AS-i parameters - overview

All information contained in the AS-i master and the AS-i slaves are described in the following parameters, which are accessible via the cyclic parameter interface (process data mode), via acyclic services (e.g. PROFIBUS DPV1), or via the KS2000 configuration software.

Overview of the parameters

Parameter numbers

Access

stored
in flash

Description

0x20

R/W

yes

Width of the process image interface

0x28

R

yes

General Information

0x30

R/W

no

AS-i string parameters

0x40 to 0x47

R/W

yes*

Projected I/O IDs of all AS-i slaves

0x48 to 0x4F

R/W

yes*

Projected ID codes of all AS-i slaves

0x50 to 0x57

R/W

yes**

Activation parameters for the AS-i slaves

0x58 to 0x59

R/W

yes*

List of the AS-i slaves that are projected at the next start

0x60 to 0x61

R/W

yes*

List of I/O IDs of all AS-i slaves to be checked

0x68 to 0x69

R/W

yes*

List of ID codes of all AS-i slaves to be checked

0x70 to 0x71

R/W

yes*

List of extended ID codes 1 of all AS-i slaves to be checked

0x78 to 0x79

R/W

yes*

List of extended ID codes 2 of all AS-i slaves to be checked

0x80 to 0x87

R

no

Data of digital AS-i slaves

0x90 to 0x97

R

no

Read I/O IDs of all AS-i slaves

0x98 to 0x9F

R

no

Read ID codes of all AS-i slaves

0xA0 to 0xA7

R

no

Read status of all AS-i slaves

0xA8 and 0xA9

R

no

List of currently projected AS-i slaves (LPS)

0xB0 and 0xB1

R

no

List of detected AS-i slaves (LDS)

0xB8 and 0xB9

R

no

List of activated AS-i slaves (LAS)

0xC0 and 0xC1

 

 

List of slaves that support the extended ID codes (ID codes 1 and 2)

0xC8

 

 

List of slaves that support extended addressing (as B slaves with addresses greater than 32)

0xD0 to 0xD7

R

no

Read extended ID codes 1 of all AS-i slaves

0xD8 to 0xDF

R

no

Read extended ID codes 2 of all AS-i slaves

0xE0 to 0xE7

R/W

yes*

Currently projected extended ID codes 1 of all AS-i slaves

0xE8 to 0xEF

R/W

yes*

Currently projected extended ID codes 2 of all AS-i slaves

0xF0

 

 

List of analog slaves

0xF8

 

 

List of safety slaves

0x100

W

-

AS-i command interface

0x108

W

-

General command interface

0x120 to 0x12F

R

no

Status register

0x140 to 0x15F

R/W

no

Physical fault counter

0x160 to 0x17F

R/W

no

Timeout counter

0x180 to 0x19F

R/W

no

Response counter

0x1A0 to 0x1BF

R/W

no

Leave DataExch counter

0x1C0 to 0x1DF

R/W

no

DataExch failed counter

0x200 to 0x27F

R/W

no

Data of analog AS-i slaves

0x300

 

 

Cycle times

0x310

 

 

Statistics

0x320 to 0x32F

 

 

Timeout statistics for each AS-i slave

0x340 to 0x35F

 

 

Data exchange repeat counter for each AS-i slave

AS-i parameters - overview 1:

*) Activation parameters for the AS-i slaves

Activation parameters can only be changed:

  • in Config Mode
  • ii Protected Mode, if Config OK is not set
AS-i parameters - overview 2:

**) Adoption of the parameters

Changes of these parameters are not indicated by the AS-i terminal until the AS-i terminal has passed the activation phase again. This is the case after

  • the AS-i terminal has been switched off and on again (power-on/reset) or
  • the AS-i master has been switched offline and online again by setting and resetting the offline flag (checkbox Offline Phase in the Settings dialog of KS2000).
  • Set Protected has been executed by short-circuiting the Set inputs Set A and Set B or
  • Set Protected has been executed via the [Project all detected slaves] button in the Settings dialog of ks2000.