.
The right-hand KS2000 window contains a graphic display of the fieldbus station terminals.

In the tree structure of the left-hand window, click on the plus-sign next to the terminal whose parameters you wish to change (item 2 in the example).

KS2000 branches for channel 1 of the KL8001

Click on Settings. You can modify the power terminal settings in the configuration mask which is then displayed.