AS-i parameter description
Parameter 0x20: Size of the process image
Parameter 0x20 contains the size of the process image. This parameter can be read or written. It is stored in the flash of the KL6201/KL6211 (i.e. it is still available after power off/on).
|
Parameter | Bit | Description | default |
|---|---|---|---|
0x20 | 0 to 15 | 0dec: 6-byte interface | 1dec |
16 to 31 | reserved | - |
After changing the process image the Bus Coupler must be restarted for the modified process image to take effect.
Parameter 0x28: General Information
Parameter 0x28 contains the number of the terminal (6201) and firmware version (this parameter is read only):
|
Parameter | Bit | Description |
|---|---|---|
0x28 | 0 to 15 | Terminal identifier: 0x1839 (6201dec) |
16 to 31 | Firmware version of the terminal |
Parameter 0x30: AS-i string parameters
Parameter 0x30 can be used to read or write AS-i strings. The whole AS-i string is transferred in triples. Parameter 0x30 is supported from firmware version BA.
|
Parameter | Bit | Description | Value |
|---|---|---|---|
0x30 | 0 to 7 | Byte 0 of data triple m (byte m) | 0 to 255 |
8 to 15 | Byte 1 of data triple m (byte m + 1) | 0 to 255 | |
16 to 23 | Byte 2 of data triple m (byte m + 2) | 0 to 255 | |
24 to 31 | Byte offset (m = multiple of 3) | m |
![]() | String transfer A string transfer can be used to transfer up to 219 bytes of string data. |
Parameters 0x40 to 0x47: Projected I/O ID (set configuration)
In protected mode, the I/O ID of the projected AS-i slaves is checked. The currently projected 4-bit I/O IDs of the AS-i slaves are located in parameters 0x40 to 0x47 (these parameters are read/write and are stored in the flash of the AS-i master (i.e. they are still available after power off/on)):
Parameter | Bit | Description |
|---|---|---|
0x40 | 0 to 3 | reserved |
4 to 7 | projected I/O ID, AS-i slave 1 (1A) | |
8 to 11 | projected I/O ID, AS-i slave 2 (2A) | |
12 to 15 | projected I/O ID, AS-i slave 3 (3A) | |
16 to 19 | projected I/O ID, AS-i slave 4 (4A) | |
20 to 23 | projected I/O ID, AS-i slave 5 (5A) | |
24 to 27 | projected I/O ID, AS-i slave 6 (6A) | |
28 to 31 | projected I/O ID, AS-i slave 7 (7A) |
Parameter | Bit | Description |
|---|---|---|
0x41 | 0 to 3 | projected I/O ID, AS-i slave 8 (8A) |
4 to 7 | projected I/O ID, AS-i slave 9 (9A) | |
8 to 11 | projected I/O ID, AS-i slave 10 (10A) | |
12 to 15 | projected I/O ID, AS-i slave 11 (11A) | |
16 to 19 | projected I/O ID, AS-i slave 12 (12A) | |
20 to 23 | projected I/O ID, AS-i slave 13 (13A) | |
24 to 27 | projected I/O ID, AS-i slave 14 (14A) | |
28 to 31 | projected I/O ID, AS-i slave 15 (15A) | |
0x42 | 0 to 3 | projected I/O ID, AS-i slave 16 (16A) |
4 to 7 | projected I/O ID, AS-i slave 17 (17A) | |
8 to 11 | projected I/O ID, AS-i slave 18 (18A) | |
12 to 15 | projected I/O ID, AS-i slave 19 (19A) | |
16 to 19 | projected I/O ID, AS-i slave 20 (20A) | |
20 to 23 | projected I/O ID, AS-i slave 21 (21A) | |
24 to 27 | projected I/O ID, AS-i slave 22 (22A) | |
28 to 31 | projected I/O ID, AS-i slave 23 (23A) | |
0x43 | 0 to 3 | projected I/O ID, AS-i slave 24 (24A) |
4 to 7 | projected I/O ID, AS-i slave 25 (25A) | |
8 to 11 | projected I/O ID, AS-i slave 26 (26A) | |
12 to 15 | projected I/O ID, AS-i slave 27 (27A) | |
16 to 19 | projected I/O ID, AS-i slave 28 (28A) | |
20 to 23 | projected I/O ID, AS-i slave 29 (29A) | |
24 to 27 | projected I/O ID, AS-i slave 30 (30A) | |
28 to 31 | projected I/O ID, AS-i slave 31 (31A) | |
0x44 | 0 to 3 | Reserved (AS-i slave address 32 is not permitted) |
4 to 7 | projected I/O ID, AS-i slave 33 (1B) | |
8 to 11 | projected I/O ID, AS-i slave 34 (2B) | |
12 to 15 | projected I/O ID, AS-i slave 35 (3B) | |
16 to 19 | projected I/O ID, AS-i slave 36 (4B) | |
20 to 23 | projected I/O ID, AS-i slave 37 (5B) | |
24 to 27 | projected I/O ID, AS-i slave 38 (6B) | |
28 to 31 | projected I/O ID, AS-i slave 39 (7B) | |
0x45 | 0 to 3 | projected I/O ID, AS-i slave 40 (8B) |
4 to 7 | projected I/O ID, AS-i slave 41 (9B) | |
8 to 11 | projected I/O ID, AS-i slave 42 (10B) | |
12 to 15 | projected I/O ID, AS-i slave 43 (11B) | |
16 to 19 | projected I/O ID, AS-i slave 44 (12B) | |
20 to 23 | projected I/O ID, AS-i slave 45 (13B) | |
24 to 27 | projected I/O ID, AS-i slave 46 (14B) | |
28 to 31 | projected I/O ID, AS-i slave 47 (15B) | |
0x46 | 0 to 3 | projected I/O ID, AS-i slave 48 (16B) |
4 to 7 | projected I/O ID, AS-i slave 49 (17B) | |
8 to 11 | projected I/O ID, AS-i slave 50 (18B) | |
12 to 15 | projected I/O ID, AS-i slave 51 (19B) | |
16 to 19 | projected I/O ID, AS-i slave 52 (20B) | |
20 to 23 | projected I/O ID, AS-i slave 53 (21B) | |
24 to 27 | projected I/O ID, AS-i slave 54 (22B) | |
28 to 31 | projected I/O ID, AS-i slave 55 (23B) | |
0x47 | 0 to 3 | projected I/O ID, AS-i slave 56 (24B) |
4 to 7 | projected I/O ID, AS-i slave 57 (25B) | |
8 to 11 | projected I/O ID, AS-i slave 58 (26B) | |
12 to 15 | projected I/O ID, AS-i slave 59 (27B) | |
16 to 19 | projected I/O ID, AS-i slave 60 (28B) | |
20 to 23 | projected I/O ID, AS-i slave 61 (29B) | |
24 to 27 | projected I/O ID, AS-i slave 62 (30B) | |
28 to 31 | projected I/O ID, AS-i slave 63 (31B) |
Parameters 0x48 to 0x4F: Projected ID code (nominal configuration)
In protected mode, the ID code of the projected AS-i slaves is checked. The projected 4-bit ID codes of the AS-i slaves are located in parameters 0x48 to 0x4F (these parameters are read/write and are stored in the flash of the AS-i master (i.e. they are still available after power off/on)):
Parameter | Bit | Description |
|---|---|---|
0x48 | 0 to 3 | reserved |
4 to 7 | projected ID code, AS-i slave 1 (1A) | |
8 to 11 | projected ID code, AS-i slave 2 (2A) | |
12 to 15 | projected ID code, AS-i slave 3 (3A) | |
16 to 19 | projected ID code, AS-i slave 4 (4A) | |
20 to 23 | projected ID code, AS-i slave 5 (5A) | |
24 to 27 | projected ID code, AS-i slave 6 (6A) | |
28 to 31 | projected ID code, AS-i slave 7 (7A) | |
0x49 | 0 to 3 | projected ID code, AS-i slave 8 (8A) |
4 to 7 | projected ID code, AS-i slave 9 (9A) | |
8 to 11 | projected ID code, AS-i slave 10 (10A) | |
12 to 15 | projected ID code, AS-i slave 11 (11A) | |
16 to 19 | projected ID code, AS-i slave 12 (12A) | |
20 to 23 | projected ID code, AS-i slave 13 (13A) | |
24 to 27 | projected ID code, AS-i slave 14 (14A) | |
28 to 31 | projected ID code, AS-i slave 15 (15A) | |
0x4A | 0 to 3 | projected ID code, AS-i slave 16 (16A) |
4 to 7 | projected ID code, AS-i slave 17 (17A) | |
8 to 11 | projected ID code, AS-i slave 18 (18A) | |
12 to 15 | projected ID code, AS-i slave 19 (19A) | |
16 to 19 | projected ID code, AS-i slave 20 (20A) | |
20 to 23 | projected ID code, AS-i slave 21 (21A) | |
24 to 27 | projected ID code, AS-i slave 22 (22A) | |
28 to 31 | projected ID code, AS-i slave 23 (23A) | |
0x4B | 0 to 3 | projected ID code, AS-i slave 24 (24A) |
4 to 7 | projected ID code, AS-i slave 25 (25A) | |
8 to 11 | projected ID code, AS-i slave 26 (26A) | |
12 to 15 | projected ID code, AS-i slave 27 (27A) | |
16 to 19 | projected ID code, AS-i slave 28 (28A) | |
20 to 23 | projected ID code, AS-i slave 29 (29A) | |
24 to 27 | projected ID code, AS-i slave 30 (30A) | |
28 to 31 | projected ID code, AS-i slave 31 (31A) | |
0x4C | 0 to 3 | Reserved (AS-i slave address 32 is not permitted) |
4 to 7 | projected ID code, AS-i slave 33 (1B) | |
8 to 11 | projected ID code, AS-i slave 34 (2B) | |
12 to 15 | projected ID code, AS-i slave 35 (3B) | |
16 to 19 | projected ID code, AS-i slave 36 (4B) | |
20 to 23 | projected ID code, AS-i slave 37 (5B) | |
24 to 27 | projected ID code, AS-i slave 38 (6B) | |
28 to 31 | projected ID code, AS-i slave 39 (7B) | |
0x4D | 0 to 3 | projected ID code, AS-i slave 40 (8B) |
4 to 7 | projected ID code, AS-i slave 41 (9B) | |
8 to 11 | projected ID code, AS-i slave 42 (10B) | |
12 to 15 | projected ID code, AS-i slave 43 (11B) | |
16 to 19 | projected ID code, AS-i slave 44 (12B) | |
20 to 23 | projected ID code, AS-i slave 45 (13B) | |
24 to 27 | projected ID code, AS-i slave 46 (14B) | |
28 to 31 | projected ID code, AS-i slave 47 (15B) |
Parameter | Bit | Description |
|---|---|---|
0x4E | 0 to 3 | projected ID code, AS-i slave 48 (16B) |
4 to 7 | projected ID code, AS-i slave 49 (17B) | |
8 to 11 | projected ID code, AS-i slave 50 (18B) | |
12 to 15 | projected ID code, AS-i slave 51 (19B) | |
16 to 19 | projected ID code, AS-i slave 52 (20B) | |
20 to 23 | projected ID code, AS-i slave 53 (21B) | |
24 to 27 | projected ID code, AS-i slave 54 (22B) | |
28 to 31 | projected ID code, AS-i slave 55 (23B) | |
0x4F | 0 to 3 | projected ID code, AS-i slave 56 (24B) |
4 to 7 | projected ID code, AS-i slave 57 (25B) | |
8 to 11 | projected ID code, AS-i slave 58 (26B) | |
12 to 15 | projected ID code, AS-i slave 59 (27B) | |
16 to 19 | projected ID code, AS-i slave 60 (28B) | |
20 to 23 | projected ID code, AS-i slave 61 (29B) | |
24 to 27 | projected ID code, AS-i slave 62 (30B) | |
28 to 31 | projected ID code, AS-i slave 63 (31B) |
Parameters 0x50 to 0x57: Activation parameters for the AS-i slaves
During the activation phase (or during the inclusion phase - for AS-i slaves that are added later), 4-bit parameter data are sent once to each AS-i slave prior to the first data exchange. The activation parameters can be specified for each AS-i slave via parameters 0x50 to 0x57. The precise definition of the activation parameters for each individual AS-i slave can be found in the documentation associated with the slave.
Parameters 0x50 to 0x57 can be read or written and are stored in the flash of the AS-i master, i.e. they are still available after power off/on of the AS-i master.
