22-byte process image

For AS-i networks, in which slave addresses between 12 and 31 are used, the 22-byte process image is required for direct access to the process data of these AS-i slaves.

Input data (KL6201/KL6211 -> PLC)

Parameter data block (6 bytes)

Process data block (16 bytes)

Byte 0

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

Byte 8

...

Byte 21

SB0

SB1

ParaIn0

ParaIn1

ParaIn2

ParaIn3

ASiSN
+ ASiIn
Slave 1

ASiIn
Slaves
2+3

ASiIn
Slaves
4+5

...

ASiIn
Slaves
30+31

Output data (PLC -> KL6201/KL6211)

Parameter data block (6 bytes)

Process data block (16 bytes)

Byte 0

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

Byte 8

...

Byte 21

CB0

CB1

ParaOut0

ParaOut1

ParaOut2

ParaOut3

ASiCN
+ ASiOut
Slave 1

ASiOut
Slaves
2+3

ASiOut
Slaves
4+5

...

ASiOut
Slaves
30+31

Key

CB n: control byte n
SB n: status byte n
Para In n: Input parameter, byte n
Para Out n: Output parameter, byte n
ASiSN: AS-i status nibble
ASiCN: AS-i command nibble
ASiIn slave x+y: Input data of the AS-i slaves x and y (one nibble per slave)
ASiOut slave x+y: Output data of the AS-i slaves x and y (one nibble per slave)