Parameter | Bit | Description | default |
|---|---|---|---|
0x50 | 0 to 3 | reserved | - |
4 to 7 | Activation parameter, AS-i slave 1 (1A) | 0x0F | |
8 to 11 | Activation parameter, AS-i slave 2 (2A) | 0x0F | |
12 to 15 | Activation parameter, AS-i slave 3 (3A) | 0x0F | |
16 to 19 | Activation parameter, AS-i slave 4 (4A) | 0x0F | |
20 to 23 | Activation parameter, AS-i slave 5 (5A) | 0x0F | |
24 to 27 | Activation parameter, AS-i slave 6 (6A) | 0x0F | |
28 to 31 | Activation parameter, AS-i slave 7 (7A) | 0x0F | |
0x51 | 0 to 3 | Activation parameter, AS-i slave 8 (8A) | 0x0F |
4 to 7 | Activation parameter, AS-i slave 9 (9A) | 0x0F | |
8 to 11 | Activation parameter, AS-i slave 10 (10A) | 0x0F | |
12 to 15 | Activation parameter, AS-i slave 11 (11A) | 0x0F | |
16 to 19 | Activation parameter, AS-i slave 12 (12A) | 0x0F | |
20 to 23 | Activation parameter, AS-i slave 13 (13A) | 0x0F | |
24 to 27 | Activation parameter, AS-i slave 14 (14A) | 0x0F | |
28 to 31 | Activation parameter, AS-i slave 15 (15A) | 0x0F | |
0x52 | 0 to 3 | Activation parameter, AS-i slave 16 (16A) | 0x0F |
4 to 7 | Activation parameter, AS-i slave 17 (17A) | 0x0F | |
8 to 11 | Activation parameter, AS-i slave 18 (18A) | 0x0F | |
12 to 15 | Activation parameter, AS-i slave 19 (19A) | 0x0F | |
16 to 19 | Activation parameter, AS-i slave 20 (20A) | 0x0F | |
20 to 23 | Activation parameter, AS-i slave 21 (21A) | 0x0F | |
24 to 27 | Activation parameter, AS-i slave 22 (22A) | 0x0F | |
28 to 31 | Activation parameter, AS-i slave 23 (23A) | 0x0F |
Parameter | Bit | Description | default |
|---|---|---|---|
0x53 | 0 to 3 | Activation parameter, AS-i slave 24 (24A) | 0x0F |
4 to 7 | Activation parameter, AS-i slave 25 (25A) | 0x0F | |
8 to 11 | Activation parameter, AS-i slave 26 (26A) | 0x0F | |
12 to 15 | Activation parameter, AS-i slave 27 (27A) | 0x0F | |
16 to 19 | Activation parameter, AS-i slave 28 (28A) | 0x0F | |
20 to 23 | Activation parameter, AS-i slave 29 (29A) | 0x0F | |
24 to 27 | Activation parameter, AS-i slave 30 (30A) | 0x0F | |
28 to 31 | Activation parameter, AS-i slave 31 (31A) | 0x0F | |
0x54 | 0 to 3 | Reserved (AS-i slave address 32 is not permitted) | - |
4 to 7 | Activation parameter, AS-i slave 33 (1B) | 0x0F | |
8 to 11 | Activation parameter, AS-i slave 34 (2B) | 0x0F | |
12 to 15 | Activation parameter, AS-i slave 35 (3B) | 0x0F | |
16 to 19 | Activation parameter, AS-i slave 36 (4B) | 0x0F | |
20 to 23 | Activation parameter, AS-i slave 37 (5B) | 0x0F | |
24 to 27 | Activation parameter, AS-i slave 38 (6B) | 0x0F | |
28 to 31 | Activation parameter, AS-i slave 39 (7B) | 0x0F | |
0x55 | 0 to 3 | Activation parameter, AS-i slave 40 (8B) | 0x0F |
4 to 7 | Activation parameter, AS-i slave 41 (9B) | 0x0F | |
8 to 11 | Activation parameter, AS-i slave 42 (10B) | 0x0F | |
12 to 15 | Activation parameter, AS-i slave 43 (11B) | 0x0F | |
16 to 19 | Activation parameter, AS-i slave 44 (12B) | 0x0F | |
20 to 23 | Activation parameter, AS-i slave 45 (13B) | 0x0F | |
24 to 27 | Activation parameter, AS-i slave 46 (14B) | 0x0F | |
28 to 31 | Activation parameter, AS-i slave 47 (15B) | 0x0F | |
0x56 | 0 to 3 | Activation parameter, AS-i slave 48 (16B) | 0x0F |
4 to 7 | Activation parameter, AS-i slave 49 (17B) | 0x0F | |
8 to 11 | Activation parameter, AS-i slave 50 (18B) | 0x0F | |
12 to 15 | Activation parameter, AS-i slave 51 (19B) | 0x0F | |
16 to 19 | Activation parameter, AS-i slave 52 (20B) | 0x0F | |
20 to 23 | Activation parameter, AS-i slave 53 (21B) | 0x0F | |
24 to 27 | Activation parameter, AS-i slave 54 (22B) | 0x0F | |
28 to 31 | Activation parameter, AS-i slave 55 (23B) | 0x0F | |
0x57 | 0 to 3 | Activation parameter, AS-i slave 56 (24B) | 0x0F |
4 to 7 | Activation parameter, AS-i slave 57 (25B) | 0x0F | |
8 to 11 | Activation parameter, AS-i slave 58 (26B) | 0x0F | |
12 to 15 | Activation parameter, AS-i slave 59 (27B) | 0x0F | |
16-19 | Activation parameter, AS-i slave 60 (28B) | 0x0F | |
20 to 23 | Activation parameter, AS-i slave 61 (29B) | 0x0F | |
24 to 27 | Activation parameter, AS-i slave 62 (30B) | 0x0F | |
28 to 31 | Activation parameter, AS-i slave 63 (31B) | 0x0F |
Parameters 0x58 and 0x59: List of the AS-i slaves that are projected at the next start
This list contains the AS-i slaves that are projected during the next start (transition from offline phase to detection phase). For each AS-i slave, parameters 0x58 to 0x59 contain a bit that indicates whether the associated AS-i slave is projected (this parameter is read/write and is stored in the flash of the AS-i master (i.e. it is still available after power off/on)):
Parameter | Bit | Description |
|---|---|---|
0x58 | 0 | reserved |
1 | 0bin: AS-i slave 1 (1A) is not projected | |
... | ... | |
31 | 0bin: AS-i slave 31 (31A) is not projected | |
0x59 | 0 | reserved |
1 | 0bin: AS-i slave 33 (1B) is not projected | |
... | ... | |
31 | 0bin: AS-i slave 63 (31B) is not projected |
Parameters 0x60 and 0x61: Verification of the I/O IDs of the AS-i slaves
This list defines whether the I/O IDs should be checked in protected mode (projecting active). For each AS-i slave, parameters 0x60 and 0x61 contain a bit that indicates whether the I/O ID of the associated AS-i slave should be checked (this parameter is read/write and is stored in the flash of the AS-i master (i.e. it is still available after power off/on)):
Parameter | Bit | Description |
|---|---|---|
0x60 | 0 | reserved |
1 | 0bin: I/O ID of AS-i slave 1 (1A) is not checked in protected mode (0) | |
... | ... | |
31 | 0bin: I/O ID of AS-i slave 31 (31A) is not checked in protected mode (0) | |
0x61 | 0 | reserved |
1 | 0bin: I/O ID of AS-i slave 33 (1B) is not checked in protected mode (0) | |
... | ... | |
31 | 0bin: I/O ID of AS-i slave 63 (31B) is not checked in protected mode (0) |
Parameters 0x68 and 0x69: Verification of the ID codes of the AS-i slaves
This list defines whether the ID codes should be checked in protected mode (projecting active). For each AS-i slave, parameters 0x68 and 0x69 contain a bit that indicates whether the ID code of the associated AS-i slave should be checked (this parameter is read/write and is stored in the flash of the AS-i master (i.e. it is still available after power off/on)):
Parameter | Bit | Description |
|---|---|---|
0x68 | 0 | reserved |
1 | 0bin: ID code of AS-i slave 1 (1A) is not checked in protected mode | |
... | ... | |
31 | 0bin: ID code of AS-i slave 31 (31A) is not checked in protected mode | |
0x69 | 0 | reserved |
1 | 0bin: ID code of AS-i slave 33 (1B) is not checked in protected mode | |
... | ... | |
31 | 0bin: ID code of AS-i slave 63 (31B) is not checked in protected mode |
Parameters 0x70 and 0x71: Verification of the extended ID codes 1 of the AS-i slaves
This list defines whether the extended ID codes 1 should be checked in protected mode (projecting active). For each AS-i slave, parameters 0x70 and 0x71 contain a bit that indicates whether the extended ID code 2 of the associated AS-i slave should be checked (this parameter is read/write and is stored in the flash of the AS-i master (i.e. it is still available after power off/on)):
Parameter | Bit | Description |
|---|---|---|
0x70 | 0 | reserved |
1 | 0bin: Extended ID code 1 of AS-i slave 1 (1A) is not checked in protected mode | |
... | ... | |
31 | 0bin: Extended ID code 1 of AS-i slave 31 (31A) is not checked in protected mode | |
0x71 | 0 | reserved |
1 | 0bin: Extended ID code 1 of AS-i slave 33 (1B) is not checked in protected mode | |
... | ... | |
31 | 0bin: Extended ID code 1 of AS-i slave 63 (31B) is not checked in protected mode |
Parameters 0x78 and 0x79: Verification of the extended ID codes 2 of the AS-i slaves
This list defines whether the ID codes should be checked in protected mode (projecting active). For each AS-i slave, parameters 0x78 and 0x79 contain a bit that indicates whether the extended ID code 2 of the associated AS-i slave should be checked (this parameter is read/write and is stored in the flash of the AS-i master (i.e. it is still available after power off/on)):
Parameter | Bit | Description |
|---|---|---|
0x78 | 0 | reserved |
1 | 0bin: Extended ID code 2 of AS-i slave 1 (1A) is not checked in protected mode | |
... | ... | |
31 | 0bin: Extended ID code 2 of AS-i slave 3 1 (31A) is not checked in protected mode | |
0x79 | 0 | reserved |
1 | 0bin: Extended ID code 2 of AS-i slave 33 (1B) is not checked in protected mode | |
... | ... | |
31 | 0bin: Extended ID code 2 of AS-i slave 63 (31B) is not checked in protected mode |
Parameters 0x80 to 0x87: Digital inputs and outputs
The digital process data of the AS-i slaves can also be read or written via the parameters. For the 12-byte KBus interface, digital outputs can only be written for the AS-i slaves from address 12 (the digital outputs of AS-i slaves 1-11 are overwritten by the process data), for the 22-byte KBus interface from address 33 (the digital outputs of AS-i slaves 1-31 are overwritten by the process data), and for the 30-byte KBus interface from address 48 (the digital outputs of AS-i slaves 1-47 are overwritten by the process data). The digital inputs (read access) or digital outputs (write access) of all AS-i slaves are stored in parameters 0x80 to 0x87 (these parameters are read/write (read for inputs, write for outputs)):
Parameter | Bit | Description |
|---|---|---|
0x80 | 0 to 3 | Digital inputs (read) or digital outputs (write), AS-i slave 0 |
4 to 7 | Digital inputs (read) or digital outputs (write), AS-i slave 1 (1A) | |
8 to 11 | Digital inputs (read) or digital outputs (write), AS-i slave 2 (2A) | |
12 to 15 | Digital inputs (read) or digital outputs (write), AS-i slave 3 (3A) | |
16-19 | Digital inputs (read) or digital outputs (write), AS-i slave 4 (4A) | |
20 to 23 | Digital inputs (read) or digital outputs (write), AS-i slave 5 (5A) | |
24 to 27 | Digital inputs (read) or digital outputs (write), AS-i slave 6 (6A) | |
28 to 31 | Digital inputs (read) or digital outputs (write), AS-i slave 7 (7A) |
Parameter | Bit | Description |
|---|---|---|
0x81 | 0 to 3 | Digital inputs (read) or digital outputs (write), AS-i slave 8 (8A) |
4 to 7 | Digital inputs (read) or digital outputs (write), AS-i slave 9 (9A) | |
8 to 11 | Digital inputs (read) or digital outputs (write), AS-i slave 10 (10A) | |
12 to 15 | Digital inputs (read) or digital outputs (write), AS-i slave 11 (11A) | |
16-19 | Digital inputs (read) or digital outputs (write), AS-i slave 12 (12A) | |
20 to 23 | Digital inputs (read) or digital outputs (write), AS-i slave 13 (13A) | |
24 to 27 | Digital inputs (read) or digital outputs (write), AS-i slave 14 (14A) | |
28 to 31 | Digital inputs (read) or digital outputs (write), AS-i slave 15 (15A) | |
0x82 | 0 to 3 | Digital inputs (read) or digital outputs (write), AS-i slave 16 (16A) |
4 to 7 | Digital inputs (read) or digital outputs (write), AS-i slave 17 (17A) | |
8 to 11 | Digital inputs (read) or digital outputs (write), AS-i slave 18 (18A) | |
12 to 15 | Digital inputs (read) or digital outputs (write), AS-i slave 19 (19A) | |
16-19 | Digital inputs (read) or digital outputs (write), AS-i slave 20 (20A) | |
20 to 23 | Digital inputs (read) or digital outputs (write), AS-i slave 21 (21A) | |
24 to 27 | Digital inputs (read) or digital outputs (write), AS-i slave 22 (22A) | |
28 to 31 | Digital inputs (read) or digital outputs (write), AS-i slave 23 (23A) | |
0x83 | 0 to 3 | Digital inputs (read) or digital outputs (write), AS-i slave 24 (24A) |
4 to 7 | Digital inputs (read) or digital outputs (write), AS-i slave 25 (25A) | |
8 to 11 | Digital inputs (read) or digital outputs (write), AS-i slave 26 (26A) | |
12 to 15 | Digital inputs (read) or digital outputs (write), AS-i slave 27 (27A) | |
16-19 | Digital inputs (read) or digital outputs (write), AS-i slave 28 (28A) | |
20 to 23 | Digital inputs (read) or digital outputs (write), AS-i slave 29 (29A) | |
24 to 27 | Digital inputs (read) or digital outputs (write), AS-i slave 30 (30A) | |
28 to 31 | Digital inputs (read) or digital outputs (write), AS-i slave 31 (31A) | |
0x84 | 0 to 3 | Reserved (AS-i slave address 32 is not permitted) |
4 to 7 | Digital inputs (read) or digital outputs (write), AS-i slave 33 (1B) | |
8 to 11 | Digital inputs (read) or digital outputs (write), AS-i slave 34 (2B) | |
12 to 15 | Digital inputs (read) or digital outputs (write), AS-i slave 35 (3B) | |
16 to 19 | Digital inputs (read) or digital outputs (write), AS-i slave 36 (4B) | |
20 to 23 | Digital inputs (read) or digital outputs (write), AS-i slave 37 (5B) | |
24 to 27 | Digital inputs (read) or digital outputs (write), AS-i slave 38 (6B) | |
28 to 31 | Digital inputs (read) or digital outputs (write), AS-i slave 39 (7B) | |
0x85 | 0 to 3 | Digital inputs (read) or digital outputs (write), AS-i slave 40 (8B) |
4 to 7 | Digital inputs (read) or digital outputs (write), AS-i slave 41 (9B) | |
8 to 11 | Digital inputs (read) or digital outputs (write), AS-i slave 42 (10B) | |
12 to 15 | Digital inputs (read) or digital outputs (write), AS-i slave 43 (11B) | |
16 to 19 | Digital inputs (read) or digital outputs (write), AS-i slave 44 (12B) | |
20 to 23 | Digital inputs (read) or digital outputs (write), AS-i slave 45 (13B) | |
24 to 27 | Digital inputs (read) or digital outputs (write), AS-i slave 46 (14B) | |
28 to 31 | Digital inputs (read) or digital outputs (write), AS-i slave 47 (15B) | |
0x86 | 0 to 3 | Digital inputs (read) or digital outputs (write), AS-i slave 48 (16B) |
4 to 7 | Digital inputs (read) or digital outputs (write), AS-i slave 49 (17B) | |
8 to 11 | Digital inputs (read) or digital outputs (write), AS-i slave 50 (18B) | |
12 to 15 | Digital inputs (read) or digital outputs (write), AS-i slave 51 (19B) | |
16 to 19 | Digital inputs (read) or digital outputs (write), AS-i slave 52 (20B) | |
20 to 23 | Digital inputs (read) or digital outputs (write), AS-i slave 53 (21B) | |
24 to 27 | Digital inputs (read) or digital outputs (write), AS-i slave 54 (22B) | |
28 to 31 | Digital inputs (read) or digital outputs (write), AS-i slave 55 (23B) | |
0x87 | 0 to 3 | Digital inputs (read) or digital outputs (write), AS-i slave 56 (24B) |
4 to 7 | Digital inputs (read) or digital outputs (write), AS-i slave 57 (25B) | |
8 to 11 | Digital inputs (read) or digital outputs (write), AS-i slave 58 (26B) | |
12 to 15 | Digital inputs (read) or digital outputs (write), AS-i slave 59 (27B) | |
16 to 19 | Digital inputs (read) or digital outputs (write), AS-i slave 60 (28B) | |
20 to 23 | Digital inputs (read) or digital outputs (write), AS-i slave 61 (29B) | |
24 to 27 | Digital inputs (read) or digital outputs (write), AS-i slave 62 (30B) | |
28 to 31 | Digital inputs (read) or digital outputs (write), AS-i slave 63 (31B) |
Parameters 0x90 to 0x97: Read I/O ID (actual configuration)
Each AS-i slave has a 4-bit I/O ID, which is stored in parameters 0x90 to 0x97 (these parameters are read only):
Parameter | Bit | Description |
|---|---|---|
0x90 | 0 to 3 | read I/O ID, AS-i slave 0 |
4 to 7 | read I/O ID, AS-i slave 1 (1A) | |
8 to 11 | read I/O ID, AS-i slave 2 (2A) | |
12 to 15 | read I/O ID, AS-i slave 3 (3A) | |
16 to 19 | read I/O ID, AS-i slave 4 (4A) | |
20 to 23 | read I/O ID, AS-i slave 5 (5A) | |
24 to 27 | read I/O ID, AS-i slave 6 (6A) | |
28 to 31 | read I/O ID, AS-i slave 7 (7A) | |
0x91 | 0 to 3 | read I/O ID, AS-i slave 8 (8A) |
4 to 7 | read I/O ID, AS-i slave 9 (9A) | |
8 to 11 | read I/O ID, AS-i slave 10 (10A) | |
12 to 15 | read I/O ID, AS-i slave 11 (11A) | |
16 to 19 | read I/O ID, AS-i slave 12 (12A) | |
20 to 23 | read I/O ID, AS-i slave 13 (13A) | |
24 to 27 | read I/O ID, AS-i slave 14 (14A) | |
28 to 31 | read I/O ID, AS-i slave 15 (15A) | |
0x92 | 0 to 3 | read I/O ID, AS-i slave 16 (16A) |
4 to 7 | read I/O ID, AS-i slave 17 (17A) | |
8 to 11 | read I/O ID, AS-i slave 18 (18A) | |
12 to 15 | read I/O ID, AS-i slave 19 (19A) | |
16 to 19 | read I/O ID, AS-i slave 20 (20A) | |
20 to 23 | read I/O ID, AS-i slave 21 (21A) | |
24 to 27 | read I/O ID, AS-i slave 22 (22A) | |
28 to 31 | read I/O ID, AS-i slave 23 (23A) | |
0x93 | 0 to 3 | read I/O ID, AS-i slave 24 (24A) |
4 to 7 | read I/O ID, AS-i slave 25 (25A) | |
8 to 11 | read I/O ID, AS-i slave 26 (26A) | |
12 to 15 | read I/O ID, AS-i slave 27 (27A) | |
16 to 19 | read I/O ID, AS-i slave 28 (28A) | |
20 to 23 | read I/O ID, AS-i slave 29 (29A) | |
24 to 27 | read I/O ID, AS-i slave 30 (30A) | |
28 to 31 | read I/O ID, AS-i slave 31 (31A) | |
0x94 | 0 to 3 | Reserved (AS-i slave address 32 is not permitted) |
4 to 7 | read I/O ID, AS-i slave 33 (1B) | |
8 to 11 | read I/O ID, AS-i slave 34 (2B) | |
12 to 15 | read I/O ID, AS-i slave 35 (3B) | |
16 to 19 | read I/O ID, AS-i slave 36 (4B) | |
20 to 23 | read I/O ID, AS-i slave 37 (5B) | |
24 to 27 | read I/O ID, AS-i slave 38 (6B) | |
28 to 31 | read I/O ID, AS-i slave 39 (7B) | |
0x95 | 0 to 3 | read I/O ID, AS-i slave 40 (8B) |
4 to 7 | read I/O ID, AS-i slave 41 (9B) | |
8 to 11 | read I/O ID, AS-i slave 42 (10B) | |
12 to 15 | read I/O ID, AS-i slave 43 (11B) | |
16 to 19 | read I/O ID, AS-i slave 44 (12B) | |
20 to 23 | read I/O ID, AS-i slave 45 (13B) | |
24 to 27 | read I/O ID, AS-i slave 46 (14B) | |
28 to 31 | read I/O ID, AS-i slave 47 (15B) |
Parameter | Bit | Description |
|---|---|---|
0x96 | 0 to 3 | read I/O ID, AS-i slave 48 (16B) |
4 to 7 | read I/O ID, AS-i slave 49 (17B) | |
8 to 11 | read I/O ID, AS-i slave 50 (18B) | |
12 to 15 | read I/O ID, AS-i slave 51 (19B) | |
16 to 19 | read I/O ID, AS-i slave 52 (20B) | |
20 to 23 | read I/O ID, AS-i slave 53 (21B) | |
24 to 27 | read I/O ID, AS-i slave 54 (22B) | |
28 to 31 | read I/O ID, AS-i slave 55 (23B) | |
0x97 | 0 to 3 | read I/O ID, AS-i slave 56 (24B) |
4 to 7 | read I/O ID, AS-i slave 57 (25B) | |
8 to 11 | read I/O ID, AS-i slave 58 (26B) | |
12 to 15 | read I/O ID, AS-i slave 59 (27B) | |
16 to 19 | read I/O ID, AS-i slave 60 (28B) | |
20 to 23 | read I/O ID, AS-i slave 61 (29B) | |
24 to 27 | read I/O ID, AS-i slave 62 (30B) | |
28 to 31 | read I/O ID, AS-i slave 63 (31B) |
Parameters 0x98 to 0x9F: Read standard ID code (actual configuration)
Each AS-i slave has a 4-bit standard ID code, which is stored in parameters 0x98 to 0x9F (these parameters are read only):
Parameter | Bit | Description |
|---|---|---|
0x98 | 0 to 3 | read ID code, AS-i slave 0 |
4 to 7 | read ID code, AS-i slave 1 (1A) | |
8 to 11 | read ID code, AS-i slave 2 (2A) | |
12 to 15 | read ID code, AS-i slave 3 (3A) | |
16 to 19 | read ID code, AS-i slave 4 (4A) | |
20 to 23 | read ID code, AS-i slave 5 (5A) | |
24 to 27 | read ID code, AS-i slave 6 (6A) | |
28 to 31 | read ID code, AS-i slave 7 (7A) | |
0x99 | 0 to 3 | read ID code, AS-i slave 8 (8A) |
4 to 7 | read ID code, AS-i slave 9 (9A) | |
8 to 11 | read ID code, AS-i slave 10 (10A) | |
12 to 15 | read ID code, AS-i slave 11 (11A) | |
16 to 19 | read ID code, AS-i slave 12 (12A) | |
20 to 23 | read ID code, AS-i slave 13 (13A) | |
24 to 27 | read ID code, AS-i slave 14 (14A) | |
28 to 31 | read ID code, AS-i slave 15 (15A) | |
0x9A | 0 to 3 | read ID code, AS-i slave 16 (16A) |
4 to 7 | read ID code, AS-i slave 17 (17A) | |
8 to 11 | read ID code, AS-i slave 18 (18A) | |
12 to 15 | read ID code, AS-i slave 19 (19A) | |
16 to 19 | read ID code, AS-i slave 20 (20A) | |
20 to 23 | read ID code, AS-i slave 21 (21A) | |
24 to 27 | read ID code, AS-i slave 22 (22A) | |
28 to 31 | read ID code, AS-i slave 23 (23A) | |
0x9B | 0 to 3 | read ID code, AS-i slave 24 (24A) |
4 to 7 | read ID code, AS-i slave 25 (25A) | |
8 to 11 | read ID code, AS-i slave 26 (26A) | |
12 to 15 | read ID code, AS-i slave 27 (27A) | |
16 to 19 | read ID code, AS-i slave 28 (28A) | |
20 to 23 | read ID code, AS-i slave 29 (29A) | |
24 to 27 | read ID code, AS-i slave 30 (30A) | |
28 to 31 | read ID code, AS-i slave 31 (31A) |
Parameter | Bit | Description |
|---|---|---|
0x9C | 0 to 3 | Reserved (AS-i slave address 32 is not permitted) |
4 to 7 | read ID code, AS-i slave 33 (1B) | |
8 to 11 | read ID code, AS-i slave 34 (2B) | |
12 to 15 | read ID code, AS-i slave 35 (3B) | |
16 to 19 | read ID code, AS-i slave 36 (4B) | |
20 to 23 | read ID code, AS-i slave 37 (5B) | |
24 to 27 | read ID code, AS-i slave 38 (6B) | |
28 to 31 | read ID code, AS-i slave 39 (7B) | |
0x9D | 0 to 3 | read ID code, AS-i slave 40 (8B) |
4 to 7 | read ID code, AS-i slave 41 (9B) | |
8 to 11 | read ID code, AS-i slave 42 (10B) | |
12 to 15 | read ID code, AS-i slave 43 (11B) | |
16 to 19 | read ID code, AS-i slave 44 (12B) | |
20 to 23 | read ID code, AS-i slave 45 (13B) | |
24 to 27 | read ID code, AS-i slave 46 (14B) | |
28 to 31 | read ID code, AS-i slave 47 (15B) | |
0x9E | 0 to 3 | read ID code, AS-i slave 48 (16B) |
4 to 7 | read ID code, AS-i slave 49 (17B) | |
8 to 11 | read ID code, AS-i slave 50 (18B) | |
12 to 15 | read ID code, AS-i slave 51 (19B) | |
16 to 19 | read ID code, AS-i slave 52 (20B) | |
20 to 23 | read ID code, AS-i slave 53 (21B) | |
24 to 27 | read ID code, AS-i slave 54 (22B) | |
28 to 31 | read ID code, AS-i slave 55 (23B) | |
0x9F | 0 to 3 | read ID code, AS-i slave 56 (24B) |
4 to 7 | read ID code, AS-i slave 57 (25B) | |
8 to 11 | read ID code, AS-i slave 58 (26B) | |
12 to 15 | read ID code, AS-i slave 59 (27B) | |
16 to 19 | read ID code, AS-i slave 60 (28B) | |
20 to 23 | read ID code, AS-i slave 61 (29B) | |
24 to 27 | read ID code, AS-i slave 62 (30B) | |
28 to 31 | read ID code, AS-i slave 63 (31B) |
Parameters 0xA0 to 0xA7: read status
Each AS-i slave has a 4-bit status, which is stored in parameters 0xA0 to 0xA7 (these parameters are read only):
Parameter | Bit | Description |
|---|---|---|
0xA0 | 0 to 3 | Status, AS-i slave 0 |
4 to 7 | status, AS-i slave 1 (1A) | |
8 to 11 | status, AS-i slave 2 (2A) | |
12 to 15 | status, AS-i slave 3 (3A) | |
16 to 19 | status, AS-i slave 4 (4A) | |
20 to 23 | status, AS-i slave 5 (5A) | |
24 to 27 | status, AS-i slave 6 (6A) | |
28 to 31 | status, AS-i slave 7 (7A) | |
0xA1 | 0 to 3 | status, AS-i slave 8 (8A) |
4 to 7 | status, AS-i slave 9 (9A) | |
8 to 11 | status, AS-i slave 10 (10A) | |
12 to 15 | status, AS-i slave 11 (11A) | |
16 to 19 | status, AS-i slave 12 (12A) | |
20 to 23 | status, AS-i slave 13 (13A) | |
24 to 27 | status, AS-i slave 14 (14A) | |
28 to 31 | status, AS-i slave 15 (15A) |
Parameter | Bit | Description |
|---|---|---|
0xA2 | 0 to 3 | status, AS-i slave 16 (16A) |
4 to 7 | status, AS-i slave 17 (17A) | |
8 to 11 | status, AS-i slave 18 (18A) | |
12 to 15 | status, AS-i slave 19 (19A) | |
16 to 19 | status, AS-i slave 20 (20A) | |
20 to 23 | status, AS-i slave 21 (21A) | |
24 to 27 | status, AS-i slave 22 (22A) | |
28 to 31 | status, AS-i slave 23 (23A) | |
0xA3 | 0 to 3 | status, AS-i slave 24 (24A) |
4 to 7 | status, AS-i slave 25 (25A) | |
8 to 11 | status, AS-i slave 26 (26A) | |
12 to 15 | status, AS-i slave 27 (27A) | |
16 to 19 | status, AS-i slave 28 (28A) | |
20 to 23 | status, AS-i slave 29 (29A) | |
24 to 27 | status, AS-i slave 30 (30A) | |
28 to 31 | status, AS-i slave 31 (31A) | |
0xA4 | 0 to 3 | Reserved (AS-i slave address 32 is not permitted) |
4 to 7 | Status, AS-i slave 33 (1B) | |
8 to 11 | Status, AS-i slave 34 (2B) | |
12 to 15 | Status, AS-i slave 35 (3B) | |
16 to 19 | Status, AS-i slave 36 (4B) | |
20 to 23 | Status, AS-i slave 37 (5B) | |
24 to 27 | Status, AS-i slave 38 (6B) | |
28 to 31 | Status, AS-i slave 39 (7B) | |
0xA5 | 0 to 3 | Status, AS-i slave 40 (8B) |
4 to 7 | Status, AS-i slave 41 (9B) | |
8 to 11 | Status, AS-i slave 42 (10B) | |
12 to 15 | Status, AS-i slave 43 (11B) | |
16 to 19 | Status, AS-i slave 44 (12B) | |
20 to 23 | Status, AS-i slave 45 (13B) | |
24 to 27 | Status, AS-i slave 46 (14B) | |
28 to 31 | Status, AS-i slave 47 (15B) | |
0xA6 | 0 to 3 | Status, AS-i slave 48 (16B) |
4 to 7 | Status, AS-i slave 49 (17B) | |
8 to 11 | Status, AS-i slave 50 (18B) | |
12 to 15 | Status, AS-i slave 51 (19B) | |
16 to 19 | Status, AS-i slave 52 (20B) | |
20 to 23 | Status, AS-i slave 53 (21B) | |
24 to 27 | Status, AS-i slave 54 (22B) | |
28 to 31 | Status, AS-i slave 55 (23B) | |
0xA7 | 0 to 3 | Status, AS-i slave 56 (24B) |
4 to 7 | Status, AS-i slave 57 (25B) | |
8 to 11 | Status, AS-i slave 58 (26B) | |
12 to 15 | Status, AS-i slave 59 (27B) | |
16 to 19 | Status, AS-i slave 60 (28B) | |
20 to 23 | Status, AS-i slave 61 (29B) | |
24 to 27 | Status, AS-i slave 62 (30B) | |
28 to 31 | Status, AS-i slave 63 (31B) |
Parameters 0xA8 and 0xA9: List of currently projected AS-i slaves (LPS)
This list contains the currently projected AS-i slaves. As soon as at least one AS-i slave from this list is projected, the AS-i master is in protected mode. This list is only updated during the transition from the offline phase to the detection phase, with the list of the AS-i slaves projected at the next start being read. For each AS-i slave, parameters 0xA8 and 0xA9 contain a bit that indicates whether the respective AS-i slave is projected (this parameter is read only):
Parameter | Bit | Description |
|---|---|---|
0xA8 | 0 | reserved |
1 | 0bin: AS-i slave 1 (1A) is not projected | |
... | ... | |
31 | 0bin: AS-i slave 31 (31A) is not projected | |
0xA9 | 0 | reserved |
1 | 0bin: AS-i slave 33 (1B) is not projected | |
... | ... | |
31 | 0bin: AS-i slave 63 (31B) is not projected |
Parameters 0xB0 and 0xB1: List of currently detected AS-i slaves (LDS)
This list contains the AS-i slaves that are currently detected at the bus. For each AS-i slave, parameters 0xB0 and 0xB1 contain a bit that indicates whether the respective AS-i slave was detected (this parameter is read only):
Parameter | Bit | Description |
|---|---|---|
0xB0 | 0 | reserved |
1 | 0bin: AS-i slave 1 (1A) was not detected | |
... | ... | |
31 | 0bin: AS-i slave 31 (31A) was not detected | |
0xB1 | 0 | reserved |
1 | 0bin: AS-i slave 33 (1B) was not detected | |
... | ... | |
31 | 0bin: AS-i slave 63 (31B) was not detected |
Parameters 0xC0 and 0xC1: List of slaves that support the extended ID codes (ID codes 1 and 2)
Parameter | Bit | Description |
|---|---|---|
0xC0 | 0 | Slave 0 supports extended ID codes |
1 | Slave 1 (1A) supports extended ID codes | |
... | ... | |
31 | Slave 31 (31A) supports extended ID codes | |
0xC1 | 0 | free |
1 | Slave 1 (1A) supports extended ID codes | |
... | ... | |
31 | Slave 31 (31A) supports extended ID codes |
Parameter 0xC8: List of slaves that support extended addressing (as B slaves with addresses greater than 32)
Parameter | Bit | Description |
|---|---|---|
0xC8 | 0 | Slave 0 supports extended addressing |
1 | Slave 1 (1A) supports extended addressing | |
... | ... | |
31 | Slave 31 (31A) supports extended addressing |
Parameters 0xB8 and 0xB9: List of activated AS-i slaves (LAS)
This list contains the AS-i slaves that are currently activated on the bus. In projecting mode, all detected AS-i slaves are activated. In protected mode, only those projected AS-i slaves with matching ID code and I/O ID in the actual and set configuration are activated. For each AS-i slave, parameters 0xB8 and 0xB9 contain a bit that indicates whether the respective AS-i slave was activated (this parameter is read only):
Parameter | Bit | Description |
|---|---|---|
0xB8 | 0 | reserved |
1 | 0bin: AS-i slave 1 (1A) was not activated | |
... | ... | |
31 | 0bin: AS-i slave 31 (31A) was not activated | |
0xB9 | 0 | reserved |
1 | 0bin: AS-i slave 33 (1B) was not activated | |
... | ... | |
31 | 0bin: AS-i slave 63 (31B) was not activated |
Parameters 0xD0 to 0xD7: Read extended ID code 1 (actual configuration)
AS-i slaves optionally have a 4-bit extended ID code 1, which is stored in parameters 0xD0 to 0xD7 (these parameters are read only):
Parameter | Bit | Description |
|---|---|---|
0xD0 | 0 to 3 | read extended ID code 1, AS-i slave 0 |
4 to 7 | read extended ID code 1, AS-i slave 1 (1A) | |
8 to 11 | read extended ID code 1, AS-i slave 2 (2A) | |
12 to 15 | read extended ID code 1, AS-i slave 3 (3A) | |
16 to 19 | read extended ID code 1, AS-i slave 4 (4A) | |
20 to 23 | read extended ID code 1, AS-i slave 5 (5A) | |
24 to 27 | read extended ID code 1, AS-i slave 6 (6A) | |
28 to 31 | read extended ID code 1, AS-i slave 7 (7A) | |
0xD1 | 0 to 3 | read extended ID code 1, AS-i slave 8 (8A) |
4 to 7 | read extended ID code 1, AS-i slave 9 (9A) | |
8 to 11 | read extended ID code 1, AS-i slave 10 (10A) | |
12 to 15 | read extended ID code 1, AS-i slave 11 (11A) | |
16 to 19 | read extended ID code 1, AS-i slave 12 (12A) | |
20 to 23 | read extended ID code 1, AS-i slave 13 (13A) | |
24 to 27 | read extended ID code 1, AS-i slave 14 (14A) | |
28 to 31 | read extended ID code 1, AS-i slave 15 (15A) | |
0xD2 | 0 to 3 | read extended ID code 1, AS-i slave 16 (16A) |
4 to 7 | read extended ID code 1, AS-i slave 17 (17A) | |
8 to 11 | read extended ID code 1, AS-i slave 18 (18A) | |
12 to 15 | read extended ID code 1, AS-i slave 19 (19A) | |
16 to 19 | read extended ID code 1, AS-i slave 20 (20A) | |
20 to 23 | read extended ID code 1, AS-i slave 21 (21A) | |
24 to 27 | read extended ID code 1, AS-i slave 22 (22A) | |
28 to 31 | read extended ID code 1, AS-i slave 23 (23A) | |
0xD3 | 0 to 3 | read extended ID code 1, AS-i slave 24 (24A) |
4 to 7 | read extended ID code 1, AS-i slave 25 (25A) | |
8 to 11 | read extended ID code 1, AS-i slave 26 (26A) | |
12 to 15 | read extended ID code 1, AS-i slave 27 (27A) | |
16 to 19 | read extended ID code 1, AS-i slave 28 (28A) | |
20 to 23 | read extended ID code 1, AS-i slave 29 (29A) | |
24 to 27 | read extended ID code 1, AS-i slave 30 (30A) | |
28 to 31 | read extended ID code 1, AS-i slave 31 (31A) |
Parameter | Bit | Description |
|---|---|---|
0xD4 | 0 to 3 | Reserved (AS-i slave address 32 is not permitted) |
4 to 7 | read extended ID code 1, AS-i slave 33 (1B) | |
8 to 11 | read extended ID code 1, AS-i slave 34 (2B) | |
12 to 15 | read extended ID code 1, AS-i slave 35 (3B) | |
16 to 19 | read extended ID code 1, AS-i slave 36 (4B) | |
20 to 23 | read extended ID code 1, AS-i slave 37 (5B) | |
24 to 27 | read extended ID code 1, AS-i slave 38 (6B) | |
28 to 31 | read extended ID code 1, AS-i slave 39 (7B) | |
0xD5 | 0 to 3 | read extended ID code 1, AS-i slave 40 (8B) |
4 to 7 | read extended ID code 1, AS-i slave 41 (9B) | |
8 to 11 | read extended ID code 1, AS-i slave 42 (10B) | |
12 to 15 | read extended ID code 1, AS-i slave 43 (11B) | |
16 to 19 | read extended ID code 1, AS-i slave 44 (12B) | |
20 to 23 | read extended ID code 1, AS-i slave 45 (13B) | |
24 to 27 | read extended ID code 1, AS-i slave 46 (14B) | |
28 to 31 | read extended ID code 1, AS-i slave 47 (15B) | |
0xD6 | 0 to 3 | read extended ID code 1, AS-i slave 48 (16B) |
4 to 7 | read extended ID code 1, AS-i slave 49 (17B) | |
8 to 11 | read extended ID code 1, AS-i slave 50 (18B) | |
12 to 15 | read extended ID code 1, AS-i slave 51 (19B) | |
16 to 19 | read extended ID code 1, AS-i slave 52 (20B) | |
20 to 23 | read extended ID code 1, AS-i slave 53 (21B) | |
24 to 27 | read extended ID code 1, AS-i slave 54 (22B) | |
28 to 31 | read extended ID code 1, AS-i slave 55 (23B) | |
0xD7 | 0 to 3 | read extended ID code 1, AS-i slave 56 (24B) |
4 to 7 | read extended ID code 1, AS-i slave 57 (25B) | |
8 to 11 | read extended ID code 1, AS-i slave 58 (26B) | |
12 to 15 | read extended ID code 1, AS-i slave 59 (27B) | |
16 to 19 | read extended ID code 1, AS-i slave 60 (28B) | |
20 to 23 | read extended ID code 1, AS-i slave 61 (29B) | |
24 to 27 | read extended ID code 1, AS-i slave 62 (30B) | |
28 to 31 | read extended ID code 1, AS-i slave 63 (31B) |
Parameters 0xD8 to 0xDF: Read extended ID code 2 (actual configuration)
AS-i slaves optionally have a 4-bit extended ID code 2, which is stored in parameters 0xD8 to 0xDF (these parameters are read only):
Parameter | Bit | Description |
|---|---|---|
0xD8 | 0 to 3 | read extended ID code 2, AS-i slave 0 |
4 to 7 | read extended ID code 2, AS-i slave 1 (1A) | |
8 to 11 | read extended ID code 2, AS-i slave 2 (2A) | |
12 to 15 | read extended ID code 2, AS-i slave 3 (3A) | |
16 to 19 | read extended ID code 2, AS-i slave 4 (4A) | |
20 to 23 | read extended ID code 2, AS-i slave 5 (5A) | |
24 to 27 | read extended ID code 2, AS-i slave 6 (6A) | |
28 to 31 | read extended ID code 2, AS-i slave 7 (7A) | |
0xD9 | 0 to 3 | read extended ID code 2, AS-i slave 8 (8A) |
4 to 7 | read extended ID code 2, AS-i slave 9 (9A) | |
8 to 11 | read extended ID code 2, AS-i slave 10 (10A) | |
12 to 15 | read extended ID code 2, AS-i slave 11 (11A) | |
16 to 19 | read extended ID code 2, AS-i slave 12 (12A) | |
20 to 23 | read extended ID code 2, AS-i slave 13 (13A) | |
24 to 27 | read extended ID code 2, AS-i slave 14 (14A) | |
28 to 31 | read extended ID code 2, AS-i slave 15 (15A) |
Parameter | Bit | Description |
|---|---|---|
0xDA | 0 to 3 | read extended ID code 2, AS-i slave 16 (16A) |
4 to 7 | read extended ID code 2, AS-i slave 17 (17A) | |
8 to 11 | read extended ID code 2, AS-i slave 18 (18A) | |
12 to 15 | read extended ID code 2, AS-i slave 19 (19A) | |
16 to 19 | read extended ID code 2, AS-i slave 20 (20A) | |
20 to 23 | read extended ID code 2, AS-i slave 21 (21A) | |
24 to 27 | read extended ID code 2, AS-i slave 22 (22A) | |
28 to 31 | read extended ID code 2, AS-i slave 23 (23A) | |
0xDB | 0 to 3 | read extended ID code 2, AS-i slave 24 (24A) |
4 to 7 | read extended ID code 2, AS-i slave 25 (25A) | |
8 to 11 | read extended ID code 2, AS-i slave 26 (26A) | |
12 to 15 | read extended ID code 2, AS-i slave 27 (27A) | |
16 to 19 | read extended ID code 2, AS-i slave 28 (28A) | |
20 to 23 | read extended ID code 2, AS-i slave 29 (29A) | |
24 to 27 | read extended ID code 2, AS-i slave 30 (30A) | |
28 to 31 | read extended ID code 2, AS-i slave 31 (31A) | |
0xDC | 0 to 3 | Reserved (AS-i slave address 32 is not permitted) |
4 to 7 | read extended ID code 2, AS-i slave 33 (1B) | |
8 to 11 | read extended ID code 2, AS-i slave 34 (2B) | |
12 to 15 | read extended ID code 2, AS-i slave 35 (3B) | |
16 to 19 | read extended ID code 2, AS-i slave 36 (4B) | |
20 to 23 | read extended ID code 2, AS-i slave 37 (5B) | |
24 to 27 | read extended ID code 2, AS-i slave 38 (6B) | |
28 to 31 | read extended ID code 2, AS-i slave 39 (7B) | |
0xDD | 0 to 3 | read extended ID code 2, AS-i slave 40 (8B) |
4 to 7 | read extended ID code 2, AS-i slave 41 (9B) | |
8 to 11 | read extended ID code 2, AS-i slave 42 (10B) | |
12 to 15 | read extended ID code 2, AS-i slave 43 (11B) | |
16 to 19 | read extended ID code 2, AS-i slave 44 (12B) | |
20 to 23 | read extended ID code 2, AS-i slave 45 (13B) | |
24 to 27 | read extended ID code 2, AS-i slave 46 (14B) | |
28 to 31 | read extended ID code 2, AS-i slave 47 (15B) | |
0xDE | 0 to 3 | read extended ID code 2, AS-i slave 48 (16B) |
4 to 7 | read extended ID code 2, AS-i slave 49 (17B) | |
8 to 11 | read extended ID code 2, AS-i slave 50 (18B) | |
12 to 15 | read extended ID code 2, AS-i slave 51 (19B) | |
16 to 19 | read extended ID code 2, AS-i slave 52 (20B) | |
20 to 23 | read extended ID code 2, AS-i slave 53 (21B) | |
24 to 27 | read extended ID code 2, AS-i slave 54 (22B) | |
28 to 31 | read extended ID code 2, AS-i slave 55 (23B) | |
0xDF | 0 to 3 | read extended ID code 2, AS-i slave 56 (24B) |
4 to 7 | read extended ID code 2, AS-i slave 57 (25B) | |
8 to 11 | read extended ID code 2, AS-i slave 58 (26B) | |
12 to 15 | read extended ID code 2, AS-i slave 59 (27B) | |
16 to 19 | read extended ID code 2, AS-i slave 60 (28B) | |
20 to 23 | read extended ID code 2, AS-i slave 61 (29B) | |
24 to 27 | read extended ID code 2, AS-i slave 62 (30B) | |
28 to 31 | read extended ID code 2, AS-i slave 63 (31B) |
Parameters 0xE0 to 0xE7: Projected extended ID code 1 (nominal configuration)
In protected mode, the extended ID code 1 of the currently projected AS-i slaves is checked. The currently projected 4-bit extended ID codes 1 of the AS-i slaves are located in parameters 0xE0 to 0xE7 (these parameters are read/write and are stored in the flash of the AS-i master (i.e. they are still available after power off/on)):
Parameter | Bit | Description |
|---|---|---|
0xE0 | 0 to 3 | reserved |
4 to 7 | projected extended ID code 1, AS-i slave 1 (1A) | |
8 to 11 | projected extended ID code 1, AS-i slave 2 (2A) | |
12 to 15 | projected extended ID code 1, AS-i slave 3 (3A) | |
16 to 19 | projected extended ID code 1, AS-i slave 4 (4A) | |
20 to 23 | projected extended ID code 1, AS-i slave 5 (5A) | |
24 to 27 | projected extended ID code 1, AS-i slave 6 (6A) | |
28 to 31 | projected extended ID code 1, AS-i slave 7 (7A) | |
0xE1 | 0 to 3 | projected extended ID code 1, AS-i slave 8 (8A) |
4 to 7 | projected extended ID code 1, AS-i slave 9 (9A) | |
8 to 11 | projected extended ID code 1, AS-i slave 10 (10A) | |
12 to 15 | projected extended ID code 1, AS-i slave 11 (11A) | |
16 to 19 | projected extended ID code 1, AS-i slave 12 (12A) | |
20 to 23 | projected extended ID code 1, AS-i slave 13 (13A) | |
24 to 27 | projected extended ID code 1, AS-i slave 14 (14A) | |
28 to 31 | projected extended ID code 1, AS-i slave 15 (15A) | |
0xE2 | 0 to 3 | projected extended ID code 1, AS-i slave 16 (16A) |
4 to 7 | projected extended ID code 1, AS-i slave 17 (17A) | |
8 to 11 | projected extended ID code 1, AS-i slave 18 (18A) | |
12 to 15 | projected extended ID code 1, AS-i slave 19 (19A) | |
16 to 19 | projected extended ID code 1, AS-i slave 20 (20A) | |
20 to 23 | projected extended ID code 1, AS-i slave 21 (21A) | |
24 to 27 | projected extended ID code 1, AS-i slave 22 (22A) | |
28 to 31 | projected extended ID code 1, AS-i slave 23 (23A) | |
0xE3 | 0 to 3 | projected extended ID code 1, AS-i slave 24 (24A) |
4 to 7 | projected extended ID code 1, AS-i slave 25 (25A) | |
8 to 11 | projected extended ID code 1, AS-i slave 26 (26A) | |
12 to 15 | projected extended ID code 1, AS-i slave 27 (27A) | |
16 to 19 | projected extended ID code 1, AS-i slave 28 (28A) | |
20 to 23 | projected extended ID code 1, AS-i slave 29 (29A) | |
24 to 27 | projected extended ID code 1, AS-i slave 30 (30A) | |
28 to 31 | projected extended ID code 1, AS-i slave 31 (31A) | |
0xE4 | 0 to 3 | Reserved (AS-i slave address 32 is not permitted) |
4 to 7 | projected extended ID code 1, AS-i slave 33 (1B) | |
8 to 11 | projected extended ID code 1, AS-i slave 34 (2B) | |
12 to 15 | projected extended ID code 1, AS-i slave 35 (3B) | |
16 to 19 | projected extended ID code 1, AS-i slave 36 (4B) | |
20 to 23 | projected extended ID code 1, AS-i slave 37 (5B) | |
24 to 27 | projected extended ID code 1, AS-i slave 38 (6B) | |
28 to 31 | projected extended ID code 1, AS-i slave 39 (7B) | |
0xE5 | 0 to 3 | projected extended ID code 1, AS-i slave 40 (8B) |
4 to 7 | projected extended ID code 1, AS-i slave 41 (9B) | |
8 to 11 | projected extended ID code 1, AS-i slave 42 (10B) | |
12 to 15 | projected extended ID code 1, AS-i slave 43 (11B) | |
16 to 19 | projected extended ID code 1, AS-i slave 44 (12B) | |
20 to 23 | projected extended ID code 1, AS-i slave 45 (13B) | |
24 to 27 | projected extended ID code 1, AS-i slave 46 (14B) | |
28 to 31 | projected extended ID code 1, AS-i slave 47 (15B) |
Parameter | Bit | Description |
|---|---|---|
0xE6 | 0 to 3 | projected extended ID code 1, AS-i slave 48 (16B) |
4 to 7 | projected extended ID code 1, AS-i slave 49 (17B) | |
8 to 11 | projected extended ID code 1, AS-i slave 50 (18B) | |
12 to 15 | projected extended ID code 1, AS-i slave 51 (19B) | |
16 to 19 | projected extended ID code 1, AS-i slave 52 (20B) | |
20 to 23 | projected extended ID code 1, AS-i slave 53 (21B) | |
24 to 27 | projected extended ID code 1, AS-i slave 54 (22B) | |
28 to 31 | projected extended ID code 1, AS-i slave 55 (23B) | |
0xE7 | 0 to 3 | projected extended ID code 1, AS-i slave 56 (24B) |
4 to 7 | projected extended ID code 1, AS-i slave 57 (25B) | |
8 to 11 | projected extended ID code 1, AS-i slave 58 (26B) | |
12 to 15 | projected extended ID code 1, AS-i slave 59 (27B) | |
16 to 19 | projected extended ID code 1, AS-i slave 60 (28B) | |
20 to 23 | projected extended ID code 1, AS-i slave 61 (29B) | |
24 to 27 | projected extended ID code 1, AS-i slave 62 (30B) | |
28 to 31 | projected extended ID code 1, AS-i slave 63 (31B) |
Parameters 0xE8 to 0xEF: Projected extended ID code 2 (nominal configuration)
In protected mode, the extended ID code 2 of the currently projected AS-i slaves is checked. The currently projected 4-bit ID codes of the AS-i slaves are located in parameters 0xE8 to 0xEF (these parameters are read/write and are stored in the flash of the AS-i master (i.e. they are still available after power off/on)):
Parameter | Bit | Description |
|---|---|---|
0xE8 | 0 to 3 | reserved |
4 to 7 | projected extended ID code 2, AS-i slave 1 (1A) | |
8 to 11 | projected extended ID code 2, AS-i slave 2 (2A) | |
12 to 15 | projected extended ID code 2, AS-i slave 3 (3A) | |
16 to 19 | projected extended ID code 2, AS-i slave 4 (4A) | |
20 to 23 | projected extended ID code 2, AS-i slave 5 (5A) | |
24 to 27 | projected extended ID code 2, AS-i slave 6 (6A) | |
28 to 31 | projected extended ID code 2, AS-i slave 7 (7A) | |
0xE9 | 0 to 3 | projected extended ID code 2, AS-i slave 8 (8A) |
4 to 7 | projected extended ID code 2, AS-i slave 9 (9A) | |
8 to 11 | projected extended ID code 2, AS-i slave 10 (10A) | |
12 to 15 | projected extended ID code 2, AS-i slave 11 (11A) | |
16 to 19 | projected extended ID code 2, AS-i slave 12 (12A) | |
20 to 23 | projected extended ID code 2, AS-i slave 13 (13A) | |
24 to 27 | projected extended ID code 2, AS-i slave 14 (14A) | |
28 to 31 | projected extended ID code 2, AS-i slave 15 (15A) | |
0xE/A | 0 to 3 | projected extended ID code 2, AS-i slave 16 (16A) |
4 to 7 | projected extended ID code 2, AS-i slave 17 (17A) | |
8 to 11 | projected extended ID code 2, AS-i slave 18 (18A) | |
12 to 15 | projected extended ID code 2, AS-i slave 19 (19A) | |
16 to 19 | projected extended ID code 2, AS-i slave 20 (20A) | |
20 to 23 | projected extended ID code 2, AS-i slave 21 (21A) | |
24 to 27 | projected extended ID code 2, AS-i slave 22 (22A) | |
28 to 31 | projected extended ID code 2, AS-i slave 23 (23A) | |
0xEB | 0 to 3 | projected extended ID code 2, AS-i slave 24 (24A) |
4 to 7 | projected extended ID code 2, AS-i slave 25 (25A) | |
8 to 11 | projected extended ID code 2, AS-i slave 26 (26A) | |
12 to 15 | projected extended ID code 2, AS-i slave 27 (27A) | |
16 to 19 | projected extended ID code 2, AS-i slave 28 (28A) | |
20 to 23 | projected extended ID code 2, AS-i slave 29 (29A) | |
24 to 27 | projected extended ID code 2, AS-i slave 30 (30A) | |
28 to 31 | projected extended ID code 2, AS-i slave 31 (31A) |
Parameter | Bit | Description |
|---|---|---|
0xEC | 0 to 3 | Reserved (AS-i slave address 32 is not permitted) |
4 to 7 | projected extended ID code 2, AS-i slave 33 (1B) | |
8 to 11 | projected extended ID code 2, AS-i slave 34 (2B) | |
12 to 15 | projected extended ID code 2, AS-i slave 35 (3B) | |
16 to 19 | projected extended ID code 2, AS-i slave 36 (4B) | |
20 to 23 | projected extended ID code 2, AS-i slave 37 (5B) | |
24 to 27 | projected extended ID code 2, AS-i slave 38 (6B) | |
28 to 31 | projected extended ID code 2, AS-i slave 39 (7B) | |
0xED | 0 to 3 | projected extended ID code 2, AS-i slave 40 (8B) |
4 to 7 | projected extended ID code 2, AS-i slave 41 (9B) | |
8 to 11 | projected extended ID code 2, AS-i slave 42 (10B) | |
12 to 15 | projected extended ID code 2, AS-i slave 43 (11B) | |
16 to 19 | projected extended ID code 2, AS-i slave 44 (12B) | |
20 to 23 | projected extended ID code 2, AS-i slave 45 (13B) | |
24 to 27 | projected extended ID code 2, AS-i slave 46 (14B) | |
28 to 31 | projected extended ID code 2, AS-i slave 47 (15B) | |
0xEE | 0 to 3 | projected extended ID code 2, AS-i slave 48 (16B) |
4 to 7 | projected extended ID code 2, AS-i slave 49 (17B) | |
8 to 11 | projected extended ID code 2, AS-i slave 50 (18B) | |
12 to 15 | projected extended ID code 2, AS-i slave 51 (19B) | |
16 to 19 | projected extended ID code 2, AS-i slave 52 (20B) | |
20 to 23 | projected extended ID code 2, AS-i slave 53 (21B) | |
24 to 27 | projected extended ID code 2, AS-i slave 54 (22B) | |
28 to 31 | projected extended ID code 2, AS-i slave 55 (23B) | |
0xEF | 0 to 3 | projected extended ID code 2, AS-i slave 56 (24B) |
4 to 7 | projected extended ID code 2, AS-i slave 57 (25B) | |
8 to 11 | projected extended ID code 2, AS-i slave 58 (26B) | |
12 to 15 | projected extended ID code 2, AS-i slave 59 (27B) | |
16 to 19 | projected extended ID code 2, AS-i slave 60 (28B) | |
20 to 23 | projected extended ID code 2, AS-i slave 61 (29B) | |
24 to 27 | projected extended ID code 2, AS-i slave 62 (30B) | |
28 to 31 | projected extended ID code 2, AS-i slave 63 (31B) |
Parameter 0xF0: List of analog slaves
(only up to address 31, because analog slaves do not support extended addressing)
Parameter | Bit | Description |
|---|---|---|
0xF0 | 0 | Slave 0 is an analog slave |
1 | Slave 1 is an analog slave | |
... | ... | |
31 | Slave 31 is an analog slave |
Parameter 0xF8: List of safety slaves
(only up to address 31, because safety slaves do not support extended addressing)
Parameter | Bit | Description |
|---|---|---|
0xF8 | 0 | Slave 0 is a safety slave |
1 | Slave 1 is a safety slave | |
... | ... | |
31 | Slave 31 is a safety slave |
Parameter 0x100: AS-i command interface
Commands can be sent to the AS-i slaves via parameter 0x100. This is possible both during the offline phase (no other commands on the AS-i bus) and during the management phase. During the management phase, only non-activated AS-i slaves can be addressed (this parameter is write only).
Parameter | Bit | Value | Description |
|---|---|---|---|
0x100 | 0 to 7 | 0 to 255 | must be unequal 0 in order for the command to be sent |
8 to 15 | 1 | ASI command for reading ID code | |
2 | ASI command for reading the EA ID | ||
3 | ASI command for reading the status | ||
4 | AS-i command write parameter | ||
5 | ASI command for data exchange | ||
6 | ASI command for resetting an ASI slave | ||
7 | AS-i command addressing call | ||
8 | AS-i command Delete operating address | ||
16 to 23 | 0 to 31 | Address of the AS-i slave for which the command is intended | |
24 to 31 | 0 to 31 | AS-i command data:
|
Acknowledge
If AS-i parameter 0x100 is written to the KL6201/KL6211 via register communication, the following information is returned as acknowledgement:
Parameter | Bit | Description | |
|---|---|---|---|
Acknowledgement to 0x100 | 7 to 0 | always 0 | |
14 to 8 | Corresponding to bits 0 to 14 of the command call. | ||
15 | Error bit: If bit 15 is set, an error occurred during command execution, and an error code is issued in bits 31 to 24! | ||
23 to 16 | Address of the AS-i slave to which the command was sent. | ||
31 to 24 | Acknowledgement of the AS-i command for parameter writing (bit 4 of the AS-i commands was set): Bits 31 to 24 return the data transferred when the AS-i command was called (bits 31 to 24 of the AS-i command). Acknowledgement of the AS-i command for addressing call (bit 7 of the AS-i command was set):addressing call If the error bit (bit 15) is not set, bits 31 to 24 contain the value 00hex. If the error bit (bit 15) is set, bits 31 to 24 contain an error code. This error code is also issued if AS-i addresses are modified via the KS2000 configuration software. | ||
0x00 | Address modification was successful. | ||
0x11 | No slave exists with an address that was specified as the old address. | ||
0x22 | Address 0 is currently assigned to another slave. | ||
0x36 | A slave with the address that was specified as the new address already exists. | ||
0x47 | After deleting the old address, no slave with address 0 exists. | ||
0x58 | After deleting the old address, an error is generated during reading of the extended ID code 1 of slave 0. | ||
0x69 | After writing of extended ID code 1, no slave with address 0 exists. | ||
0x6B | After writing of the new address, the slave with the new address is not available during reading of the ID code. | ||
0x6C | After writing of the new address, the slave with the new address is not available during reading of the status. | ||
0x7D | The address could not be saved permanently (non-volatile). | ||
0x7E | The extended ID code of an A/B slave could not be saved permanently (non-volatile). | ||
0x7F | ID code 1 is invalid for A/B slaves | ||
0x83 | The new address is a B address. | ||
0x84 | The new address is a B address. The slave selected with the old address is not an A/B slave, i.e. it does not support the B addresses (33 to 63). | ||
0x85 | The new address is an A address. Slave is not an A/B slave: the associated B slave for the new address exists. | ||
Parameter 0x108: General command interface
Parameter 0x108 can be used to execute general commands (this parameter is write only):
Parameter | Bit | Value | Description |
|---|---|---|---|
0x108 | 0 to 15 | 0x0210 | The detected AS-i slaves are automatically projected (all AS-i slaves from the LDS are entered in the LPS, including read ID codes and I/O IDs) |
16 to 31 | 0 | reserved | |
0x108 | 0 to 15 | 0x0301 | Specifies which data exchange repeat counter is addressed via parameters 0x340 to 0x35F. |
16 to 24 | 0x01 | Repeat counter for one repetition of the data exchange telegram | |
0x02 | Repeat counter for two repetitions of the data exchange telegram | ||
0x03 | Repeat counter for three repetitions of the data exchange telegram | ||
0x04 | Repeat counter for four repetitions of the data exchange telegram | ||
0x05 | Repeat counter for five repetitions of the data exchange telegram | ||
25 to 31 | 0 | reserved | |
0x108 | 0 to 15 | 0x0C00 | Initialization of the string transfer to slave profile 7.4 |
0x0C10 | Command Read_ID_String | ||
0x0C20 | Command Read_Diagnosis_String | ||
0x0C30 | Command Read_Parameter_String | ||
0x0C40 | Command Write_Parameter_String | ||
16 to 23 | 0...62 | Slave address | |
24 to 31 | 0 | reserved |
Parameters 0x120 to 0x12F: General status information
Parameter 0x120 ff contains general status information for the KL6201/KL6211 and the connected AS-i network.
Parameter | Bit | Description |
|---|---|---|
0x120 | 0 to 15 | Startup status (0: no error) |
16 to 31 | Status of automatic project configuration (0: no error) | |
0x121 to 0x127 | in each case 0 to 31 | reserved |
0x128 to 0x12F | in each case 0 to 31 | reserved |
Parameters 0x140 to 0x15F: Physical fault counter
Each AS-i slave has a counter that is incremented if a response from the associated AS-i slave had a start bit, stop bit or parity bit error (this parameter is read/write):
Parameter | Bit | Description |
|---|---|---|
0x140 | 0 to 15 | Physical fault counter, AS-i slave 0 |
16 to 31 | Physical fault counter, AS-i slave 1 (1A) | |
0x141 | 0 to 15 | Physical fault counter, AS-i slave 2 (2A) |
16 to 31 | Physical fault counter, AS-i slave 3 (3A) | |
0x142 | 0 to 15 | Physical fault counter, AS-i slave 4 (4A) |
16 to 31 | Physical fault counter, AS-i slave 5 (5A) | |
0x143 | 0 to 15 | Physical fault counter, AS-i slave 6 (6A) |
16 to 31 | Physical fault counter, AS-i slave 7 (7A) | |
0x144 | 0 to 15 | Physical fault counter, AS-i slave 8 (8A) |
16 to 31 | Physical fault counter, AS-i slave 9 (9A) | |
0x145 | 0 to 15 | Physical fault counter, AS-i slave 10 (10A) |
16 to 31 | Physical fault counter, AS-i slave 11 (11A) | |
0x146 | 0 to 15 | Physical fault counter, AS-i slave 12 (12A) |
16 to 31 | Physical fault counter, AS-i slave 13 (13A) | |
0x147 | 0 to 15 | Physical fault counter, AS-i slave 14 (14A) |
16 to 31 | Physical fault counter, AS-i slave 15 (15A) | |
0x148 | 0 to 15 | Physical fault counter, AS-i slave 16 (16A) |
16 to 31 | Physical fault counter, AS-i slave 17 (17A) |
Parameter | Bit | Description |
|---|---|---|
0x149 | 0 to 15 | Physical fault counter, AS-i slave 18 (18A) |
16 to 31 | Physical fault counter, AS-i slave 19 (19A) | |
0x14A | 0 to 15 | Physical fault counter, AS-i slave 20 (20A) |
16 to 31 | Physical fault counter, AS-i slave 21 (21A) | |
0x14B | 0 to 15 | Physical fault counter, AS-i slave 22 (22A) |
16 to 31 | Physical fault counter, AS-i slave 23 (23A) | |
0x14C | 0 to 15 | Physical fault counter, AS-i slave 24 (24A) |
16 to 31 | Physical fault counter, AS-i slave 25 (25A) | |
0x14D | 0 to 15 | Physical fault counter, AS-i slave 26 (26A) |
16 to 31 | Physical fault counter, AS-i slave 27 (27A) | |
0x14E | 0 to 15 | Physical fault counter, AS-i slave 28 (28A) |
16 to 31 | Physical fault counter, AS-i slave 29 (29A) | |
0x14F | 0 to 15 | Physical fault counter, AS-i slave 30 (30A) |
16 to 31 | Physical fault counter, AS-i slave 31 (31A) | |
0x150 | 0 to 15 | Reserved (AS-i slave address 32 is not permitted) |
16 to 31 | Physical fault counter, AS-i slave 33 (1A) | |
0x151 | 0 to 15 | Physical fault counter, AS-i slave 34 (2A) |
16 to 31 | Physical fault counter, AS-i slave 35 (3A) | |
0x152 | 0 to 15 | Physical fault counter, AS-i slave 36 (4A) |
16 to 31 | Physical fault counter, AS-i slave 37 (5A) | |
0x153 | 0 to 15 | Physical fault counter, AS-i slave 38 (6A) |
16 to 31 | Physical fault counter, AS-i slave 39 (7A) | |
0x154 | 0 to 15 | Physical fault counter, AS-i slave 40 (8A) |
16 to 31 | Physical fault counter, AS-i slave 41 (9A) | |
0x155 | 0 to 15 | Physical fault counter, AS-i slave 42 (10A) |
16 to 31 | Physical fault counter, AS-i slave 43 (11A) | |
0x156 | 0 to 15 | Physical fault counter, AS-i slave 44 (12A) |
16 to 31 | Physical fault counter, AS-i slave 45 (13A) | |
0x157 | 0 to 15 | Physical fault counter, AS-i slave 46 (14A) |
16 to 31 | Physical fault counter, AS-i slave 47 (15A) | |
0x158 | 0 to 15 | Physical fault counter, AS-i slave 48 (16A) |
16 to 31 | Physical fault counter, AS-i slave 49 (17A) | |
0x159 | 0 to 15 | Physical fault counter, AS-i slave 50 (18A) |
16 to 31 | Physical fault counter, AS-i slave 51 (19A) | |
0x15A | 0 to 15 | Physical fault counter, AS-i slave 52 (20A) |
16 to 31 | Physical fault counter, AS-i slave 53 (21A) | |
0x15B | 0 to 15 | Physical fault counter, AS-i slave 54 (22A) |
16 to 31 | Physical fault counter, AS-i slave 55 (23A) | |
0x15C | 0 to 15 | Physical fault counter, AS-i slave 56 (24A) |
16 to 31 | Physical fault counter, AS-i slave 57 (25A) | |
0x15D | 0 to 15 | Physical fault counter, AS-i slave 58 (26A) |
16 to 31 | Physical fault counter, AS-i slave 59 (27A) | |
0x15E | 0 to 15 | Physical fault counter, AS-i slave 60 (28A) |
16 to 31 | Physical fault counter, AS-i slave 61 (29A) | |
0x15F | 0 to 15 | Physical fault counter, AS-i slave 62 (30A) |
16 to 31 | Physical fault counter, AS-i slave 63 (31A) |
Parameters 0x160 to 0x17F: Timeout counter
Each AS-i slave has a counter that is incremented if the associated AS-i slave has not responded (this parameter is read/write):
Parameter | Bit | Description |
|---|---|---|
0x160 | 0 to 15 | Timeout counter, AS-i slave 0 |
16 to 31 | Timeout counter, AS-i slave 1 (1A) | |
0x161 | 0 to 15 | Timeout counter, AS-i slave 2 (2A) |
16 to 31 | Timeout counter, AS-i slave 3 (3A) | |
0x162 | 0 to 15 | Timeout counter, AS-i slave 4 (4A) |
16 to 31 | Timeout counter, AS-i slave 5 (5A) | |
0x163 | 0 to 15 | Timeout counter, AS-i slave 6 (6A) |
16 to 31 | Timeout counter, AS-i slave 7 (7A) | |
0x164 | 0 to 15 | Timeout counter, AS-i slave 8 (8A) |
16 to 31 | Timeout counter, AS-i slave 9 (9A) | |
0x165 | 0 to 15 | Timeout counter, AS-i slave 10 (10A) |
16 to 31 | Timeout counter, AS-i slave 11 (11A) | |
0x166 | 0 to 15 | Timeout counter, AS-i slave 12 (12A) |
16 to 31 | Timeout counter, AS-i slave 13 (13A) | |
0x167 | 0 to 15 | Timeout counter, AS-i slave 14 (14A) |
16 to 31 | Timeout counter, AS-i slave 15 (15A) | |
0x168 | 0 to 15 | Timeout counter, AS-i slave 16 (16A) |
16 to 31 | Timeout counter, AS-i slave 17 (17A) | |
0x169 | 0 to 15 | Timeout counter, AS-i slave 18 (18A) |
16 to 31 | Timeout counter, AS-i slave 19 (19A) | |
0x16A | 0 to 15 | Timeout counter, AS-i slave 20 (20A) |
16 to 31 | Timeout counter, AS-i slave 21 (21A) | |
0x16B | 0 to 15 | Timeout counter, AS-i slave 22 (22A) |
16 to 31 | Timeout counter, AS-i slave 23 (23A) | |
0x16C | 0 to 15 | Timeout counter, AS-i slave 24 (24A) |
16 to 31 | Timeout counter, AS-i slave 25 (25A) | |
0x16D | 0 to 15 | Timeout counter, AS-i slave 26 (26A) |
16 to 31 | Timeout counter, AS-i slave 27 (27A) | |
0x16E | 0 to 15 | Timeout counter, AS-i slave 28 (28A) |
16 to 31 | Timeout counter, AS-i slave 29 (29A) | |
0x16F | 0 to 15 | Timeout counter, AS-i slave 30 (30A) |
16 to 31 | Timeout counter, AS-i slave 31 (31A) | |
0x170 | 0 to 15 | Reserved (AS-i slave address 32 is not permitted) |
16 to 31 | Timeout counter, AS-i slave 33 (1B) | |
0x171 | 0 to 15 | Timeout counter, AS-i slave 34 (2B) |
16 to 31 | Timeout counter, AS-i slave 35 (3B) | |
0x172 | 0 to 15 | Timeout counter, AS-i slave 36 (4B) |
16 to 31 | Timeout counter, AS-i slave 37 (5B) | |
0x173 | 0 to 15 | Timeout counter, AS-i slave 38 (6B) |
16 to 31 | Timeout counter, AS-i slave 39 (7B) | |
0x174 | 0 to 15 | Timeout counter, AS-i slave 40 (8B) |
16 to 31 | Timeout counter, AS-i slave 41 (9B) | |
0x175 | 0 to 15 | Timeout counter, AS-i slave 42 (10B) |
16 to 31 | Timeout counter, AS-i slave 43 (11B) | |
0x176 | 0 to 15 | Timeout counter, AS-i slave 44 (12B) |
16 to 31 | Timeout counter, AS-i slave 45 (13B) | |
0x177 | 0 to 15 | Timeout counter, AS-i slave 46 (14B) |
16 to 31 | Timeout counter, AS-i slave 47 (15B) | |
0x178 | 0 to 15 | Timeout counter, AS-i slave 48 (16B) |
16 to 31 | Timeout counter, AS-i slave 49 (17B) | |
0x179 | 0 to 15 | Timeout counter, AS-i slave 50 (18B) |
16 to 31 | Timeout counter, AS-i slave 51 (19B) |
Parameter | Bit | Description |
|---|---|---|
0x17A | 0 to 15 | Timeout counter, AS-i slave 52 (20B) |
16 to 31 | Timeout counter, AS-i slave 53 (21B) | |
0x17B | 0 to 15 | Timeout counter, AS-i slave 54 (22B) |
16 to 31 | Timeout counter, AS-i slave 55 (23B) | |
0x17C | 0 to 15 | Timeout counter, AS-i slave 56 (24B) |
16 to 31 | Timeout counter, AS-i slave 57 (25B) | |
0x17D | 0 to 15 | Timeout counter, AS-i slave 58 (26B) |
16 to 31 | Timeout counter, AS-i slave 59 (27B) | |
0x17E | 0 to 15 | Timeout counter, AS-i slave 60 (28B) |
16 to 31 | Timeout counter, AS-i slave 61 (29B) | |
0x17F | 0 to 15 | Timeout counter, AS-i slave 62 (30B) |
16 to 31 | Timeout counter, AS-i slave 63 (31B) |
Parameters 0x180 to 0x19F: Response counter
Each AS-i slave has a counter that is incremented if the associated AS-i slave has responded correctly (this parameter is read/write):
Parameter | Bit | Description |
|---|---|---|
0x180 | 0 to 15 | Response counter, AS-i slave 0 |
16 to 31 | Response counter, AS-i slave 1 (1A) | |
0x181 | 0 to 15 | Response counter, AS-i slave 2 (2A) |
16 to 31 | Response counter, AS-i slave 3 (3A) | |
0x182 | 0 to 15 | Response counter, AS-i slave 4 (4A) |
16 to 31 | Response counter, AS-i slave 5 (5A) | |
0x183 | 0 to 15 | Response counter, AS-i slave 6 (6A) |
16 to 31 | Response counter, AS-i slave 7 (7A) | |
0x184 | 0 to 15 | Response counter, AS-i slave 8 (8A) |
16 to 31 | Response counter, AS-i slave 9 (9A) | |
0x185 | 0 to 15 | Response counter, AS-i slave 10 (10A) |
16 to 31 | Response counter, AS-i slave 11 (11A) | |
0x186 | 0 to 15 | Response counter, AS-i slave 12 (12A) |
16 to 31 | Response counter, AS-i slave 13 (13A) | |
0x187 | 0 to 15 | Response counter, AS-i slave 14 (14A) |
16 to 31 | Response counter, AS-i slave 15 (15A) | |
0x188 | 0 to 15 | Response counter, AS-i slave 16 (16A) |
16 to 31 | Response counter, AS-i slave 17 (17A) | |
0x189 | 0 to 15 | Response counter, AS-i slave 18 (18A) |
16 to 31 | Response counter, AS-i slave 19 (19A) | |
0x18A | 0 to 15 | Response counter, AS-i slave 20 (20A) |
16 to 31 | Response counter, AS-i slave 21 (21A) | |
0x18B | 0 to 15 | Response counter, AS-i slave 22 (22A) |
16 to 31 | Response counter, AS-i slave 23 (23A) | |
0x18C | 0 to 15 | Response counter, AS-i slave 24 (24A) |
16 to 31 | Response counter, AS-i slave 25 (25A) | |
0x18D | 0 to 15 | Response counter, AS-i slave 26 (26A) |
16 to 31 | Response counter, AS-i slave 27 (27A) | |
0x18E | 0 to 15 | Response counter, AS-i slave 28 (28A) |
16 to 31 | Response counter, AS-i slave 29 (29A) | |
0x18F | 0 to 15 | Response counter, AS-i slave 30 (30A) |
16 to 31 | Response counter, AS-i slave 31 (31A) | |
0x190 | 0 to 15 | Reserved (AS-i slave address 32 is not permitted) |
16 to 31 | Response counter, AS-i slave 33 (1B) | |
0x191 | 0 to 15 | Response counter, AS-i slave 34 (2B) |
16 to 31 | Response counter, AS-i slave 35 (3B) | |
0x192 | 0 to 15 | Response counter, AS-i slave 36 (4B) |
16 to 31 | Response counter, AS-i slave 37 (5B) |
Parameter | Bit | Description |
|---|---|---|
0x193 | 0 to 15 | Response counter, AS-i slave 38 (6B) |
16 to 31 | Response counter, AS-i slave 39 (7B) | |
0x194 | 0 to 15 | Response counter, AS-i slave 40 (8B) |
16 to 31 | Response counter, AS-i slave 41 (9B) | |
0x195 | 0 to 15 | Response counter, AS-i slave 42 (10B) |
16 to 31 | Response counter, AS-i slave 43 (11B) | |
0x196 | 0 to 15 | Response counter, AS-i slave 44 (12B) |
16 to 31 | Response counter, AS-i slave 45 (13B) | |
0x197 | 0 to 15 | Response counter, AS-i slave 46 (14B) |
16 to 31 | Response counter, AS-i slave 47 (15B) | |
0x198 | 0 to 15 | Response counter, AS-i slave 48 (16B) |
16 to 31 | Response counter, AS-i slave 49 (17B) | |
0x199 | 0 to 15 | Response counter, AS-i slave 50 (18B) |
16 to 31 | Response counter, AS-i slave 51 (19B) | |
0x19A | 0 to 15 | Response counter, AS-i slave 52 (20B) |
16 to 31 | Response counter, AS-i slave 53 (21B) | |
0x19B | 0 to 15 | Response counter, AS-i slave 54 (22B) |
16 to 31 | Response counter, AS-i slave 55 (23B) | |
0x19C | 0 to 15 | Response counter, AS-i slave 56 (24B) |
16 to 31 | Response counter, AS-i slave 57 (25B) | |
0x19D | 0 to 15 | Response counter, AS-i slave 58 (26B) |
16 to 31 | Response counter, AS-i slave 59 (27B) | |
0x19E | 0 to 15 | Response counter, AS-i slave 60 (28B) |
16 to 31 | Response counter, AS-i slave 61 (29B) | |
0x19F | 0 to 15 | Response counter, AS-i slave 62 (30B) |
16 to 31 | Response counter, AS-i slave 63 (31B) |
Parameters 0x1A0 to 0x1BF: Leave data exchange counter
Each AS-i slave has a counter that is incremented if the associated AS-i slave was removed from the LAS, i.e. if it has not (or not correctly) responded three times in a row (this parameter is read/write):
Parameter | Bit | Description |
|---|---|---|
0x1A0 | 0 to 15 | Leave data exchange counter, AS-i slave 0 |
16 to 31 | Leave data exchange counter, AS-i slave 1 (1A) | |
0x1A1 | 0 to 15 | Leave data exchange counter, AS-i slave 2 (2A) |
16 to 31 | Leave data exchange counter, AS-i slave 3 (3A) | |
0x1A2 | 0 to 15 | Leave data exchange counter, AS-i slave 4 (4A) |
16 to 31 | Leave data exchange counter, AS-i slave 5 (5A) | |
0x1A3 | 0 to 15 | Leave data exchange counter, AS-i slave 6 (6A) |
16 to 31 | Leave data exchange counter, AS-i slave 7 (7A) | |
0x1A4 | 0 to 15 | Leave data exchange counter, AS-i slave 8 (8A) |
16 to 31 | Leave data exchange counter, AS-i slave 9 (9A) | |
0x1A5 | 0 to 15 | Leave data exchange counter, AS-i slave 10 (10A) |
16 to 31 | Leave data exchange counter, AS-i slave 11 (11A) | |
0x1A6 | 0 to 15 | Leave data exchange counter, AS-i slave 12 (12A) |
16 to 31 | Leave data exchange counter, AS-i slave 13 (13A) | |
0x1A7 | 0 to 15 | Leave data exchange counter, AS-i slave 14 (14A) |
16 to 31 | Leave data exchange counter, AS-i slave 15 (15A) | |
0x1A8 | 0 to 15 | Leave data exchange counter, AS-i slave 16 (16A) |
16 to 31 | Leave data exchange counter, AS-i slave 17 (17A) | |
0x1A9 | 0 to 15 | Leave data exchange counter, AS-i slave 18 (18A) |
16 to 31 | Leave data exchange counter, AS-i slave 19 (19A) | |
0x1AA | 0 to 15 | Leave data exchange counter, AS-i slave 20 (20A) |
16 to 31 | Leave data exchange counter, AS-i slave 21 (21A) | |
0x1AB | 0 to 15 | Leave data exchange counter, AS-i slave 22 (22A) |
16 to 31 | Leave data exchange counter, AS-i slave 23 (23A) |
Parameter | Bit | Description |
|---|---|---|
0x1AC | 0 to 15 | Leave data exchange counter, AS-i slave 24 (24A) |
16 to 31 | Leave data exchange counter, AS-i slave 25 (25A) | |
0x1AD | 0 to 15 | Leave data exchange counter, AS-i slave 26 (26A) |
16 to 31 | Leave data exchange counter, AS-i slave 27 (27A) | |
0x1AE | 0 to 15 | Leave data exchange counter, AS-i slave 28 (28A) |
16 to 31 | Leave data exchange counter, AS-i slave 29 (29A) | |
0x1AF | 0 to 15 | Leave data exchange counter, AS-i slave 30 (30A) |
16 to 31 | Leave data exchange counter, AS-i slave 31 (31A) | |
0x1B0 | 0 to 15 | Reserved (AS-i slave address 32 is not permitted) |
16 to 31 | Leave data exchange counter, AS-i slave 33 (1B) | |
0x1B1 | 0 to 15 | Leave data exchange counter, AS-i slave 34 (2B) |
16 to 31 | Leave data exchange counter, AS-i slave 35 (3B) | |
0x1B2 | 0 to 15 | Leave data exchange counter, AS-i slave 36 (4B) |
16 to 31 | Leave data exchange counter, AS-i slave 37 (5B) | |
0x1B3 | 0 to 15 | Leave data exchange counter, AS-i slave 38 (6B) |
16 to 31 | Leave data exchange counter, AS-i slave 39 (7B) | |
0x1B4 | 0 to 15 | Leave data exchange counter, AS-i slave 40 (8B) |
16 to 31 | Leave data exchange counter, AS-i slave 41 (9B) | |
0x1B5 | 0 to 15 | Leave data exchange counter, AS-i slave 42 (10B) |
16 to 31 | Leave data exchange counter, AS-i slave 43 (11B) | |
0x1B6 | 0 to 15 | Leave data exchange counter, AS-i slave 44 (12B) |
16 to 31 | Leave data exchange counter, AS-i slave 45 (13B) | |
0x1B7 | 0 to 15 | Leave data exchange counter, AS-i slave 46 (14B) |
16 to 31 | Leave data exchange counter, AS-i slave 47 (15B) | |
0x1B8 | 0 to 15 | Leave data exchange counter, AS-i slave 48 (16B) |
16 to 31 | Leave data exchange counter, AS-i slave 49 (17B) | |
0x1B9 | 0 to 15 | Leave data exchange counter, AS-i slave 50 (18B) |
16 to 31 | Leave data exchange counter, AS-i slave 51 (19B) | |
0x1BA | 0 to 15 | Leave data exchange counter, AS-i slave 52 (20B) |
16 to 31 | Leave data exchange counter, AS-i slave 53 (21B) | |
0x1BB | 0 to 15 | Leave data exchange counter, AS-i slave 54 (22B) |
16 to 31 | Leave data exchange counter, AS-i slave 55 (23B) | |
0x1BC | 0 to 15 | Leave data exchange counter, AS-i slave 56 (24B) |
16 to 31 | Leave data exchange counter, AS-i slave 57 (25B) | |
0x1BD | 0 to 15 | Leave data exchange counter, AS-i slave 58 (26B) |
16 to 31 | Leave data exchange counter, AS-i slave 59 (27B) | |
0x1BE | 0 to 15 | Leave data exchange counter, AS-i slave 60 (28B) |
16 to 31 | Leave data exchange counter, AS-i slave 61 (29B) | |
0x1BF | 0 to 15 | Leave data exchange counter, AS-i slave 62 (30B) |
16 to 31 | Leave data exchange counter, AS-i slave 63 (31B) |
Parameters 0x1C0 to 0x1DF: DataExch failed counter
Each AS-i slave has a counter that is incremented if the associated AS-i slave has not (or not correctly) responded to a DataExchange telegram (this parameter is read/write):
Parameter | Bit | Description |
|---|---|---|
0x1C0 | 0 to 15 | DataExch failed counter, AS-i slave 0 |
16 to 31 | DataExch failed counter, AS-i slave 1 (1A) | |
0x1C1 | 0 to 15 | DataExch failed counter, AS-i slave 2 (2A) |
16 to 31 | DataExch failed counter, AS-i slave 3 (3A) | |
0x1C2 | 0 to 15 | DataExch failed counter, AS-i slave 4 (4A) |
16 to 31 | DataExch failed counter, AS-i slave 5 (5A) | |
0x1C3 | 0 to 15 | DataExch failed counter, AS-i slave 6 (6A) |
16 to 31 | DataExch failed counter, AS-i slave 7 (7A) | |
0x1C4 | 0 to 15 | DataExch failed counter, AS-i slave 8 (8A) |
16 to 31 | DataExch failed counter, AS-i slave 9 (9A) |
Parameter | Bit | Description |
|---|---|---|
0x1C5 | 0 to 15 | DataExch failed counter, AS-i slave 10 (10A) |
16 to 31 | DataExch failed counter, AS-i slave 11 (11A) | |
0x1C6 | 0 to 15 | DataExch failed counter, AS-i slave 12 (12A) |
16 to 31 | DataExch failed counter, AS-i slave 13 (13A) | |
0x1C7 | 0 to 15 | DataExch failed counter, AS-i slave 14 (14A) |
16 to 31 | DataExch failed counter, AS-i slave 15 (15A) | |
0x1C8 | 0 to 15 | DataExch failed counter, AS-i slave 16 (16A) |
16 to 31 | DataExch failed counter, AS-i slave 17 (17A) | |
0x1C9 | 0 to 15 | DataExch failed counter, AS-i slave 18 (18A) |
16 to 31 | DataExch failed counter, AS-i slave 19 (19A) | |
0x1CA | 0 to 15 | DataExch failed counter, AS-i slave 20 (20A) |
16 to 31 | DataExch failed counter, AS-i slave 21 (21A) | |
0x1CB | 0 to 15 | DataExch failed counter, AS-i slave 22 (22A) |
16 to 31 | DataExch failed counter, AS-i slave 23 (23A) | |
0x1CC | 0 to 15 | DataExch failed counter, AS-i slave 24 (24A) |
16 to 31 | DataExch failed counter, AS-i slave 25 (25A) | |
0x1CD | 0 to 15 | DataExch failed counter, AS-i slave 26 (26A) |
16 to 31 | DataExch failed counter, AS-i slave 27 (27A) | |
0x1CE | 0 to 15 | DataExch failed counter, AS-i slave 28 (28A) |
16 to 31 | DataExch failed counter, AS-i slave 29 (29A) | |
0x1CF | 0 to 15 | DataExch failed counter, AS-i slave 30 (30A) |
16 to 31 | DataExch failed counter, AS-i slave 31 (31A) | |
0x1C0 | 0 to 15 | Reserved (AS-i slave address 32 is not permitted) |
16 to 31 | DataExch failed counter, AS-i slave 33 (1B) | |
0x1D1 | 0 to 15 | DataExch failed counter, AS-i slave 34 (2B) |
16 to 31 | DataExch failed counter, AS-i slave 35 (3B) | |
0x1D2 | 0 to 15 | DataExch failed counter, AS-i slave 36 (4B) |
16 to 31 | DataExch failed counter, AS-i slave 37 (5B) | |
0x1D3 | 0 to 15 | DataExch failed counter, AS-i slave 38 (6B) |
16 to 31 | DataExch failed counter, AS-i slave 39 (7B) | |
0x1D4 | 0 to 15 | DataExch failed counter, AS-i slave 40 (8B) |
16 to 31 | DataExch failed counter, AS-i slave 41 (9B) | |
0x1D5 | 0 to 15 | DataExch failed counter, AS-i slave 42 (10B) |
16 to 31 | DataExch failed counter, AS-i slave 43 (11B) | |
0x1D6 | 0 to 15 | DataExch failed counter, AS-i slave 44 (12B) |
16 to 31 | DataExch failed counter, AS-i slave 45 (13B) | |
0x1D7 | 0 to 15 | DataExch failed counter, AS-i slave 46 (14B) |
16 to 31 | DataExch failed counter, AS-i slave 47 (15B) | |
0x1D8 | 0 to 15 | DataExch failed counter, AS-i slave 48 (16B) |
16 to 31 | DataExch failed counter, AS-i slave 49 (17B) | |
0x1D9 | 0 to 15 | DataExch failed counter, AS-i slave 50 (18B) |
16 to 31 | DataExch failed counter, AS-i slave 51 (19B) | |
0x1DA | 0 to 15 | DataExch failed counter, AS-i slave 52 (20B) |
16 to 31 | DataExch failed counter, AS-i slave 53 (21B) | |
0x1DB | 0 to 15 | DataExch failed counter, AS-i slave 54 (22B) |
16 to 31 | DataExch failed counter, AS-i slave 55 (23B) | |
0x1DC | 0 to 15 | DataExch failed counter, AS-i slave 56 (24B) |
16 to 31 | DataExch failed counter, AS-i slave 57 (25B) | |
0x1DD | 0 to 15 | DataExch failed counter, AS-i slave 58 (26B) |
16 to 31 | DataExch failed counter, AS-i slave 59 (27B) | |
0x1DE | 0 to 15 | DataExch failed counter, AS-i slave 60 (28B) |
16 to 31 | DataExch failed counter, AS-i slave 61 (29B) | |
0x1DF | 0 to 15 | DataExch failed counter, AS-i slave 62 (30B) |
16 to 31 | DataExch failed counter, AS-i slave 63 (31B) |
Parameters 0x200 to 0x27F: Analog slave data
Parameter | Bit | Description | ||||||
|---|---|---|---|---|---|---|---|---|
Channel | if analog output | if analog input | ||||||
Write | Read | Read | Write | |||||
0x200 | Bit 0 to 31 | (Slave 0) | Since slave no. 0 is not designated for analog AS-i slaves, zeros are transferred to the process image in this instance. | |||||
0x201 | Bit 0 to 31 | |||||||
0x202 | Bit 0 to 31 | |||||||
0x203 | Bit 0 to 31 | |||||||
0x204 | Bit 0 to 15 | Slave 1, channel 1 | Analog value | - | Analog value | not possible | ||
Bit 16 | V flag** (valid) | V flag (valid) | V flag (valid) | |||||
Bit 17 | - | - | O flag (overflow) | |||||
Bit 21 | - | No Response | No Response | |||||
Bit 22 | - | Toggle timeout | Toggle timeout | |||||
Bit 23 | - | Data exchange disabled* | Data exchange disabled* | |||||
0x205 | Bit 0 to 15 | Slave 1, channel 2 | Analog value | - | Analog value | not possible | ||
Bit 16 | V flag** (valid) | V flag (valid) | V flag (valid) | |||||
Bit 17 | - | - | O flag (overflow) | |||||
Bit 21 | - | No Response | No Response | |||||
Bit 22 | - | Toggle timeout | Toggle timeout | |||||
Bit 23 | - | Data exchange disabled* | Data exchange disabled* | |||||
0x206 | Bit 0 to 15 | Slave 1, channel 3 | Analog value | - | Analog value | not possible | ||
Bit 16 | V flag** (valid) | V flag (valid) | V flag (valid) | |||||
Bit 17 | - | - | O flag (overflow) | |||||
Bit 21 | - | No Response | No Response | |||||
Bit 22 | - | Toggle timeout | Toggle timeout | |||||
Bit 23 | - | Data exchange disabled* | Data exchange disabled* | |||||
0x207 | Bit 0 to 15 | Slave 1, channel 4 | Analog value | - | Analog value | not possible | ||
Bit 16 | V flag** (valid) | V flag (valid) | V flag (valid) | |||||
Bit 17 | - | - | O flag (overflow) | |||||
Bit 21 | - | No Response | No Response | |||||
Bit 22 | - | Toggle timeout | Toggle timeout | |||||
Bit 23 | - | Data exchange disabled* | Data exchange disabled* | |||||
... | ... | ... | ... | ... | ... | ... | ||
0x27C | ... | Slave 31, channel 1 | ... | ... | ... | ... | ||
0x27D | ... | Slave 31, channel 2 | ... | ... | ... | ... | ||
0x27E | ... | Slave 31, channel 3 | ... | ... | ... | |||
0x27F | ... | Slave 31, channel 4 | ... | ... | ... | ... | ||
*) if ASI control bit 3 = 0bin
**) The V flag (valid) must be set by the controller in order for the AS-i slave to switch its outputs.
Parameter 0x300: Cycle times
Parameter | Bit | Description |
|---|---|---|
0x300 | Bits 0-15 | current cycle time in µs |
Bits 16-31 | maximum cycle time in µs |
Parameter 0x310: Statistics
Parameter | Bit | Description |
|---|---|---|
0x310 | Bits 0-7 | Max. number of data exchange errors per ASI cycle |
Bits 8-15 | Timeouts/data exchange telegrams in % | |
Bits 16-31 | reserved |
Parameters 0x320 to 0x32F: Timeout statistics for each AS-i slave
Parameter | Bit | Description |
|---|---|---|
0x320 | Bit 0 to 7 | Timeouts/telegram in percent, AS-i slave 0 |
Bit 8 to 15 | Timeouts/telegram in percent, AS-i slave 1 (1A) | |
Bit 16 to 23 | Timeouts/telegram in percent, AS-i slave 2 (2A) | |
Bit 24 to 31 | Timeouts/telegram in percent, AS-i slave 3 (3A) | |
0x321 | Bit 0 to 7 | Timeouts/telegram in percent, AS-i slave 4 (4A) |
Bit 8 to 15 | Timeouts/telegram in percent, AS-i slave 5 (5A) | |
Bit 16 to 23 | Timeouts/telegram in percent, AS-i slave 6 (6A) | |
Bit 24 to 31 | Timeouts/telegram in percent, AS-i slave 7 (7A) | |
0x322 | Bit 0 to 7 | Timeouts/telegram in percent, AS-i slave 8 (8A) |
Bit 8 to 15 | Timeouts/telegram in percent, AS-i slave 9 (9A) | |
Bit 16 to 23 | Timeouts/telegram in percent, AS-i slave 10 (10A) | |
Bit 24 to 31 | Timeouts/telegram in percent, AS-i slave 11 (11A) | |
0x323 | Bit 0 to 7 | Timeouts/telegram in percent, AS-i slave 12 (12A) |
Bit 8 to 15 | Timeouts/telegram in percent, AS-i slave 13 (13A) | |
Bit 16 to 23 | Timeouts/telegram in percent, AS-i slave 14 (14A) | |
Bit 24 to 31 | Timeouts/telegram in percent, AS-i slave 15 (15A) | |
0x324 | Bit 0 to 7 | Timeouts/telegram in percent, AS-i slave 16 (16A) |
Bit 8 to 15 | Timeouts/telegram in percent, AS-i slave 17 (17A) | |
Bit 16 to 23 | Timeouts/telegram in percent, AS-i slave 18 (18A) | |
Bit 24 to 31 | Timeouts/telegram in percent, AS-i slave 19 (19A) | |
0x325 | Bit 0 to 7 | Timeouts/telegram in percent, AS-i slave 20 (20A) |
Bit 8 to 15 | Timeouts/telegram in percent, AS-i slave 21 (21A) | |
Bit 16 to 23 | Timeouts/telegram in percent, AS-i slave 22 (22A) | |
Bit 24 to 31 | Timeouts/telegram in percent, AS-i slave 23 (23A) | |
0x326 | Bit 0 to 7 | Timeouts/telegram in percent, AS-i slave 24 (24A) |
Bit 8 to 15 | Timeouts/telegram in percent, AS-i slave 25 (25A) | |
Bit 16 to 23 | Timeouts/telegram in percent, AS-i slave 26 (26A) | |
Bit 24 to 31 | Timeouts/telegram in percent, AS-i slave 27 (27A) | |
0x327 | Bit 0 to 7 | Timeouts/telegram in percent, AS-i slave 28 (28A) |
Bit 8 to 15 | Timeouts/telegram in percent, AS-i slave 29 (29A) | |
Bit 16 to 23 | Timeouts/telegram in percent, AS-i slave 30 (30A) | |
Bit 24 to 31 | Timeouts/telegram in percent, AS-i slave 31 (31A) | |
0x328 | Bit 0 to 7 | Reserved (AS-i slave address 32 is not permitted) |
Bit 8 to 15 | Timeouts/telegram in percent, AS-i slave 33 (1B) | |
Bit 16 to 23 | Timeouts/telegram in percent, AS-i slave 34 (2B) | |
Bit 24 to 31 | Timeouts/telegram in percent, AS-i slave 35 (3B) | |
0x329 | Bit 0 to 7 | Timeouts/telegram in percent, AS-i slave 36 (4B) |
Bit 8 to 15 | Timeouts/telegram in percent, AS-i slave 37 (5B) | |
Bit 16 to 23 | Timeouts/telegram in percent, AS-i slave 38 (6B) | |
Bit 24 to 31 | Timeouts/telegram in percent, AS-i slave 39 (7B) | |
0x32A | Bit 0 to 7 | Timeouts/telegram in percent, AS-i slave 40 (8B) |
Bit 8 to 15 | Timeouts/telegram in percent, AS-i slave 41 (9B) | |
Bit 16 to 23 | Timeouts/telegram in percent, AS-i slave 42 (10B) | |
Bit 24 to 31 | Timeouts/telegram in percent, AS-i slave 43 (11B) | |
0x32B | Bit 0 to 7 | Timeouts/telegram in percent, AS-i slave 44 (12B) |
Bit 8 to 15 | Timeouts/telegram in percent, AS-i slave 45 (13B) | |
Bit 16 to 23 | Timeouts/telegram in percent, AS-i slave 46 (14B) | |
Bit 24 to 31 | Timeouts/telegram in percent, AS-i slave 47 (15B) | |
0x32C | Bit 0 to 7 | Timeouts/telegram in percent, AS-i slave 48 (16B) |
Bit 8 to 15 | Timeouts/telegram in percent, AS-i slave 49 (17B) | |
Bit 16 to 23 | Timeouts/telegram in percent, AS-i slave 50 (18B) | |
Bit 24 to 31 | Timeouts/telegram in percent, AS-i slave 51 (19B) | |
0x32D | Bit 0 to 7 | Timeouts/telegram in percent, AS-i slave 52 (20B) |
Bit 8 to 15 | Timeouts/telegram in percent, AS-i slave 53 (21B) | |
Bit 16 to 23 | Timeouts/telegram in percent, AS-i slave 54 (22B) | |
Bit 24 to 31 | Timeouts/telegram in percent, AS-i slave 55 (23B) |
Parameter | Bit | Description | |
|---|---|---|---|
0x32E | Bit 0 to 7 | Timeouts/telegram in percent, AS-i slave 56 (24B) | |
Bit 8 to 15 | Timeouts/telegram in percent, AS-i slave 57 (25B) | ||
Bit 16 to 23 | Timeouts/telegram in percent, AS-i slave 58 (26B) | ||
Bit 24 to 31 | Timeouts/telegram in percent, AS-i slave 59 (27B) | ||
0x32F | Bit 0 to 7 | Timeouts/telegram in percent, AS-i slave 60 (28B) | |
Bit 8 to 15 | Timeouts/telegram in percent, AS-i slave 61 (29B) | ||
Bit 16 to 23 | Timeouts/telegram in percent, AS-i slave 62 (30B) | ||
Bit 24 to 31 | Timeouts/telegram in percent, AS-i slave 63 (31B) | ||
Parameters 0x340 to 0x35F: Data exchange repeat counter for each AS-i slave
There are 5 repeat counters, since the data exchange telegram is sent up to six times before the slave is removed from the LAS - the maximum number of repeats is therefore five. The counters indicate how often one, two, three, four or five repetitions were required:
- If, for example, the slave started responding after the 4th repetition, the repeat counter will have been incremented three times.
- If the slave does not respond six times, it is removed from the LAS, and none of the repeat counter is incremented.
The general command interface (parameter 0x108) determines which of the 5 repeat counters is addressed via parameters 0x340 to 0x35F (switchover of x).
Parameter | Bit | Description |
|---|---|---|
0x340 | 0 to 15 | reserved |
16 to 31 | Data exchange repeat counter x, AS-i slave 1 (1A) | |
0x341 | 0 to 15 | Data exchange repeat counter x, AS-i slave 2 (2A) |
16 to 31 | Data exchange repeat counter x, AS-i slave 3 (3A) | |
0x342 | 0 to 15 | Data exchange repeat counter x, AS-i slave 4 (4A) |
16 to 31 | Data exchange repeat counter x, AS-i slave 5 (5A) | |
0x343 | 0 to 15 | Data exchange repeat counter x, AS-i slave 6 (6A) |
16 to 31 | Data exchange repeat counter x, AS-i slave 7 (7A) | |
0x344 | 0 to 15 | Data exchange repeat counter x, AS-i slave 8 (8A) |
16 to 31 | Data exchange repeat counter x, AS-i slave 9 (9A) | |
0x345 | 0 to 15 | Data exchange repeat counter x, AS-i slave 10 (10A) |
16 to 31 | Data exchange repeat counter x, AS-i slave 11 (11A) | |
0x346 | 0 to 15 | Data exchange repeat counter x, AS-i slave 12 (12A) |
16 to 31 | Data exchange repeat counter x, AS-i slave 13 (13A) | |
0x347 | 0 to 15 | Data exchange repeat counter x, AS-i slave 14 (14A) |
16 to 31 | Data exchange repeat counter x, AS-i slave 15 (15A) | |
0x348 | 0 to 15 | Data exchange repeat counter x, AS-i slave 16 (16A) |
16 to 31 | Data exchange repeat counter x, AS-i slave 17 (17A) | |
0x349 | 0 to 15 | Data exchange repeat counter x, AS-i slave 18 (18A) |
16 to 31 | Data exchange repeat counter x, AS-i slave 19 (19A) | |
0x34A | 0 to 15 | Data exchange repeat counter x, AS-i slave 20 (20A) |
16 to 31 | Data exchange repeat counter x, AS-i slave 21 (21A) | |
0x34B | 0 to 15 | Data exchange repeat counter x, AS-i slave 22 (22A) |
16 to 31 | Data exchange repeat counter x, AS-i slave 23 (23A) | |
0x34C | 0 to 15 | Data exchange repeat counter x, AS-i slave 24 (24A) |
16 to 31 | Data exchange repeat counter x, AS-i slave 25 (25A) | |
0x34D | 0 to 15 | Data exchange repeat counter x, AS-i slave 26 (26A) |
16 to 31 | Data exchange repeat counter x, AS-i slave 27 (27A) | |
0x34E | 0 to 15 | Data exchange repeat counter x, AS-i slave 28 (28A) |
16 to 31 | Data exchange repeat counter x, AS-i slave 29 (29A) | |
0x34F | 0 to 15 | Data exchange repeat counter x, AS-i slave 30 (30A) |
16 to 31 | Data exchange repeat counter x, AS-i slave 31 (31A) |
Parameter | Bit | Description |
|---|---|---|
0x340 | 0 to 15 | Reserved (AS-i slave address 32 is not permitted) |
16 to 31 | Data exchange repeat counter x, AS-i slave 33 (1B) | |
0x351 | 0 to 15 | Data exchange repeat counter x, AS-i slave 34 (2B) |
16 to 31 | Data exchange repeat counter x, AS-i slave 35 (3B) | |
0x352 | 0 to 15 | Data exchange repeat counter x, AS-i slave 36 (4B) |
16 to 31 | Data exchange repeat counter x, AS-i slave 37 (5B) | |
0x353 | 0 to 15 | Data exchange repeat counter x, AS-i slave 38 (6B) |
16 to 31 | Data exchange repeat counter x, AS-i slave 39 (7B) | |
0x354 | 0 to 15 | Data exchange repeat counter x, AS-i slave 40 (8B) |
16 to 31 | Data exchange repeat counter x, AS-i slave 41 (9B) | |
0x355 | 0 to 15 | Data exchange repeat counter x, AS-i slave 42 (10B) |
16 to 31 | Data exchange repeat counter x, AS-i slave 43 (11B) | |
0x356 | 0 to 15 | Data exchange repeat counter x, AS-i slave 44 (12B) |
16 to 31 | Data exchange repeat counter x, AS-i slave 45 (13B) | |
0x357 | 0 to 15 | Data exchange repeat counter x, AS-i slave 46 (14B) |
16 to 31 | Data exchange repeat counter x, AS-i slave 47 (15B) | |
0x358 | 0 to 15 | Data exchange repeat counter x, AS-i slave 48 (16B) |
16 to 31 | Data exchange repeat counter x, AS-i slave 49 (17B) | |
0x359 | 0 to 15 | Data exchange repeat counter x, AS-i slave 50 (18B) |
16 to 31 | Data exchange repeat counter x, AS-i slave 51 (19B) | |
0x35A | 0 to 15 | Data exchange repeat counter x, AS-i slave 52 (20B) |
16 to 31 | Data exchange repeat counter x, AS-i slave 53 (21B) | |
0x35B | 0 to 15 | Data exchange repeat counter x, AS-i slave 54 (22B) |
16 to 31 | Data exchange repeat counter x, AS-i slave 55 (23B) | |
0x35C | 0 to 15 | Data exchange repeat counter x, AS-i slave 56 (24B) |
16 to 31 | Data exchange repeat counter x, AS-i slave 57 (25B) | |
0x35D | 0 to 15 | Data exchange repeat counter x, AS-i slave 58 (26B) |
16 to 31 | Data exchange repeat counter x, AS-i slave 59 (27B) | |
0x35E | 0 to 15 | Data exchange repeat counter x, AS-i slave 60 (28B) |
16 to 31 | Data exchange repeat counter x, AS-i slave 61 (29B) | |
0x35F | 0 to 15 | Data exchange repeat counter x, AS-i slave 62 (30B) |
16 to 31 | Data exchange repeat counter x, AS-i slave 63 (31B) |